Backlight

Toggling this option will turn the backlight feature 

either on or off. Allow approximately 60 seconds 

for the backlight to power off.

B

oiler

 a

Djustments

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

6°F

5) WWSD 

 

72°F

6) DHW PRTY  

OFF

Boiler Adjustments

The “Boiler Adjustments” screen is applicable to the 

“Boiler” option which is selected within the “Special 

Functions” screen, enter the “Boiler Adjustments” 

screen by holding down the set button after 

selecting “Boiler”.

     Maximum Boiler Temperature

“Maximum Boiler Temperature” is used in the 

outdoor reset design calculation, and also serves as 

the maximum setting for the boiler.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

10°F

5) WWSD 

 

72°F

6) DHW PRTY  

OFF

     Minimum Boiler Temperature

Reduces the risk of condensing flue gases. It can run 

with both condensing, and non-condensing boilers. 

Setup as per boiler manufacturers recommendation.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

10°F

5) WWSD 

 

72°F

6) DHW PRTY  

OFF

     Outdoor Design Temperature

The “Outdoor Design Temperature” option should 

be set to reflect your specific city or region. It factors 

into the outdoor reset curve calculation.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

10°F

5) WWSD 

 

72°F

6) DHW PRTY  

OFF

     Differential

A differential of 10° is 5° above setpoint and 5° 

below setpoint.

 Range from 2°F to 60°F.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

10°F

5) WWSD 

 

72°F

6) DHW PRTY  

OFF

     Warm Weather Shutdown

“Warm Weather Shutdown” is the outdoor 

temperature that must be reached for the control 

to enter an energy-saving hibernation mode.

BOILER ADJUSTMENTS

1) MAX BOILER 

190°F

2) MIN BOILER 

120°F

3) OUT DESIGN 

-10°F

4) DIFF 

 

10°F

5) WWSD 

 

72°F

6) DHW PRTY  

OFF

5) SENSOR1   

NONE

6) SENSOR2   

NONE

7) CONT FAN  

OFF

8) TIME 

 

5:53am

9) DAY 

 

MON

10) BACKLIGHT  ON

ADJUSTMENTS

Содержание THM-0200

Страница 1: ...HBX Control Systems Inc Installation Manual THM 0200 Programmable Thermostat Version 1 07 THM 0200...

Страница 2: ...ith the codes and practices applicable to the jurisdiction for the actual installation The HBX THM 0200 is a microprocessor based controller and as such is not to be regarded as a safety limit control...

Страница 3: ...evening and sleep and weekend settings The THM 0200 has two external sensor inputs and multiple heating and cooling modes and can function as a single boiler reset control Some features of the THM 020...

Страница 4: ...tons simultaneously for 5 seconds from the Status Screen To select the desired option use the and buttons to toggle and the set button to select 1 Type SelectbetweenHeating Cooling Boiler andavarietyo...

Страница 5: ...SPECIAL FUNCTIONS 2 Cool Heat Function Select the 2 Cool Heat Function for applications using 2 stage cooling and 1 stage heating See diagram 8 for wiring example 1 TYPE 2COOL HEAT 2 C OR F F 3 VIEW A...

Страница 6: ...witched from heat to cool as the air crosses a certain temperature Auto changeover switches from heat to cool automatically while manual changeover thermostats must be changed by hand If you select NO...

Страница 7: ...the previous screen START HEAT 1 6 00A 74 F 2 8 00A 64 F 3 4 30P 72 F 4 9 00P 90 F 5 BACK WEEKDAY PROGRAMS Weekend Programs Adjust four time periods within the two weekend program menu The Back option...

Страница 8: ...RM Ave averages external 1 and internal sensor Floor displays the floor temperature using external 1 sensor 1 WEEKDAY 2 WEEKEND 3 HOLD TEMP 76 F 4 MODE ROOM 5 SENSOR1 NONE 6 SENSOR2 NONE ADJUSTMENTS R...

Страница 9: ...s external 1 2 sensors using floor temperature Outdoor will use external 2 sensor to display outdoor temperature 2 WEEKEND 3 HOLD TEMP OFF 4 MODE FLOOR 5 DIFF 6 F 6 SENSOR1 FLOOR 7 SENSOR2 OUTDOOR ADJ...

Страница 10: ...al sensor uses external sensor 2 4 MODE DUAL 5 FLOOR MAX 78 F 6 FLOOR MIN 69 F 7 SENSOR 1 FLOOR 8 SENSOR 2 NONE 9 TIME 5 18AM ADJUSTMENTS Dual Mode Continuous Fan ON Enables the fan to run continuousl...

Страница 11: ...both condensing and non condensing boilers Setupasperboilermanufacturersrecommendation BOILER ADJUSTMENTS 1 MAX BOILER 190 F 2 MIN BOILER 120 F 3 OUT DESIGN 10 F 4 DIFF 10 F 5 WWSD 72 F 6 DHW PRTY OFF...

Страница 12: ...g Examples 5 4 3 2 1 6 7 8 9 10 1 2 3 Output 1 and 2 4 5 Dry Contact Output 6 7 8 External Therm 1 and 2 9 10 Power In the following examples extra thermistors are not needed on pins 6 8 and 7 8 These...

Страница 13: ...R HERE TH 1 6 RL 1 2 A 1 Y G THM 0200 Thermostat Transformer R C 24VAC 3 Room Only Cooling Fan THM 0200 HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWE...

Страница 14: ...2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWER HERE TH 1 6 RL 1 2 A 1 Heat Fan Cool Transformer R C 24VAC 4 Heating and Cooling Fan HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 RL 1...

Страница 15: ...2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWER HERE TH 1 6 RL 1 2 A 1 Transformer R C 24VAC HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 RL 1 RL 5 4 1 2 A DO NOT CO...

Страница 16: ...s a 30 second pre purge and 60 second post purge Boiler Enable Outdoor Sensor Boiler Sensor Transformer R C 24VAC 9 Boiler THM 0200 HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5...

Страница 17: ...15 NOTES...

Страница 18: ...2014 HBX Controls 16 NOTES...

Страница 19: ...on repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in fact or by operation of law statutory or otherwise inclu...

Страница 20: ...V1 02 Toll Free Technical Support 1 855 554 6629...

Отзывы: