10
Overview
SERIES 2000-RANGE-VALVE
Reverse Output (20 - 4mA)
The transmitter as standard is adjusted to 4-20 mA.
Push on [PROG] and go to P105.
Push once at [
h
] to change the output to 20-4 mA (Reverse output).
Push at [PROG] to confirm this.
Now the transmitter will give 20 mA at atmospheric pressure
P105
Adjustment Samping (0 till 25 sec)
In P106 an electronic damping can be adjusted between 0 and 25 seconds.
This can be done with the push buttons [
h
] (up) and [
i
] (down).
Always confirm by pushing once at [PROG].
P106
Indication of Process Temperature (Read Out On Display)
1. Push [PROG] until “100” is shown on the display.
2. Push 7 times at [
h
], go to [P107].
3. Push [PROG] to confirm this. Now the process temperature appears on the display (Indication: +/-2
o
C).
This will remain on the display. To get the actual pressure back on the display you have to push again on P107 until the
actual pressure appears on the display again.
P107
Temperature In
o
C OR
o
F
The temperature of the transmitter is standard adjusted at
o
C (“DEGR”). When pushing at [
h
] in P108, this will change into
o
F (“FAHR”).
Always confirm by pushing once at [PROG].
P108
Read Out On Display
Curr (0) = current
(4 - 20 mA)
Unit (1) = pressure unit
(See conversion table)
PErC (2) = percentages
(0 - 100%)
TEnP (3) = temperature
(
o
C of
o
F)
HECt (4) = hectoliter
(only in combination with P111)
Cb n (5) = Cubic meter
(only in combination with P111)
Ltr (6) = Liters
(only in combination with P111)
As standard the transmitter is delivered with read out in mA (0). To change this, follow the next steps:
1. Push [PROG] until “100” is shown on the display.
2. Push 9 times at [
h
] / SPAN till “109” appears on the display.
3. Confirm with [PROG].
4. Push once at [
h
].
5. Push [PROG] to confirm this.
The transmitter will now read mH
2
O (mWC).
The pressure unit can be changed with the conversion table in “P104”.
1 = mH
2
O (=mWK), 3 = bar, 5 = PSI, 11 = inch WK.
Also the read out can be 0 - 100%. In this case select “P109”, option 2.
P109