Overview

SERIES  2000-RANGE-VALVE                                                      

Reverse Output (20 - 4mA)

The transmitter as standard is adjusted to 4-20 mA.
Push on [PROG] and go to P105.
Push once at [

h

] to change the output to 20-4 mA (Reverse output).

Push at [PROG] to confirm this.  
Now the transmitter will give 20 mA at atmospheric pressure

P105

Adjustment Samping (0 till 25 sec)

In P106 an electronic damping can be adjusted between 0 and 25 seconds.
This can be done with the push buttons [

h

] (up) and [

i

] (down).

Always confirm by pushing once at [PROG].

P106

Indication of Process Temperature (Read Out On Display)

1. Push [PROG] until “100” is shown on the display.
2. Push 7 times at [

h

], go to [P107].

3. Push [PROG] to confirm this. Now the process temperature appears on the display (Indication: +/-2

o

C).

This will remain on the display. To get the actual pressure back on the display you have to push again on P107 until the 
actual pressure appears on the display again.

P107

Temperature In 

o

C OR 

o

F

The temperature of the transmitter is standard adjusted at 

o

C (“DEGR”). When pushing at [

h

] in P108, this will change into 

o

F (“FAHR”).

Always confirm by pushing once at [PROG].

P108

Read Out On Display

Curr (0) = current 

(4 - 20 mA)

Unit (1) = pressure unit 

(See conversion table)

PErC (2) = percentages 

(0 - 100%)

TEnP (3) = temperature 

(

o

C of 

o

F)

HECt (4) = hectoliter 

(only in combination with P111)

Cb n (5) = Cubic meter 

(only in combination with P111)

Ltr (6) = Liters 

(only in combination with P111)

As standard the transmitter is delivered with read out in mA (0). To change this, follow the next steps:
1. Push [PROG] until “100” is shown on the display.
2. Push 9 times at [

h

] / SPAN till “109” appears on the display.

3. Confirm with [PROG].
4. Push once at [

h

].

5. Push [PROG] to confirm this. 
  The transmitter will now read mH

2

O (mWC).

  The pressure unit can be changed with the conversion table in “P104”. 
  1 = mH

2

O (=mWK), 3 = bar, 5 = PSI, 11 = inch WK.

Also the read out can be 0 - 100%. In this case select “P109”, option 2.

P109

Содержание 2000-RANGE-VALVE Series

Страница 1: ...erview Gladiator Acoustic Switch Series A Higher Level of Performance Instruction Manual www hawkmeasurement com For more information please visit SERIES 2000 RANGE VALVE Pressure and Level Transmitte...

Страница 2: ...nting PA 5 PG9 cable gland 6 Electronics housing AISI 304 7 Hexagon nut SW 41 AISI 304 8 Stop AISI 316 9 O ring 2x VITON 10 Nipple SW 41 1 BSP M 2x AISI 316 11 Safety Lock AISI 304 12 M4 Bolt AISI 304...

Страница 3: ...sing the auxiliary tool to ensure the parts are in line Use silicone grease 2 Tighten the valve bolts 18 4x 3 3 Remove the auxiliary tool and make sure the valve and be closed and opened easily 4 Make...

Страница 4: ...libration All transmitters are fully calibrated at the factory to the conditions stipulated in users order When the buyer has not requested calibration the transmitter will be calibrated at the highes...

Страница 5: ...supply is based on the total circuit resistance The maximum permissible load Ri max in case of 24 Vdc is 600 Ohm By increasing the power supply the external load can be increased to 1200 Ohm 36 Vdc s...

Страница 6: ...bar is supplied to the transmitter the button must be held until the word SPAN appears on the display The transmitter is adjusted at 20 mA now The span can also be adjusted without test pressure see P...

Страница 7: ...See Conversiontable P105 4 20 mA 20 4 mA Reverse output P106 Adjustment damping 0 to 25 sec P107 Indication of process temp Read out on display P108 0 C 1 F P109 Read out on display Curr 0 current 4...

Страница 8: ...pressure P101 Span Adjustment 20 mA Without Test Pressure Before adjusting the span take care the right pressure unit is selected See also P104 and P109 Example Adjustment of the span at 0 2 bar First...

Страница 9: ...smitters working with software revision 1 will direct process cancel mounting position P103 Adjustment Pressure Unit On Display See Conversion Table P104 104 Conversion Factor Display 1 1 000 mH2 O mW...

Страница 10: ...on P107 until the actual pressure appears on the display again P107 Temperature In o C OR o F The temperature of the transmitter is standard adjusted at o C DEGR When pushing at h in P108 this will c...

Страница 11: ...simulation Pressure simulation Unit To perform a pressure simulation follow the next steps 1 Push PROG until 100 is shown on the display 2 Push 10 times at h SPAN till 110 appears on the display 3 Con...

Страница 12: ...rizontal tank Cilindric Push PROG until 100 is shown on the display 2 Push 11 x at h SPAN till 111 appears Confirm with PROG 3 Push h once Confirm with PROG 4 Enter the height H1 of the tank in meters...

Страница 13: ...the length L of the tank For a ball or cone shaped tank take the cylindrical length plus the length of 1 ball cone Confirm with PROG 7 Enter H3 in meters if the transmitter is installed like in the le...

Страница 14: ...al Cone From Software Revision 3 1 Push PROG till 100 appears on the display 2 Push 11 times at h till 111 appears Confirm with PROG 3 Push three times at h Confirm with PROG 4 Enter height H1 of the...

Страница 15: ...confirm Lo Pr appears on the display 4 Push h i for adjusting to ON or OFF 5 Push PROG to confirm Adjustment Communication Protection 1 Push PROG till 100 appears on the display 2 Push h SPAN 13 times...

Страница 16: ...H HART DTM This DTM is developed to make configuration changes of HAWK Series 2000 RANGE VALVE option H HART transmitters easy This DTM can be used with almost every FDT container To be able to insta...

Страница 17: ...his is very important to prevent distortion of the weld spud The diaphragm of the SERIES 2000 RANGE VALVE is protected with a special protection cap Protect the diaphragm until installation takes plac...

Отзывы: