Furnished and Installed by Others
Furnished By Factory, Installed By Others
Factory Furnished And Installed
ITEM
DESCRIPTION
1
Drip Leg
l
2
Main Gas High Pressure Hand Shut-Off Valve (If Required)
l
3
Main Gas High Pressure Regulator (If Required)
l
4
Vent Line Thru Roof To Outside Atmosphere
l
5
Main Gas Hand Shut-Off Valve
l
6
Main Gas Pressure Regulator
l
7
Safety Shut-Off Valve
l
8
Manual Leak Test Hand Valve
l
9
Main Gas Burner
l
10
Leak Test Petcock W/ Plugged Test Connection
l
11
Pilot Gas Supply Line
l
12
Pilot Gas Hand Valve
l
13
Pilot Gas Pressure Regulator
l
14
Pilot Gas Solenoid Valve
l
15
Needle Valve (If Required)
l
16
Pilot Gas Burner
l
1
To Natural Gas Or Propane Fuel Supply.
Figure 3 – Typical On-Off Gas Piping
For Counterflo Heaters (1/2# Inlet Pressure)
GAS FLOW CAPACITY (CFH)
Iron Pipe Size (IPS) Inches
Length of
Pipe
(Equiv. Ft.)
1 1-1/4
1-1/2 2
3 4
6 8
50
100
150
200
244 537
173
380
141
310
122 268
832
1680
588
1188
480
970
416 840
5018
8464
3549
5986
2896
4885
2509 4232
22472 41516
15894 29364
12972 23965
11238 20760
250
300
400
500
109 240
99 219
86 189
77 169
372
751
339
685
294
594
263 531
2244
3785
2047
3454
1774
2992
1587 2677
10050 18567
8170 16943
7945 14679
7108 13132
1000
1500
2000
54 119
44
97
38 84
185
375
151
306
131 265
1121
1891
915 1544
793 1338
5022
9279
4101
7577
3554 6567
Figure 2 – Gas Flow Capacity for Piping of
Different Sizes and Lengths