Page 11 of 22
14.
Remove the P1 & G short, the relay should remain de-energised.
15.
Remove the P2 & G short, the relay should energise.
16.
Testing the volt free contacts: -
Ensure the supply to the volt free contacts has been switched OFF and remove the
wires from the terminal block. Use an approved ohmmeter to measure the contact
resistance.
Check with the Relay de-energised (Led OFF) that the-
C & NO is greater than 1M Ohm and,
C & NC is less than 1 Ohm.
Check with the Relay energised (Led ON) that the-
C & NO is less than 1 Ohm and,
C & NC is greater than 1M Ohm