MACH
®
C750-C1050 Outdoor Boilers
7
2.4 E
XHAUST
V
ENT
I
NSTALLATION
This MACH
®
Outdoor Boiler is designed for outdoor use only.
See MACH
®
C750-C1050 Installation & Owner’s Manual
for additional venting requirements.
2.4.1
Exhaust Vent System Installation
(Customer Supplied)
The exhaust vent should extend a minimum of 12 inches above the hood or at least two (2) feet above
the highest part of any independent structure within ten (10) feet of the vent.
Boiler clearance for combustibles / non-combustibles should be maintained per MACH
®
C750-C1050
Installation & Owner’s Manual.
2.4.2
Stainless Steel Exhaust System
Install manufactured exhaust vent systems in accordance with the manufacturer’s listing and instructions.
2.4.3
Stainless Steel Adapter
An adapter is required to be installed between the boiler and the stainless venting. Below is a
table containing the available adapter for each MACH
®
boiler size. Installer should use Adapters
listed below or equivalent.
MACH
®
Boiler Size
Nominal Stack
Size
Stainless Adapter for Stainless Vent
Supplier / Part Number
C-750,C-900,C-1050
8"
Heat-Fab / 9801MACH
Stainless Steel Adapter for Stainless Steel Vent
2.5 CPVC
E
XHAUST
V
ENT
S
YSTEM
This MACH
®
Outdoor Boiler is designed for outdoor use only.
See MACH
®
C750-C1050 Installation & Owner’s Manual
for additional venting requirements.
2.5.1
Stainless Steel Adapter for CPVC
An adapter is required to be installed between the boiler and the CPVC venting. Below is a table
containing the available adapter for each MACH
®
boiler size. Installer should use Adapters listed
below or equivalent.
The boiler vent should be installed per this manuals instruction. The
information contained herein should be used as a guide only and is not intended to be used in lieu of
qualified technical expertise. Failure to comply may result in injury or death.