Installation, Operation & Maintenance Manual

SECTION 2 - INSTALLATION AND OPERATION

2.1 INSTALLATION

Carefully unpack the pump and select a mounting 
location in the Plenum area (

see Figure 1

). The 

pump must be level and the inlet must be below the 
lowest drain, either coil or furnace. If wall or case 
mounting, use the mounting tabs on either side of 
the reservoir to secure the pump.

2.1.1 Piping

Run flexible tubing or pipe from the evaporator and 
furnace to the pump. Connect to either inlet barbed 
fitting. Make sure the pipe does not interfere with 
the float. If barbed fitting is not used, cut an angle 
on the inlet pipe so that it doesn’t close off against 
the bottom of the pump.
Connect tubing to the check valve. Extend this 
tubing straight up as high as necessary. (Do not 
extend this tubing past the head/GPH of the pump 
installed). Do not kink the tubing, as this will block 
the flow. From this high point, slope the discharge 
tubing downward to a point above the drain, then 
turn down and extend to a point below or level 
with the bottom of the condensate pump. If it is not 
possible to slope the discharge tubing downwards, 
make an inverted “U” trap directly above the pump 
at the highest point (

Figure 2

).

Figure 2

Discharge tube should 

slope down towards 

oulet if possible

3/8” ID Tubing

To Floor Drain

Do not kink tube !

Hose Clamp

Active/Circulating

Plenum Airspace

Forced-Air Return

Forced-Air Supply

Living/Working Space of a 

Typical Commercial building

Drop 

Ceiling

Figure 1

Содержание PlenumPlus KL-1DG-115

Страница 1: ...PlenumPlus Commercial Grade Condensate Removal Pumps KL 1DG 115 KL 1DG 230 and KL 1DG 277 IOM Manual Manual No 52200 Rev A Rev Date 2019 ...

Страница 2: ...e does not apply if the product has been misapplied or mechanically damaged HARTELL assumes no liability for resultant damages of any kind arising out of the use of its products ONE YEAR LIMITED WARRANTY SECTION 1 INTRODUCTION 1 SECTION 2 INSTALLATION AND OPERATION 2 2 1 INSTALLATION 2 2 1 1 Piping 2 2 1 2 Electrical Connections 3 2 1 3 Line Voltage 3 2 1 4 Low Voltage Auxiliary Safety Switch 3 2 ...

Страница 3: ... the precautions listed below before continuing READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION 1 Pumpshouldonlybeusedwithliquidscompatible with pump component materials Do not use to pump flammable or explosive fluids Do not use in explosive atmospheres 2 The pump is supplied with Pigtails to hard wire the pump To reduce the risk of electrical shock be certain that it is connected to...

Страница 4: ...t close off against the bottom of the pump Connect tubing to the check valve Extend this tubing straight up as high as necessary Do not extend this tubing past the head GPH of the pump installed Do not kink the tubing as this will block the flow From this high point slope the discharge tubing downward to a point above the drain then turn down and extend to a point below or level with the bottom of...

Страница 5: ... thermostat demand in a high water condition Figure 3 Condensate Pump Wire Nut From Thermostat Yellow Yellow Furnace A C Red White Green Yellow Figure 3 T hermostat demand disruption should not be utili z ed if cooling or heating re q uirements are a necessity A n alarm system should be used with the au x iliary switch instead 2 2 OPERATION After proper installation the operation of the HARTELL co...

Страница 6: ... algae formation Flush the reservoir with warm water and a mild soap or detergent See note from point 3 2 3 2 PUMP MOTOR RUNS WITH NO DISCHARGE 1 Inspect the discharge tubing for its full length to make sure it is clear make sure the tubing end is not plugged 2 Make sure the check valve is not clogged If clogged UNPLUG THE PUMP remove the fitting and clean with mild soap or detergent See note belo...

Отзывы: