HBDF mk2 instruction manual 15 EN 

                  June - 2021                WWW.HBPRODUCTS.DK 

12 / 12

 

 

LED indication 

1)

 

Green LED, flash indicates power supply, And DI external start signal is ON.                                                                                              

2)

 

Red LED indicates Defrost mode or sensor error (Outside measuring range).  

 

LED signal 

ON/OFF/Frequency 

Functionality 

Green  

On or flash 

Supply voltage connected 

Flash (Run-In mode) 

Run-in start signal / operation. 

OFF 

No supply voltage   

Red  

Flash   

Defrost mode “ start”  

Flash quickly  

Defrost mode “stop” 

OFF 

Defrost fan/sensor delay (timer end)  

Fault Detection 

Fault 

Reason 

Correction of fault 

No LED is on / no function 

No supply to the sensor or defective 
cable. 

Check for fault in the power supply 
or replace the supply cable. 

Sensor does not provide a useable 
mA signal and relays does not work 

The “Enable start/stop” is set to on 
and no digital signal is provided 

Set the Enable start/stop is set to off 
if you don’t like to use this function. 

Red LED is flashing 

Power supply is too small. 

Install a power supply with a 
capacity of at least 30 W. 

Very high actual measurement  
(above 5000 pF) 

The wire is shorted to the evaporator 
fins 

Make sure the end of the wire is 
outside the evaporator and use the 
terminal connector.  
If that doesn’t solve the problem the 
wire has to be replaced. 

No analog output or Relay contact 
activation 
 

There may be bad ground 
connection to the frame. 

Clean the metal surface and protect it 
with special compound/grease.  

 
Practical measurement of output signals: 4-20 mA signal: Function and stability of the 4-20 mA signal can be checked 
by connecting a hand-held multimeter. If the supply is connected and the power LED flashes and there is no output 
signal, the electronics may be defective. 

 
Sensor Repair

 

In case of defects with the sensor, it will typically only be necessary to replace the electronical part. 

Complaints are processed by HB Products’ dealers/distributors. 
Please consider their complaint procedures before returning the sensor.  

Spareparts 

Position 

Designation 

Specification 

Product number 

Mechanical part 

10 m wire 

HBDF-MEK-10M 

 

Mechanical part 

20 m wire 

HBDF-MEK-20M 

 

Mechanical part 

30 m wire 

HBDF-MEK-30M 

Electronic part 

PCB 

HBDF-MK2-EL 

Temp. sensor 

Pt1000-Cable type 

HBPT-Pt1000 cable 

Communication cable 

HB USB cable 

HBxC-USB 

 

Note! All terminals are protected against improper termination for a supply voltage up to 40 V. If 
the supply voltage is higher than 40 V, the electronics will be damaged. 

Содержание HBDF-MK2

Страница 1: ...outputs Simple analog Provide a simple analog signal 4 20 mA linear to the ice thickness for a PLC Smart analog Provide an analog signal when the specified ice thickness is reached and when defrost ca...

Страница 2: ...point out important safety instructions for the user It will always be found in places in the chapters where the information is relevant The safety instructions and the warnings must always be read an...

Страница 3: ...The wire must be between the fins where ice will built up It can be on the inlet side on the outlet side or in the middle of the evaporator If you have the overview of where ice is building up you do...

Страница 4: ...d from the evaporator Use the terminal connector delivered together with the wire HBDF snap on Clip can be used for securing the wire but passing behind the pipes provide a better and more secure fast...

Страница 5: ...formed and place both wires and temperature sensor there Sensor wire is passed in out through the evaporator from the inlet side to the outlet side as shown The second picture show ice on the air outl...

Страница 6: ...2 plug for communication and setup The sensor needs power connection to be setup and to have the correct function of the relays Wiring the HBDF Mk2 When the wire ground cable and temperature sensor is...

Страница 7: ...HBDF mk2 instruction manual 15 EN June 2021 WWW HBPRODUCTS DK 7 12 Simple defrost with electric heater...

Страница 8: ...that indicates you have changed something and need to store the data in the sensor The sensor has three different operation modes The sensor mode is selected in the basic settings Simple analog In th...

Страница 9: ...for a period defined by a parameter When the time has passed the evaporator should be dry and free from ice ready for a new cycle Parameters used for controlling the output Filter time constant avera...

Страница 10: ...period sensor delay time This Relay2 can be used for initiating the fan to blow the water out of the evaporator or to prevent the fan from blowing the water out During the defrost time and sensor dela...

Страница 11: ...on in the box Press the green button until the red LED turn off Press the green button once and the calibration is done Using the HB tool Connect power supply to the box Connect the HB tool to the box...

Страница 12: ...nd of the wire is outside the evaporator and use the terminal connector If that doesn t solve the problem the wire has to be replaced No analog output or Relay contact activation There may be bad grou...

Отзывы: