Harrington Signal HS-3100 Скачать руководство пользователя страница 37

HS-3100/3200 Programming Manual

31

Code Bells:

 Checking this option causes 

only selected coded bells 

to sound coded

signals. If coded bells are used the following options are then also shown:

-- No Restore:

 If checked, the panel does not sound the Code again when the input

restores. If not checked, the panel sounds a single round of the Code when the input
restores

-- Code:

 This is the sequence that is sounded when an alarm is received on this input. It

can be up to 4 digits long. Hexadecimal digits are used, thus each digit can be from 1 to
F, where A=10, B=11, C=12, D=13, E=14 and F=15.

-- Round: 

This is the number of times the Code is repeated. It can be between 1 and 4

times for no restore inputs, and between 2 and 4 for restore inputs. Note: A minimum of
three rounds of code is required per NFPA 72.

Night Sens. and Day Sens.: 

Selects the Alarm threshold sensitivity for addressable

smoke sensors. Heat sensors always use Normal sensitivity. Increased sensitivity causes
alarms at lower levels of smoke. Sensors not attached to a switch always use the Night
Sensitivity. Sensors attached to a switch use Night Sensitivity while the switch is Off and
Day Sensitivity while the switch is On. Night Sensitivity must always be equal to or more
sensitive than the Day Sensitivity.

Manual Restart:

 Check this to require that the control module not be reset by 

System

Reset

 but by 

Manual Restart

. Use of this option requires that there be a 

Manual Restart

function key assigned to the panel.

Trigger Manual Restart: 

Check this option to have a monitor module generate a Manual

Restart when activated. Module Restart must have Non-reporting function.

Pushbuttons

The push buttons located on the right hand side are:

Exit: 

Closes the window and returns to the previous window.

Devices:

 Opens the Devices Window for the current circuit (Circuits Window only).

Copy: 

Copies the circuit/device information, relates and message from another input to

the current input (see Figure 21). The current input does not have to be defined. Relates
cannot be copied between conventional and addressable input points. The 

Panel ID,

Circuit ID

 and 

Device ID

 (not always shown) list the circuit/device to be copied from.

Marking 

Transfer Main Definition

 copies the listed circuit/device type and function to the

current circuit/device. 

Note:

 Not all inputs can be copied to all other possible inputs.

Marking 

Transfer Relates

 copies the relates from the listed circuit/device relates to the

current one. This may cause some invalid relates. Marking 

Transfer Message

 causes the

message to be copied. Marking 

Transfer Devices

 (if shown) copies any device definitions

that the listed circuit contains. These devices copy messages and relates as based on
those settings above. There is no checking made at this time as to the validity of the
values copied. 

Unexpected results can occur if care is not taken.

 For each database

that is created, a warning about using copy is shown. Marking the check box in the
warning stops the box from appearing again for the database. This option can help speed
up the creation of a database. By completely defining one input, these values can be
copied to all other inputs, making any minor changes that are required after the copy.

Figure 18: Copy Window

Содержание HS-3100

Страница 1: ...Harrington Signal HS 3100 3200 Fire Alarm Control Unit Programming Manual Revision 1 January 2009 Document LT 2001HAR HARRINGTON FIRE ALARM SIGNAL INC...

Страница 2: ......

Страница 3: ...12 2 6 Panel Window 14 2 7 Outputs Dialog 17 2 8 Options Dialog 19 2 9 Circuits and Devices Windows 28 2 10 Internal Circuits Window 32 2 11 Relate Window 34 2 12 Pushbuttons 35 3 0 LCD Programming 36...

Страница 4: ......

Страница 5: ...e 11 Dialer Configuration 1 24 Figure 12 Dialer Configuration 2 25 Figure 13 Call Directions 26 Figure 14 Zone Data 27 Figure 15 Dialer Maintenance and Common Reporting Codes 27 Figure 16 Circuits Win...

Страница 6: ......

Страница 7: ...by the HS2 program otherwise a Database Mismatch trouble condition is generated This condition disables the panel until a correct HS2 program is loaded 5 The database must be completely loaded for it...

Страница 8: ...M500M Monitor module Classes A B initiating M501M Mini Monitor module Class B initiating M502M Monitor Module for 2 wire smoke detectors Classes A B initiating M500S Control module M500R Relay Module...

Страница 9: ...e The available bases are The sensor LED activates the relay and sounder bases When this LED stays on for more than 10 seconds the base activates This requires that the HS 3030 have the LED mode set t...

Страница 10: ...00 always ignores illegal modules Wrong Type U This occurs if the device is not the type expected for the address For example the database lists an address to have a ion smoke detector but a photo smo...

Страница 11: ...zero disables this function Once this is done wire the power for the device as shown in Figure 1 A third party power supply must be UL ULC listed compatible power supply suitable for fire application...

Страница 12: ...upted delete it and rename its BAK backup file to have a DBA extension This restores the database to the state prior to the last editing session Panel Description The HS 3200 has two Class A or B SLCs...

Страница 13: ...n for the entire network If coded bells are required the bell codes are defined for each input individually The following options are available Alert A First Stage alarm activates the selected bells i...

Страница 14: ...sounds Steady continuously or uses a Temporal pattern as specified in ANSI S3 41 and ISO 8201 Audible Emergency Evacuation Signal The pattern used s On s Off s On s Off s On 1 s Off repeated Waterflow...

Страница 15: ...zer The Pre Alarm Buzzer when enabled will cause a tone to sound when an addressable device is in alarm during the Retard period The tone is a triple beep repeated every second Master ID Master ID def...

Страница 16: ...nel is currently defined the Add Panel Box is displayed Switches Displays the Switches Window This window determines which devices are attached to the switches and the timers associated to each switch...

Страница 17: ...all 16 possible switches and highlights the current one Select any one to make it the current switch List entries show the message RELATES FOUND for switches that have related devices HH MM Timer The...

Страница 18: ...User Guide Verify List Displays the Verify List If there is no Verify List a requester will appear asking whether you wish to perform a verification See section 2 6 5 of the Network Plus User Guide f...

Страница 19: ...new group can have any number between 1 and 250 By default the number is the next one available There is no need for the groups to be sequentially numbered or to start at 1 Delete Group This removes...

Страница 20: ...ed panel as its Next ID Delete Remove the current panel from the system All programming for that panel will be lost Any of the panel s outputs that are referenced will become invalid and will be remov...

Страница 21: ...Outputs Button to show the Outputs Dialog see the Outputs Dialog section which allows for the programming of the Outputs and the relays The Options button displays the Options Dialog see the Options...

Страница 22: ...for programming see Figure 10 The LCD check box is located immediately left of the buttons It indicates whether or not the annunciator has an alpha numeric LCD This setting is used by NP only to dete...

Страница 23: ...s is located below the Common LED setting It is not displayed for HS 3134 Annunciators This option enables double or disables single the COM 1 network port If both ports are enabled the Next ID text b...

Страница 24: ...ow Supv The output sounds when there is any supervisory condition present on the panel Pressing Acknowledge silences the circuit Follow Trouble follow Trbl The output sounds when there is any trouble...

Страница 25: ...t or Level 1 Disconnect Disconnect sets the privilege level required for the Disconnect and Test Mode Hot Keys These can be set to Level 1 default or Level 0 If Level 0 is chosen the Disconnect Hot Ke...

Страница 26: ...he time between digits is three times this speed The time between rounds is seven times this speed Note that a minimum of three rounds of coded bells is required per NFPA 72 Maintenance Margin Mainten...

Страница 27: ...eceived by the panel System Reset System Reset resets part or all of the system The green LED flashes when the system or part of the system can be reset The yellow LED flashes when there are conventio...

Страница 28: ...Test Mode Places panel into test mode Press again to return to normal mode The red LED will flash while in test mode This function can be set to Privilege Level 0 or 1 It follows the Disconnect privil...

Страница 29: ...iates the general evacuation sequence All bells are activated in Evacuation mode selected function relays are activated and selected releaser circuits are activated and municipal alarm relay is activa...

Страница 30: ...ialer will use the third telephone number only if all attempts to communicate to the first telephone number fail If all attempts to communicate to the third number also fail a failure to communicate t...

Страница 31: ...s When 40 60 is selected the pulse dialing make break ratio is the 40 60 When 33 67 is selected the pulse dialing make break ratio is 33 67 The Handshake option determines the handshake used for BPS t...

Страница 32: ...for a valid initial handshake from the receiver after dialing the programmed telephone number Call Directions The Call Directions dialog see Figure 13 contains the options that determine which teleph...

Страница 33: ...Reporting Code Zone Alarm Restoral Reporting Code Trouble Reporting Code Trouble Restoral Reporting Code Supervisory Reporting Code Supervisory Restoral Reporting Code Dialer Maintenance and Common R...

Страница 34: ...ddressable input circuits The Devices Window see Figure 17 allows for the defining of addressable devices These two windows are nearly identical Most controls on one are found on the other with the fe...

