Harsco Industrial P-K DURATION II D2DW-30(S/D) Скачать руководство пользователя страница 17

 

P-K DURATION II 

™ Indirect Domestic Water Heating System 

 

17 

4  OPERATION 

4.1 

LOVE

 

C

ONTROLLER

 

  Read instructions and understand operation before operating or making adjustments 

to the digital temperature controller. 

 
A digital temperature controller (right) positions the valve in response to outlet water temperature.  A 4-20 
milliamp signal drives the valve actuator.  The controller uses a type J thermocouple to sense the outlet domestic 
water temperature. 
 
The default screen is shown.  PV - the top number (red) - is the 
temperature of the water in the P-K COMPACT

®

 water heater and SV - the 

lower number (green) - is the setpoint. 

The index button 

 changes the parameters displayed on the screen.  

The PV line lists the parameter name and the SV line lists the parameter 
value. 

Press the enter button 

 to store any value after it is changed.   

 

The up 

and down 

 buttons are used to change the values of 

the parameters. 
 

4.1.1 

Controller Operation 

To change the setpoint, press the up or down buttons to change SV to the desired value.  Once the desired value 
is displayed, press the enter button to store the value.   
 
The temperature control starts in the operation mode.  The following table lists the operating parameters, their 
factory default settings, and a description of the parameters function.  Parameters are accessed by repeatedly 
pressing the index key until the desired parameter is displayed. 

 

Operational Mode 

Parameter 

Default Value 

Description of Parameter Function 

Home Screen  = 

Setpoint 

120°F 

Setpoint temperature of outlet water 

r-S 

RUN 

Run 

– Stop output control. 

Must be in run for control to operate 

SP 

Sets the number of digits to the 

right of the decimal point 

AL1H 

20 

Alarm 1 High Set Point, 

Alarms at se AL1H value 

LoC 

Off 

Set front panel security, 

Off = no security, On = settings are locked 

OUt1 

### 

Output value of controller, 0 

– 100% 

 

Содержание P-K DURATION II D2DW-30(S/D)

Страница 1: ...ANEOUS INDIRECT DOMESTIC HOT WATER SYSTEM Model _______ Serial ______________________ Start Up Date _______________________ Harsco Industrial Patterson Kelley 155 Burson Street East Stroudsburg PA 183...

Страница 2: ...P K DURATION II Indirect Domestic Water Heating System 2...

Страница 3: ...nd Storage 7 3 2 Compliance with Codes 8 3 3 Setup 8 3 4 Mechanical Connections 9 3 5 Electrical Connections 15 3 6 Pre Start Check List 16 3 7 Safety Checks 16 4 OPERATION 17 4 1 LOVE Controller 17 4...

Страница 4: ...any system Harsco Industrial Patterson Kelley cannot be responsible for the design or operation of such systems and a qualified engineer or contractor must be consulted 2 SAFETY 2 1 GENERAL The P K Du...

Страница 5: ...ntact Harsco Industrial Patterson Kelley Technical Service at 570 476 7261 or toll free at 877 728 5351 2 3 SAFETY FEATURES It is the responsibility of the customer to maintain the safety features suc...

Страница 6: ...Burn hazard Hot fluids Use caution when servicing or draining the P K Duration II system Isolation valves are provided on all inlets and outlets for your convenience Close the applicable isolation val...

Страница 7: ...d by a qualified installer service agency or gas supplier 3 1 RECEIVING AND STORAGE 3 1 1 Initial Inspection Upon receiving the P K Duration II system inspect it for signs of shipping damage Since som...

Страница 8: ...piping is constructed and stamped in accordance with ASME Boiler and Pressure Vessel Code Section VIII with a standard 150 psig set pressure 3 3 SETUP 3 3 1 Foundation and Placement Provide a firm lev...

Страница 9: ...omestic hot water capacity in a 32 wide x 64 long footprint and requires four 4 piping connections to operate as seen below A DHW Supply 2 Sweat Ball Valve B DHW Return 2 Sweat Ball Valve C Boiler Wat...

Страница 10: ...th the curved red arrow middle 3 4 2 1 Boiler Piping Figure As the domestic hot water supply temperature drops below the desired setpoint the control valve actuates allowing the flow of hot boiler wat...

Страница 11: ...mage which shows the manifold The Boiler water is piped to each heat exchanger from one connection point limiting the requirement for multiple connections provided the same boiler water is required to...

Страница 12: ...ining flow across the temp gauges and RTD Minimizes heat exchanger scale formation by maintaining velocity across the plates Inhibits bacterial growth by preventing stagnant water conditions As domest...

Страница 13: ...er heating system does not require a domestic water storage tank if hot water is constantly available for the 3 way valve If using in conjunction with a boiler the initial call for heat takes time unt...

Страница 14: ...Domestic Water Flush the domestic water periodically by using the drain valve located on the DHW supply line Bottom At the same time the strainer should be checked and cleaned properly NOTICE Under no...

Страница 15: ...rain valve on the boiler water strainer once a steady flow of water occurs STEP 5 Open the manual isolation valves on the inlet of the boiler piping STEP 6 Check for any leaks in all piping connection...

Страница 16: ...mpt to operate a P K Duration II system that has failed to pass all the safety checks described below After checking controls by manual adjustment make sure they are always reset to their proper setti...

Страница 17: ...is changed The up and down buttons are used to change the values of the parameters 4 1 1 Controller Operation To change the setpoint press the up or down buttons to change SV to the desired value Once...

Страница 18: ...llustrate the correct positioning for the various valve actuators NOTICE For water to water applications or when valve is oversized equal percentage valves are the preferred type 4 2 1 Siemens Valve A...

Страница 19: ...g information 5 1 2 Weekly Check for leaks in the boiler piping and the domestic piping Correct immediately if discovered 5 1 3 Monthly Check all relief valves by slightly opening the stem Once you se...

Страница 20: ...circulator pump Be sure water is flowing through the recirculation pipe Check valves in pipe line must be operational Check for proper boiler water flow 5 2 5 Domestic water temperature is too high or...

Страница 21: ...DED SPARE PARTS Circulator Pump bearing and seal assembly Dial Thermometers Temperature sensor RTD Temperature Controller Relief Valve Thermostat for over temperature control Use of Non Factory Author...

Страница 22: ...P K DURATION II Indirect Domestic Water Heating System 22 6 2 WIRING DIAGRAM...

Страница 23: ...TION II Indirect Domestic Water Heating System 23 6 3 MODELS 6 3 1 Boiler Piping CALLOUT TAG PART DESCRIPTION 1 3 WAY ELECTRONIC CONTROL VALVE 2 2 BALL VALVE 3 WYE STRAINER 4 STRAINER BLOW DOWN VALVE...

Страница 24: ...ye Strainer 2 2 Pressure Gauge XX XX PSI 3 Temperature Gauge XXF XXF 4 Automatic Air Vent 5 Section VIII Pressure Only Relief Valve 6 2 Ball Valves 7 Wye Strainer Blow Down Valve 8 Recirculation Pump...

Страница 25: ...rect Domestic Water Heating System 25 6 3 3 Control Panel and Heat Exchanger TAG NUMBER PART DESCRIPTION 1 POWER LIGHT 2 HIGH LIMIT LIGHT 3 DISCONNECT SWITCH 4 TEMPERATURE CONTROLLER 5 FUSES 6 HEAT EX...

Страница 26: ...ovided by Seller the defective item will become the property of Seller Transportation to Seller s facility or other designated facility for repairs of any products or party alleged defective shall in...

Страница 27: ...val installation or reinstallation charges any material and or permits required for installation reinstallation or repair charges to return the boiler and or components L INCIDENTAL SPECIAL OR CONSEQU...

Страница 28: ...P K DURATION II Indirect Domestic Water Heating System 28...

Отзывы: