Calibration of the sensor 

 
The sensor can be calibrated using three different methods: 
 
When typing in the active wire length and the distance between the fins the basic calibration is calculated, and the 
sensor is working, but the accuracy can be improved by making a zero calibration. The calibration is always done when 
the evaporator is dry and without significant ice 
 
 

Using the green button in the box 

 
Press the green button until the red LED turn off 
Press the green button once and the calibration is done 
 
 
 
 
 
 
 
 
 
 
 
 

Using the HB-tool  

 

 
 
 
 
 
 
 
 
 
 
 

Connect power supply to the box 
Connect the HB-tool to the box 
Open basic settings tab 
Click on the zero-calibration button. 

 

 

Calibration - when using the thin wire 
 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
When the sensor is installed and the evaporator is dry 
and without ice, connect the sensor to the HB-tool 
using a USB cable. 
 

 

Open basic settings tab 

 

Click on the zero-calibration button. 

 

Click on the small box at the bottom of the 
page  

 

Type in the same value as the zero calibration 
into the field called “SPAN calibration in pF”  

 

Click on “Send Zero/Span values” 

Содержание HBDF-MK2

Страница 1: ...outputs Simple analog Provide a simple analog signal 4 20 mA linear to the ice thickness for a PLC Smart analog Provide an analog signal when the specified ice thickness is reached and when defrost ca...

Страница 2: ...point out important safety instructions for the user It will always be found in places in the chapters where the information is relevant The safety instructions and the warnings must always be read an...

Страница 3: ...The wire must be between the fins where ice will built up It can be on the inlet side on the outlet side or in the middle of the evaporator If you have the overview of where ice is building up you do...

Страница 4: ...d from the evaporator Use the terminal connector delivered together with the wire HBDF snap on Clip can be used for securing the wire but passing behind the pipes provide a better and more secure fast...

Страница 5: ...formed and place both wires and temperature sensor there Sensor wire is passed in out through the evaporator from the inlet side to the outlet side as shown The second picture show ice on the air outl...

Страница 6: ...2 plug for communication and setup The sensor needs power connection to be setup and to have the correct function of the relays Wiring the HBDF Mk2 When the wire ground cable and temperature sensor is...

Страница 7: ...HBDF mk2 instruction manual 15 EN June 2021 WWW HBPRODUCTS DK 7 12 Simple defrost with electric heater...

Страница 8: ...that indicates you have changed something and need to store the data in the sensor The sensor has three different operation modes The sensor mode is selected in the basic settings Simple analog In th...

Страница 9: ...for a period defined by a parameter When the time has passed the evaporator should be dry and free from ice ready for a new cycle Parameters used for controlling the output Filter time constant avera...

Страница 10: ...period sensor delay time This Relay2 can be used for initiating the fan to blow the water out of the evaporator or to prevent the fan from blowing the water out During the defrost time and sensor dela...

Страница 11: ...on in the box Press the green button until the red LED turn off Press the green button once and the calibration is done Using the HB tool Connect power supply to the box Connect the HB tool to the box...

Страница 12: ...nd of the wire is outside the evaporator and use the terminal connector If that doesn t solve the problem the wire has to be replaced No analog output or Relay contact activation There may be bad grou...

Отзывы: