LOCATION OF UNIT:  

The Model 8330 Stainless Steel combination Shower 

Eye/Face Wash should be installed in close proximity to potential accident areas. It 
should be clearly identified, free from obstructions and easy to access. 
 

SUPPLY LINE:  

The minimum recommended line size is 1-1/4” IPS with 30-90 psi (2-

6 ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet 
filter is recommended. 
 

PLUMBING CONNECTIONS:  

Inlet supply is female 1-1/4” IPS. Waste outlet is 

female 1-1/4” IPS. 

 

INSTALLATION PROCEDURE 

 

Refer to Installation Drawing for clarification. Check parts list to insure all required parts 
are included. Use pipe joint sealant PST #565 (Loctite) on all connections. 
 

STEP 1: 

Prepare the emergency shower foundation by using the floor flange as a 
template. Locate the three holes for the 3/8-16 UNC x 6” anchor bolts. 
(Not supplied). They should extend 1” above the floor level. 

 

STEP 2:

 

Once the concrete foundation is ready (dry), assemble the floor flange to 
the anchor bolts; then securely fasten with 3/8-16 UNC Hex nuts and 3/8” 
washers (Not supplied). Seal and tighten floor flange and (1-1/4”) tee 
making certain the waste tee is facing the proper location and the foot 
control holes are facing side to side. 

 

STEP 3:

 

Assemble nipple (1-1/4” x 21-1/2”) to the tee and tighten with a pipe 
wrench. 

 

STEP 4:

 

Assemble the eye/face wash loop assembly to the (21-1/2”) nipple from 
Step three. Connect the pipe wrench to the nipple between the two tees to 
avoid damage. 

 

STEP 5:

 

Assemble in the following order: 

 

Attach nipple (1

-

1/4” x 24”) onto the loop assembly. 

 

Attach nipple (1-1/4” x 24”) onto the tee. 

 

Attach tee (1-1/4” x 1-1/4” x 1”) onto nipple. 

 

Attach nipple (1” x 8”) and valve assembly onto tee. 

 

Attach street el (1”) and nipple (1” x 12-1/2”) onto valve. 

 

STEP 6: 

Assemble showerhead onto street el (1”). If necessary, use Dow Corning 
832 sealant placing 5 small beads on the male threads, just above the first 
thread. 

 

STEP 7: 

Assemble the sign onto the unit. Use the strap, screws, washers and nuts 
provided to mount the sign onto the upright. The sign should be positioned 
for maximum visibility. 

 

STEP 8: 

Insert the plug into the optional supply line tee that is not used. Before 
connecting the supply water line to the emergency shower; 

FLUSH THE 

LINE THOROUGHLY

 