USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Page 17 of 36
2.70 THP VS Pump Family
IS3206VSP3 Rev-A
terminals also supply power to the user interface, so care must be taken when connecting to these terminals to
ensure proper operation of the user interface. DIP switch #1 must be “ON”.
This pump can be controlled from third party pool controls as well as Hayward controls that are not software
compatible using relay contacts to select the speeds set in the Timer Menu (see section 6.7). In addition to this
section you may also consult the applicable pool control installation manual for electrical connection details. Once
installed, Remote Control Mode must be set to Relay Control in the pump Configuration Menu (see section 6.6).
Preset Speeds 1-4 and Quick Clean are disabled when the pump is remotely controlled. When inputs INP1-3 are
activated via the pool control relay contacts, timer speeds 1-8 are selected according to the following table (see
section 6.7):
Timer
Speed
INP1
Status
INP2
Status
INP3
Status
1 OFF
OFF
OFF
2 ON
OFF
OFF
3 OFF
ON
OFF
4 ON
ON
OFF
5 OFF
OFF
ON
6 ON
OFF
ON
7 OFF
ON
ON
8 ON
ON
ON
The number of speeds available depends on the number of auxiliary relays used as noted below:
1.
Filter pump relay plus 1 auxiliary relays allows control of 2 speeds
2.
Filter pump relay plus 2 auxiliary relays allows control of 4 speeds
3.
Filter pump relay plus 3 auxiliary relays allows control of 8 speeds
5.4.
Wall Mounted Digital Control Interface Wiring (Optional)
Figure 5.4-1
Connection wire must be rated for a minimum of 300V, and may be up to 500 feet in length. Use removable
4-position terminal block connectors for wiring connection to interface and motor drive PCB’s taking care to note the
wire colors and corresponding numbers next to the connectors.
Terminal block must be installed with screws facing
up to ensure proper connection.
DIP switch #1 must be “ON”.