2-44
888-2586-001
9/15/06
WARNING: Disconnect primary power prior to servicing.
Platinum Z16HD+
Section 2 Installation & Initial Turn-On
Many transmitters are located at the end of a long transmission line which is highly
susceptible to transient phenomena. Devices such as Metal Oxide Varistors are
inexpensive and very effective in reducing over voltage spikes. These units are limited
in the amount of energy that can be dissipated, but will handle, if designed properly,
very large currents. You can’t take a direct lightning hit and still operate, but not many
things will. It has been reported by engineers that installation of a third transformer and
transient protection devices, have eliminated the difficulty.
2.11.5 3 Phase Wye Distribution Transformers
The WYE connected system is also considered a symmetrical form of three phase
power distribution. All impedances are balanced as seen from each terminal, see Figure
2-20. It is important when using a WYE connected system that the fourth wire (neutral)
is connected to the mid-point of the system as shown in the diagram. When this
connection is made it provides a path for the zero sequence currents as well as any
harmonic currents which are generated due to the rectification of the secondary
voltages.
Figure 2-20 3 Phase 4 wire WYE Configuration
Содержание Platinum Z16HD+
Страница 4: ...MRH 2 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...9 15 06 888 2586 001 MRH 1 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...