background image

03/21   

      Model SP158.15 

 

       Page 4 of 8 

STEP 3:  Plumbing 

a)  Run the heat trace out the grommet from Step 1, situating it within the nearest square cut in the grommet. 

b)  Connect and seal the galvanized 

reducer, and then the galvanized 
nipple, to the auxiliary outlet.  The 
nipple will run through the grommet, 
with the heat trace alongside it.   

c)  Connect and seal the freeze valve 

assembly to the end of the nipple.  
Point the freeze valve drain fitting 
downward.   

d)  Pressurize the plumbing and check 

for leaks. 

e)  Make sure the heat trace is running 

smooth and flat along the new 
plumbing, but do NOT zip tie it into 
place yet. 

STEP 4:  Heat Trace 

a)  Run the heat trace straight and level along the side of the plumbing and freeze valve.  Wrap it around the 

outlet plug of the freeze valve, then run it straight back along the opposite side.   

b)  Push the end of the heat trace through the open square cut in the grommet and feed the excess length 

back within the jacket.  The heat trace must run along the opposite side of the auxiliary outlet plumbing 
until it rejoins the vertical shower piping.  The excess length beyond this point should run out through the 
insulation slit that the extra heat trace originally used.  Store this excess length where the extra heat trace 
was originally located.   

c)  Install the heat trace zip ties (found in a bundle of 6) approximately where shown.  Use more than the 4 

shown if needed.  

The purpose of these zip ties is to ensure that the heat trace maintains solid 

contact with the piping as continually as possible

 

– make sure the heat trace is ideally positioned 

before tightening down the zip ties. 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING:

  The heat trace must lay flush against the plumbing, contacting it wherever possible, in order 

to transfer the necessary heat into the water.  Failure to bring the heat trace into adequate contact with 
the plumbing may cause local freezing within the plumbing, risking damage, leakage, and malfunction. 

Содержание SP158.15

Страница 1: ...upon written authority from HAWS Sparks Nevada HAWS will not be liable for any damages caused by defective materials or poor workmanship except for replacements as provided above Buyer agrees that Haw...

Страница 2: ...trofit installations Wire cutters Pipe wrench and slip joint pliers if possible Pipe joint sealant Loctite PST 567 recommended Serrated knife or saw only for installing without the SP121 Insulation co...

Страница 3: ...iping Carefully clip the zip ties holding this coil together taking care not to damage the heat trace c This extra heat trace will soon be pulled rearward so it can run out the back of the unit Clip t...

Страница 4: ...ough the open square cut in the grommet and feed the excess length back within the jacket The heat trace must run along the opposite side of the auxiliary outlet plumbing until it rejoins the vertical...

Страница 5: ...errated knife or saw Do not cut off any more than is necessary Place the insulation around the freeze valve assembly noting the opening for the freeze valve drain c Place the new insulation disc into...

Страница 6: ...5 After cleaning lubricate all three O rings with an appropriate food grade lubricant such as Dow Corning 111 and confirm that the small O ring is in place 6 Reinstall the thermostat cartridge and ch...

Страница 7: ...APPROVED DRAWN PART NUMBER SCALE REVISION JL 09 17 20 2 SP158 15 FREEZE PROTECTION VALVE 1 1 JL 04 19 21 DRAWING TYPE SIZE A 5588 BY BJM PARTS BREAKDOWN DATE DATE REV ECN 5661 CHK D MODEL S 1455 KLEPP...

Страница 8: ...AL CODES SHOULD BE ADHERED TO 2021 Haws Corporation All Rights Reserved HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation THIS DOCUMENT IS TRUE AND CORRE...

Отзывы: