4.3 

P7/IS Controller technical specifications 

 

Taken@25

°

C, specifications subject to alteration. 

 

Supply 

Supply voltage 

240Vac/110Vac/24Vac 

±

10% factory set 

Note- the 240V unit will operate at 240V +10% but its Intrinsically  
safe certification is valid to 250V max (240V+4%). 

Installation Cat 

Overvoltage Cat II 

Supply frequency 

50/60 Hz  

Consumption  

approx 5 V/A 

 
Electrode 

 

Volts   

 

8.0Vac max (open circuit electrodes) 

Current 

 

8mA max (short circuit electrodes) 

Sensitivity 

Standard: - approx 300 Ohms to 20K Ohms,  

  

user adjustable.  
Special:-low range to approx 7K Ohm  
 

Switching  
response

 

 

<1s 

 
Operating Temp

 

-20

°

C to +40

°

 
Cable 

Typically 70m. 
See drawing 2920 for maximum permitted  
Levels for intrinsic safety.   
Capacitance max before sensitivity is affected - 
30nF @ 20KR, 100nF@500R, ignoring drawing 2920. 
 

 

Output Relay 

Volt free contact S.P.C.O rated 240Vac @ 5A max, resistive. 

 

 

For intrinsically safe model- 
Load must not exceed 100VA 
Current must not exceed 5amps 
Voltage must not exceed 250V 
 

Output Led

   

Red Led “On” when relay energised 

 

 

 

 

Fail-safe 

 

High or Low factory set 

 

Enclosure 

Material 

 

Polycarbonate 

Mounting 

 

Snap fastener for Din Rail mounting DIN 46 277  

 

Weight  

 

325g 

Terminals 

 

Captive self-locking screws, accepts up to 4mm

2

 conductor. 

Dimensions   

55 x 110 x 75mm W x D x H

 

Содержание P7/I.S.

Страница 1: ...troller type P7 I S Certificate No SIRA03ATEX2160X Electrode Holders Certificate No SIRA03ATEX2159X Conductivity Operated Level Control System Certificate No Ex03E2161 Hawker Electronics Limited O M 7...

Страница 2: ...4 2 3 Basic controller testing 10 4 3 Technical specification 12 5 0 Electrode Holders 13 5 1 Cat 1 Electrode holders 13 5 1 1 Type identification 13 5 1 2 Certification markings 14 5 1 3 Conditions o...

Страница 3: ...ected the unit either de energises or energises its internal relay dependent on the fail safe setting providing the user with a set of volt free S P C O contacts The unit may be used for High or Low a...

Страница 4: ...acing ventilation or cooling should be provided Ambient operating temperature ranges other than 20 C to 40 C will be indicated on the product label The equipment is intended to be used only in dry cle...

Страница 5: ...se to a spread of additional risks in the event of a power failure it must be possible to maintain them in a safe state of operation independently of the rest of the installation this is the responsib...

Страница 6: ...uipment shall only be carried out by the manufacturer or in accordance with the applicable code of practice 6 The certification of this equipment relies on the following materials used in its construc...

Страница 7: ...rnal relay contacts These relay contacts must not switch more than 5A r m s or 250V r m s or 100 VA 4 1 4 Electrical connection and housing The electrical connections are made to the terminal blocks s...

Страница 8: ...IS technical specifications for ordering information Always check to ensure the controller specifications are suited to the supply and its application before installing The input supply fail safe set...

Страница 9: ...ded that this manual be used for optimum performance No attempt should be made to remove this trim Precautions before testing Before disconnecting any mains leads or control wiring at the controller o...

Страница 10: ...erating cycle to ensure correct operation 4 2 3 Basic controller testing If necessary the controller can be tested without connecting to the electrode holders so its correct basic function and the use...

Страница 11: ...e supply to the volt free contacts has been switched OFF and remove the wires from the terminal block Use an approved ohmmeter to measure the contact resistance Check with the Relay de energised Led O...

Страница 12: ...cial low range to approx 7K Ohm Switching response 1s Operating Temp 20 C to 40 C Cable Typically 70m See drawing 2920 for maximum permitted Levels for intrinsic safety Capacitance max before sensitiv...

Страница 13: ...gases that may attack metals or solvents that may affect polymeric materials Suitable precautions e g regular checks as part of routine inspections or establishing from the material s data sheet that...

Страница 14: ...Sira 03ATEX2159X may be used in zones 0 1 and 2 with flammable gases and vapours with apparatus groups IIA IIB IIC and with temperature classes T1 T2 T3 T4 T5 and T6 The ambient temperature operating...

Страница 15: ...recommended distance is 23cm Using plastic coated electrodes which are available from stock can eliminate bridging always bare at least 50mm of the coating and have the reference G electrode central...

Страница 16: ...alculating cable capacitance and inductance follow 6 1 Cable inductance Example of calculating cable inductance Method A As the L R Ratio remains constant regardless of cable length this is the easies...

Страница 17: ...ch as the HPE8 when mounted 230mm apart may be up to 18m in length before this figure is exceeded Light duty electrodes such as the HPE7 mounted 75mm apart may be up to 15m in length which is far beyo...

Страница 18: ...ed except that it must not be supplied from nor contain under normal or abnormal conditions a source of potential with respect to earth ground in excess of 250V a c r m s or 250V d c and ii Controller...

Страница 19: ...roller G terminals Where a multiple controller system uses a Holder Type 1G 0 HPE5 IS as a common G holder the maximum number of P1 P2 holders that may be fitted is five 7 4 Permissible interconnectin...

Страница 20: ...Page 20 of 22...

Страница 21: ...K Notified Body Sira Certification Service 0518 Rake Lane Eccleston Chester CH4 9JN Conformity has been demonstrated with reference to the following documentation EC type examination certificate Sira...

Страница 22: ...Page 22 of 22...

Страница 23: ...l 41 41 541 5877 Fax 41 41 541 5878 Email General Information Sales info kesn ch Accounts Department accounts kesn ch USA O ce 233 Rogue River Highway 425 Grants Pass Oregon 97527 5429 USA Tel 1 503 2...

Отзывы: