1.
Remove rear access plate and clean out economizer tubes. (Place receptacle to collect
soot as the swirlers are pulled out. Do not operate fans while access plate is off as
considerable soot may be blown into surrounding area.) Be sure gasket is properly seated
when replacing the access plate.
2.
Inspect refractory around burner. If cracked or damaged, repair or replace.
3.
Clean exhauster fan wheels.
4.
Disassemble nozzle tip and clean. Clean all parts before reassembling.
5.
Lubricate burner motor.
6.
Lubricate fan motor as directed by motor manufacturer and inspect fan motor wiring for
loose connections.
7.
Check all control settings as outlined.
8.
Clean gas pressure regulator.
9.
Clean magnetic oil supply valve.
10.
Turn main disconnect switch to “off” and open control box. Make sure controls are free
from dust and grease. Check and clean relay and starter contacts, and inspect for loose
wiring. Do not use file, sandpaper, or other abrasives to clean contacts – clean with
notebook or heavy wrapping paper, not newspaper.
NOTE: Keep screened air intakes clear of obstructions at all times.
B.
LUBRICATION INSTRUCTIONS
ITEM
All 3 phase fan motors (1
HP to 100 HP) ODP or TEFC
Fractional HP exhauster
motors, single phase, ODP
or TEFC
Fractional HP burner motors
and oil pump motors, single
phase, ODP or TEFC
Fan shaft bearings
Manufacturer
U.S. or equal
Century, G.E., or
equal
Century, G.E. or
equal
Linkbelt or equal
Bearing Type
Single row ball
bearings
Bronze sleeve
bearings
Bronze sleeve
bearings
Self-aligning
single row ball
bearings, resilient
mounted
Recommendation
Note #1
Note #2
Note #2
Note #1
NOTES
1.
Remove top and bottom grease plugs. Install lubrication fitting in place of top plug.
Annually flush with lithium base grease, consistency #2, until clean grease is
discharged from bottom hole. Run motor with drain plug removed until grease stops
flowing from drain. Reinstall drain plug.
2.
Annually add ½ to 1 teaspoon of grade SAE 30 motor oil to each bearing. Add oil
slowly so that felt packing will absorb the oil properly.
-24-