Changing the Batteries

Outdoor Unit

FIG 11

Loss of  Comunication Mode

The Loss of  Communication mode occurs when the 

base unit has lost communication with the outdoor unit 

for more than 3 hours. 

When the WAV-0110 is in this mode, the base unit will 

output a resistance for 0°F on the control it has been 

connected to. 

The base unit will indicate that it is in this mode by 

blinking both LED’s , five times every three seconds 

(see FIG 12).

FIG 12

Loss of  Communication Troubleshooting

Step 1 

Disconnect power from the base unit for 30 seconds and 

reconnect it. Once the unit is powered back up it can take 

up to 15 minutes for the outdoor unit to communicate with 

the base unit. During this time you will still be in “Loss of 

Communication” mode. If  you do not wish to wait UP TO 

15 minutes, you can go to the outdoor sensor and press the 

button, (referred to on page 7) which will force the outdoor 

unit to send a temperature to the base unit. If after trying 

this step the base unit is still in “Loss of Communication” 
mode, proceed to Step 2.

Step 2

Remove the cover from the outdoor unit and press the 

button. The RED LED should light up when the button is 

pressed. If  it does not or is very dim this indicates that the 

batteries are dead and need to be changed. If  after trying 

this step the base unit is still in “Loss of Communication” 

mode, proceed to Step 3.

Step 3

Try powering down the outdoor sensor by taking out one 

battery for 30 seconds. After re-inserting the battery wait 

15 seconds then press the button on the unit. If  after trying 

this step the base unit is still in “Loss of Communication” 

mode, proceed to Step 4.

Step 4

Try re-pairing the units. See page 7 for instructions. 

If  after trying this step the base unit is still in Loss of 

Communication mode, proceed to Step 5.

Step 5

Call HBX Tech support:

Flip Forward and Out

Flip and Replace Batteries

Signal

Power

Telephone: +1 (403) 720 0029

Fax: +1 (403) 720 0054

[email protected]

Содержание WAV-0110

Страница 1: ...Page 1 HBX Control Systems Inc WAV 0112 WAV 0111 WAV 0110 Installation Manual WAV 0110 WAV 0111 WAV 0112 Version 1 005...

Страница 2: ...o Safety Symbols and Warnings 3 o Receiving Inspection and Storage 3 o Description 4 o Technical Data and Dimensions 5 Installation and Wiring 6 8 o Mounting and Wiring 6 o Setting the Dipswitches 6 o...

Страница 3: ...rsonal injury or have adverse effects on the installation process if handled incorrectly Disconnect Power Source The presence of low voltage 24VAC or high voltage 120VAC could result in personal injur...

Страница 4: ...0 are Temperature range 20 F to 225 F operating temperature range down to 40 F Proprietary pairing and communication protocol 500 5k 10k 20k Ohm thermistor options built in dipswitch selectable Provid...

Страница 5: ...MB Contains FFC ID 0A3MRF24J40MB Dimensions OZ OZ THERM OUT 24 VAC GND Signal Power OZ OZ THERM OUT 24 VAC GND 116 mm 78 mm 114 mm 76 mm Front View Outdoor Sensor Inside View Indoor Sensor Inside View...

Страница 6: ...r Vitodens 200 setup Dip 1 ON only 500 Ohms Dip 2 ON only 5k Ohms Both ON 20k Ohms Both OFF 10k Ohms Default Setting ON ON ON ON ON ON ON ON Dip 1 ON only 500 Ohms Dip 2 ON only 5k Ohms Both ON 20k Oh...

Страница 7: ...ed on the outdoor sensor until the red LED light turns off approx 15 seconds then release the button The LED will switch back on after a few seconds as it is initiating the pairing process see FIG 6 O...

Страница 8: ...also at least 1 foot away from any metal in all directions so there is not interference with the wireless sensor FIG 9 Do not mount the outdoor sensor with the conduit knockout facing upwards as rain...

Страница 9: ...or sensor and press the button referred to on page 7 which will force the outdoor unit to send a temperature to the base unit If after trying this step the base unit is still in Loss of Communication...

Страница 10: ...64129 5 41 53777 8 47 45249 9 49 42750 13 55 36111 16 61 30615 19 67 26037 23 73 22200 26 79 18994 29 85 16297 33 91 14016 Temp C Temp F Resistance Ohms Dip 1 ON only 500 Ohms Dip 2 ON only 5k Ohms B...

Страница 11: ...d above the purchasers sole remedy shall be at HBX s option repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in...

Страница 12: ...Page 12 HBX Control Systems Inc 2015 Phone 1 403 720 0029 Fax 1 403 720 0054 Email info hbxcontrols com Web www hbxcontrols com HBX Control Systems Inc 4516 112th Avenue SE Calgary AB Canada T2C 2K2...

Отзывы: