2-20
888-2586-001
9/15/06
WARNING: Disconnect primary power prior to servicing.
Platinum Z16HD+
Section 2 Installation & Initial Turn-On
NOTE:
The single phase Z16HD+ requires a dual single phase feed, one to each cabinet.
The fuse ratings on the outline drawing are rated for each feed, not both. Each
cabinet should be fused separately.
2.5.7.1
Information concerning some 360 to 416 volt systems
This transmitter is equipped with MOVs (metallic oxide varistors) which provide a
measure of protection against incoming overvoltage transients. However, the selection
of some of the MOVs relies upon knowing the approximate voltage from each AC
phase to ground. Unfortunately a few AC power systems around the world do not have
a direct connection to earth ground, thereby making it impossible to predict the phase-
to-earth ground voltage.
In a typical 380 volt system that has a connection to earth ground, each AC phase will
measure about 220 volts to ground. The phase-to-phase, and phase-to-ground voltages
should be balanced within a few percent.
However, in a system which has no direct connection to earth ground, each AC phase
will measure a voltage which follows no particular pattern. In such a case, the MOV
protection may need to be modified. Please consult with an electrician if this applies to
your installation. If applicable, the phase-to-earth 275 volt MOVs in the RV7 through
RV13 and RV20 positions may be replaced with 510 volt MOVs (Harris part number
5600042000, quantity 8).
For safety reasons, you also must install a 4 pole disconnect device if your neutral line
is not connected to earth ground.
NOTE:
Install the exciter input cables in a metal conduit which is separate from the AC
supply. Remote control cabling may be included in the same conduit with the
exciter cabling. AC power wiring and small signal lines should never be put in
the same conduit.
Содержание Platinum Z16HD+
Страница 4: ...MRH 2 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...9 15 06 888 2586 001 MRH 1 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...