This setting is used to configure the pump(s)
component in your system.
• Pump 1- The chosen pump type will close the
lower contact at 1-2 (PUMP1) when a demand is
in place. Pump choice options: System, System 2,
App, None
• Pump 1 Post Purge (0 -240 seconds) the amount
of time if necessary for Pump 1 to run after the call
associated with it has been removed.
• Pump 1 Start Delay (0 -240 seconds) the amount
of time if necessary for Pump 1 be delayed to
run after the call associated with it has been
activated.
• Pump 2- The chosen pump type will close the
lower contact at 3-4 (PUMP2) when a demand is
in place. Pump choice options: System, System 2,
App, None
• Pump 2 Post Purge (0 -240 seconds) the amount
of time if necessary for Pump2 to run after the call
associated with it has been removed.
• Pump 2 Start Delay (0 -240 seconds) the amount
of time if necessary for Pump 2 be delayed to
run after the call associated with it has been
activated.
• Pump 3- The chosen pump type will close the
lower contact at 3-4 (PUMP2) when a demand is
in place. Pump choice options: System, System 2,
App, Flow Alarm, None
• Pump 3 Post Purge (0 -240 seconds) the amount
of time if necessary for Pump2 to run after the call
associated with it has been removed.
• Pump 3 Start Delay (0 -240 seconds) the amount
of time if necessary for Pump 2 be delayed to
run after the call associated with it has been
activated.
• Pump Exercise Time (0-240 Hrs) the amount of time
that need to pass before the pumps will exercise
the system pumps. (0 = no exercising)
PUMP SEQUENCER MODE: PUMP SETUP
There is no post purge, start delay, exercising options for Injection, Floating up
and Floating down Valves.
PUMP OPTIONS
System
– If there are any heating calls the pump
contact will close
System 2
– If there are any heating calls the pump
contact will close
App
– if the virtual app switch is activated this pump
contact will close
Flow Alarm
– When no flow is detected the flow alarm
will close. This happens after 10 no flow attempts on
each pump
None
– No pumps are being utilized in your system
setup