C. Fault finding
Symptoms
Possible cause
Action
Valve does not open
One-way flow restrictor blocked Replace or unscrew several
times the set screw until valve
functions properly
One-way flow restrictor closed
too far
Undo the set screw until valve
functions properly
Valve allows pressure creep
One-way flow restrictor blocked Replace or screw set screw in
and out fully several times and
then reset
Filter in control circuit blocked
Clean the filter
Air in the control circuit or valve
chamber
Vent
Membrane defect
Carry out service, replace
membrane
Foreign matter in the main valve Carry out service and remove
foreign matter
Valve spindle jammed by
encrustation
Carry out service and remove
encrustation
Loud noise
Unsatisfactory installation
conditions
Change outlet pressure by 0.1
to 0.2 bar. Slightly open or close
One-way flow restrictor. Contact
Hawle customer service
department.
Wrong valve size
Calculate correct valve size. (If
necessary contact Hawle)
Erratic operation
One-way flow restrictor
incorrectly set
Reset (according to Chapter:
Setting the reaction speed
)
Original pressure value is not
reached
Pressure gauge faulty
Check or replace pressure
gauge
Changed operating conditions
Reset accordingly (see Chapter:
Recommended installation)
Epoxy-coating damaged
Transportation damage,
installation damage
Repair with Hawle two-
component repair set for
coatings
Содержание HAWIDO 1505
Страница 1: ...manual Pressure reducing valve with inlet pressure control and non return function...
Страница 14: ...11 3 1 Main valve with stainless steel connection ND 40 to ND 200 drawing 08 12 2011 pl...
Страница 17: ...14 3 3 Control valve pressure reducing stainless steel design 05 09 2017...
Страница 19: ...16 3 5 Control valve pressure sustaining INOX drawing 05 09 2017 pl...
Страница 26: ...23 3 8 Position indicator drawing DN 40 DN 100 DN 125 DN 300 12 03 2014 pl...
Страница 30: ...27...