Page 12 of 22
4.3
P7/IS Controller technical specifications
Taken@25
°
C, specifications subject to alteration.
Supply
Supply voltage
240Vac/110Vac/24Vac
±
10% factory set
Note- the 240V unit will operate at 240V +10% but its Intrinsically
safe certification is valid to 250V max (240V+4%).
Installation Cat
Overvoltage Cat II
Supply frequency
50/60 Hz
Consumption
approx 5 V/A
Electrode
Volts
8.0Vac max (open circuit electrodes)
Current
8mA max (short circuit electrodes)
Sensitivity
Standard: - approx 300 Ohms to 20K Ohms,
user adjustable.
Special:-low range to approx 7K Ohm
Switching
response
<1s
Operating Temp
-20
°
C to +40
°
C
Cable
Typically 70m.
See drawing 2920 for maximum permitted
Levels for intrinsic safety.
Capacitance max before sensitivity is affected -
30nF @ 20KR, 100nF@500R, ignoring drawing 2920.
Output Relay
Volt free contact S.P.C.O rated 240Vac @ 5A max, resistive.
For intrinsically safe model-
Load must not exceed 100VA
Current must not exceed 5amps
Voltage must not exceed 250V
Output Led
Red Led “On” when relay energised
Fail-safe
High or Low factory set
Enclosure
Material
Polycarbonate
Mounting
Snap fastener for Din Rail mounting DIN 46 277
Weight
325g
Terminals
Captive self-locking screws, accepts up to 4mm
2
conductor.
Dimensions
55 x 110 x 75mm W x D x H