Power     Termination Procedure

 

(AI365 Rev 5 – 01Mar16) 

 

 
 
 
 
 
 
 
CP / CR PROCEDURE 

 

1)

 

Terminate the cable into the Exd cable gland as per the 
manufacturer’s instructions. Consider at this stage the 
relative position of the phases. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
2)

 

Cut the conductors to the lengths shown. 
(For earth conductors which are being terminated to the 
earth ring (see step 6) but not carried through the 
contact, cut back X = 100mm for all sizes, see 10 - 13) 
 
 
 
 
 
 
 
 
 
 
 

 
 
3)

 

Strip back the insulation as shown. (For all earth 
conductors terminated via the internal earth ring, cut 
back the insulation flush with the gland entry thread, see 
10 - 13). 

 

 
 
 
 
 
 
 
 
 

 
 
 

 
4)

 

Unscrew the rear engaging nut from the CP / CR shell. 
Remove the rear shell, spacer tube and insert from the 
CP / CR shell. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
5)

 

a) 

CONTACT SIZES 50 - 240mm²

Remove the screws from the front of the contacts 
only and push the crimp lugs out of the insert. 

 
 
 
 
 
 
 
 
 
 
 
 
 
b)

 

CONTACT SIZES 300 – 630mm²

Remove the screw from the plastic housing and 
remove the contact from inside. 

 
 
 
 
 
 
 
 
 
 
 

 
 
 

CP / CR SHELL 

INSERT 

SPACER TUBE 

REAR SHELL 

ENGAGING NUT 

REMOVE CONTACT 
SCREWS 

CRIMP LUGS 

HOUSING SCREW 

CONTACT 

X mm 

Y mm 

CONTACT SIZE

X mm (± 1.5mm)

50mm²

147

70mm²

147

95mm²

147

120mm²

146

150mm²

146

185mm² (ExP 40 & 50)

149

185mm² (ExP 75)

159

240mm² (ExP 40 & 50)

149

240mm² (ExP 75)

159

300mm²

167

400mm²

172

500mm²

188

630mm²

188

CONTACT SIZE

Y mm (± 1.5mm)

50mm²

30

70mm²

30

95mm²

32

120mm²

32

150mm²

32

185mm²

40

240mm²

45

300mm²

50

400mm²

57

500mm²

62

630mm²

67

IMPORTANT NOTE 

Hawke International does not recommend the use of their Power      Connectors in applications where rigid PVC / SWA / PVC 

power cabling (typically to BS 6346 standards) is used in portable / semi-portable applications. 

 

In addition, Hawke recommends that barrier type glands are fitted to flexible power and loose filled control cabling entering the 

connectors to maintain the Exd protection concept and to reduce the potential for core movements within the cable being 

transferred to the connector’s internal components. 