![Hawle HAWIDO 1505 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/hawle/hawido-1505/hawido-1505_manual_2109918005.webp)
-2-
A. Description
1. Function
Note functional diagram on p. 4.
1. Reduces a variable inlet pressure (p1) to a lower and constant outlet pressure (p2) with a pressure
reducing valve (6). Fluctuating flow rate and inlet pressure have no effect on the outlet pressure
controlled by the control valve. The outlet pressure (p2) is adjustable in the range from 1.5 to 12 bar
(standard).
2. Maintains a minimal inlet pressure by means of a pressure relief valve (10). Variable flow rates have
no effect on the maintained pressure which is regulated by the control valve. The overpressure or
maintained pressure of the standard version can be set within the range of 2 bar to 16 bar.
3. Prevents any backflow when the inlet pressure (p1) is lower than the outlet pressure (p2).
Technical features:
Medium:
Drinking water
Pressure stages:
PN 10 (from DN 200 Standard)
PN16 (up to DN150 Standard)
PN25
Flanges:
Connection dimensions according to DIN EN 1092 - 2
Manometer:
EN 837-1; Accuracy class 1.0
Main valve material:
EN-GJS-400-15
Temperature range:
2
– 40 °C
2. General safety instructions
These instructions must be read through carefully and understood before starting the commissioning.
Damage to property and injuries to persons could occur as a result of improper installation, commissioning,
operation and maintenance.
The Hawle regulating valve (HAWIDO) has been designed for use in drinking water supplies.
Other application media only after consultation with the manufacturer.
The technical regulations (e.g. SVGW, ÖVGW, DVGW...) and codes of practice (e.g. VDE, VDI ...), laws and
standards are taken as a minimum standard, and must be adhered to and applied.
Work on electrical installations (e.g. installation of electrical position indicators, solenoid valves, etc.) may
only be carried out by personnel authorised for this work.
In principle, the responsibility for the layout, the installation position, the installation and the commissioning of
the fittings in the pipe work lies with the designer, the installation company and/or the operator. Design or
installation errors can adversely affect the safe operation of the regulating valve, and can represent a
significant risk. Please consult us in case of doubt.
Содержание HAWIDO 1505
Страница 1: ...manual Pressure reducing valve with inlet pressure control and non return function...
Страница 14: ...11 3 1 Main valve with stainless steel connection ND 40 to ND 200 drawing 08 12 2011 pl...
Страница 17: ...14 3 3 Control valve pressure reducing stainless steel design 05 09 2017...
Страница 19: ...16 3 5 Control valve pressure sustaining INOX drawing 05 09 2017 pl...
Страница 26: ...23 3 8 Position indicator drawing DN 40 DN 100 DN 125 DN 300 12 03 2014 pl...
Страница 30: ...27...