HBDF mk2 instruction manual 15 EN
June - 2021 WWW.HBPRODUCTS.DK
11 / 12
Calibration of the sensor
The sensor can be calibrated using three different methods:
When typing in the active wire length and the distance between the fins the basic calibration is calculated, and the
sensor is working, but the accuracy can be improved by making a zero calibration. The calibration is always done when
the evaporator is dry and without significant ice
Using the green button in the box
Press the green button until the red LED turn off
Press the green button once and the calibration is done
Using the HB-tool
Connect power supply to the box
Connect the HB-tool to the box
Open basic settings tab
Click on the zero-calibration button.
Calibration - when using the thin wire
When the sensor is installed and the evaporator is dry
and without ice, connect the sensor to the HB-tool
using a USB cable.
•
Open basic settings tab
•
Click on the zero-calibration button.
•
Click on the small box at the bottom of the
page
•
Type in the same value as the zero calibration
into the field called “SPAN calibration in pF”
•
Click on “Send Zero/Span values”