background image

SPECIFICATIONS 

Model 

(EC) 

40  80 120

160

220

300

400 500

600

750

Dry 

Weight 

110 176 225

271

310

373

634 726

845

1067

Operation Weight** 

335 

560 

650

825

880

1135

1680 

1930

2085

2635

Pump Cap/GPH req.* 

270 

360 

540

720

720

810

540+ 

630+

630+

630+

Cap/GPH @ Lift* 

387 

1135 

1135

1135

1135

1100

1080 

1080

1060

1060

Pump Lift/ft.  

4

4

4

5

6

7

7

*  These figures do not include the 3 to 6 percent bleed-off rate required to reduce scaling for standard unit. 
**Unit in operation, media fully saturated. 
+ Per pump 
EC = Evaporative cooler 

 

WATER CONNECTIONS ALL UNITS 

1-1/2 FPT Overflow 

¾ FPT Drain 

½ MPT Bleed-off 

½ FPT Float Valve 

 

ELECTRICAL SPECIFICATION 

Model 

(EC) 

40 

80  120 160 220 300 400 500 600  750 

Pump Motor Model 

CP 1000 

5 MSP 

(2) 5 MSP 

HP  

1/50 

1/6 

1/6 

Amperage  

1.1 A 

5.0 A 

5.0 A 

Voltage 115 

EC = Evaporative Cooler 
 

APPROXIMATE BLEED-OFF FLOW RATE 

Model 

EC-40  -80 

EC-120  -160 

EC-220  -300 

EC-400  -750 

Per Minute 

½ to 1 qt. 

1 to 2 qt. 

2 to 3 qt. 

2 (2-3 qt.) 

 

CONSTRUCTION AND MEDIA SPECIFICATION 

 

Celdek Glasdek 

Maximum Water Temperature 

130ºF 

165ºF 

Maximum Air Temperature 

300ºF 

300ºF 

pH Range 

6-9 

6-9 

Cabinet 

Aluminized Steel and Painted 

Evaporator Reservoir 

Stainless Steel and Painted 

 

INSTALLATION INSTRUCTIONS 

 
  
1.  When installing the evaporative cooler, special consideration should be given to the physical positioning of 

the unit, electrical power supply, the proper water supply, and the structural members to support the 
cooler at the operating weights.  It is recommended that supports be placed within every four feet to 
distribute the weight evenly.  Be sure the supports are level. 

2.  After the unit is properly located, electrical connection may be made.  If the Evaporative Cooler has been 

purchased separately, wiring from a 115 volt supply may be connected to the junction box supplied with 
the unit.  Refer to the wiring schematic supplied in owner’s packet or, pages 4 and 5 of typical wiring 
schematics, and to drawings for standard unit, units with automatic drain kit, or units with automatic drain 
kit and freeze protection. 
          When the evaporator cooler is purchased with a system exhaust blower and filter, most connections 
may have been made already.  Refer to schematic with owner’s packets for any additional wiring to be 
done. 

- 3  -

Содержание EC-40

Страница 1: ...on arrival inspect the unit for shipping damage and completeness If any part is missing or damaged notify the carrier immediately Always refer to the unit s serial and model numbers located on the specification plate when making an inquiry regarding maintenance and parts To insure unit integrity use only Factory Authorized Replacement Parts ISEC 1 July 1997 ...

Страница 2: ...ts of components 3 Use extreme caution when making voltage tests with live circuits follow the established safety procedures 4 Electrical repairs should be performed by trained qualified personnel only Failure to follow safe electrical procedures can result in series injury or death 5 Do not attempt to operate unit by jumping or otherwise bypassing any circuit 6 Keep evaporator reservoir clean Do ...

Страница 3: ... 130ºF 165ºF Maximum Air Temperature 300ºF 300ºF pH Range 6 9 6 9 Cabinet Aluminized Steel and Painted Evaporator Reservoir Stainless Steel and Painted INSTALLATION INSTRUCTIONS 1 When installing the evaporative cooler special consideration should be given to the physical positioning of the unit electrical power supply the proper water supply and the structural members to support the cooler at the...

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ... valve until it disappears The exact amount will depend upon the pH and hardness of the water and the intensity of evaporation Clean and flush distribution header on a regular basis Water depositing into Transition and Reservoir Not Draining 1 Reservoir float valve FV improperly adjusted See Installation Instructions note 4 2 Float valve bad not shutting off Replace 3 Check overflow and drain valv...

Отзывы: