H B X C P U - 0 6 0 0 C o n t r o l
V e r s i o n 1 . 0 . 0
Page 18
USE WEB OUTDOOR TEMP
: This setting can be used for
outdoor temperature reading via the web instead
of installing an outdoor sensor. The control must be
connected to a Wi-Fi network and the user must set
the controller to a building via the Sensorlinx mobile
app for this setting to work.
(ON/OFF)
WARM WEATHER SHUTDOWN (WWSD)
: This setting is
used to set the temperature in which the CPU-0600
will go into WWSD. If the system rises above this
temperature, the system will be shut off. In WWSD the
boilers and all pumps will shut off.
(35°F to 120°F) Default: 70°F
WWSD TIME
: This setting is used as a lag time for
WWSD. This will hold the control from entering WWSD
until this time has elapsed. The timer starts when the
outdoor temperature hits WWSD. This setting is useful
in the shoulder seasons when there are large outdoor
temperature swings.
(0°F to 240°F) Default: 0°F
MIXING MODE: DESIGN TEMPERATURES
If the control disconnects from the Wi-Fi after 2 hours or longer it will go to the
coldest day of the year set in your outdoor reset design or maximum boiler
temperature.