ELECTRICAL HOOK-UP
This heater must have its own independent circuit using four wires; three live and one earth
ground, of the appropriate rating protected by the correctly rated three pole breaker.
STEP 1:
ELECTRICAL CONNECTION: a 1-
3/8” hole on the bottom of the unit is provided for
customer connection. Customer to supply 480VAC/3-phase/60Hz power in a
”Delta”
configuration, including three power leads and a ground conductor, each sized for the
system’s
maximum amperage of 24A. The customer is responsible for providing a local fused disconnect
switch or circuit breaker sized accordingly. The maximum power draw of the system is 20 kW.
STEP 2:
TEST FUNCTION OF UNIT
Turn on eyewash. Carefully monitor initial few minutes of flow with hand in eyewash flow. Check
to ensure initial flow does not contain brief shots of hot water. See troubleshooting if any
problems.
IMPORTANT: REPEAT TEST PROCEDURE WEEKLY!
THIS UNIT MUST
NOT
BE CONNECTED IN STAR CONFIGURATION
WARNING
FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR
SERIOUS INJURY
WARNING
HAZARD OF ELECTRICAL SHOCK! BEFORE BEGINNING ANY WORK ON THE
INSRALLATION, MAKE SURE THE ELECTRICAL SUPPLY TO THE HEATER IS TURNED
“OFF”. FALIURE TO DO THIS COULD RESULT IN DEATH, SERIOUS BODILY INJURY,
OR PROPERTY DAMAGE.
WARNING
WATER HEATERS EQUIPPED FOR ONE VOLTAGE ONLY: CHECK THE RATING PLATE
ON THE FRONT OF THE UNIT. DO NOT USE THIS WATER HEATER WITH ANY
VOLTAGE OTHER THAN THE ONE SHOWN ON THE MODEL RATING PLATE. FAILURE
TO DO SO CAN RESULT IN DEATH, SERIOUS BODILY INJURY, OR PROPERTY
DAMAGE. IF YOU HAVE ANY QUESTIONS OR DOUBTS CONSULT YOUR ELECTRIC
COMPANY.