Страница 35: ...B Style B wiring and an end of line resistor This must be chosen for M500DM M501M and M503M modules Monitor Class A This is a standard monitor module using Class A Style D wiring This can be used only...

Страница 36: ...inputs operate LEDs only no other outputs are allowed This function type is assigned by NP automatically Message The Message is located in the middle of the top of the window This 3 line by 20 charac...

Страница 37: ...to have a monitor module generate a Manual Restart when activated Module Restart must have Non reporting function Pushbuttons The push buttons located on the right hand side are Exit Closes the windo...

Страница 38: ...t of all the internal circuits Some of the internal circuits are Internal Circuit 0 General Alarm This is the General Alarm function General Alarm can be received from an annunciator or from an SE 200...

Страница 39: ...hbuttons The following push buttons are available List Entries This new feature allows the user to control the information displayed Relevant only lists items applicable to the current version only Al...

Страница 40: ...left corner of the window It lists all the panels both Control and Annunciator that are defined in the system along with their panel message The high lighted entry in the list is the one that is being...

Страница 41: ...rs or control modules defined Each entry shows the devices s address panel circuit device its state and its device message The states are on for selected and blank for not selected Devices that are no...

Страница 42: ...o display other menus show information or request information Menus have a or next to the description of each item Use the arrow keys on the keypad to move the cursor and press Enter to select In Figu...

Страница 43: ...is recorded in the archive Calibrate Calibrates the clock so that it keeps correct time Calibration takes 2 to 45 days Waiting longer gives more accurate results The panel functions normally while ca...

Страница 44: ...Line 4 Menu Options listed below The menu has the following options OK Return to Program Menu Test Force an immediate battery test Calibrate This function is restricted to Privilege Level 2 This calib...

Страница 45: ...input mode OFF Select bypassed devices to be returned to normal operation Each bypassed device is listed in order Select next to keep the bypass on or select OFF to remove the bypass After the last d...

Страница 46: ...s required access to the menu is denied This function allows for the manual operation of the relays There are three possible states Automatic state determined by inputs Forced On or Forced Off This mo...

Страница 47: ...the length of time the panel will wait before reporting the GRID package off line This can be set from 10 to 255 seconds Disconnect If enabled the Common Disconnect hot key will shut down Port 3 The...

Страница 48: ...e Passcodes are four digit numbers in the range 1000 to 9999 Type in the new passcode and press Enter to accept Asterisks are displayed instead of the numbers Clear removes any digits typed If no digi...

Страница 49: ...tion a minus sign refers to a restoral or off condition and an equal sign refers to a one time event Archive Alarm List Description A ALARM Alarm B bypass Bypassed Circuit Device C com Comlink D dupl...

Страница 50: ...ne Description 0 General Alarm 802 Privilege Level 1 Initiating Circuit 1 81 1st Stage Alarm 2 Initiating Circuit 2 82 2nd Stage Alarm 50 Network Verify 83 Switch 51 Comlink 1 84 Test Mode 52 Comlink...

Страница 51: ...ber Comlink 6 Zone 54 Unit ID Number 1 8 MR 2614 9 16 MR 2644 239 City tie 240 MRDL City tie Output Supervision Zone 60 Output Circuit Number Auxiliary Power Supervision Zone 61 Auxiliary Power Circui...

Страница 52: ...Reset 010 Common Disconnect 011 General Alarm 016 Switch 1 On 017 Switch 2 On 018 Switch 3 On 019 Switch 4 On 020 Switch 5 On 021 Switch 6 On 022 Switch 7 On 023 Switch 8 On 024 Switch 9 On 025 Switc...

Страница 53: ...itch 16 Off 051 Manual Restart Network Reboot Zone 92 Unit ID of panel broadcasting the command Network Reboot Required Who Zone 94 Unit ID of panel generating the Network Reboot Required trouble Netw...

Страница 54: ...a few minutes Unfortunately fire alarm control panels need both of these characteristics that is driving a heavy bell load for a relatively short time at the end of a 24 hour standby current drain Thi...

Страница 55: ...1 stop bit for communication over the serial port The default baud rate is 9600 bps All screens have a common status line across the top It shows from left to right the current time the current date t...

Страница 56: ...o the beginning of the list 10 Miscellaneous Troubles Display a list of all the troubles currently displayed by the STATUS MISC TROUBLES selection from the LCD 11 Output Supervision Shows the current...

Страница 57: ...s 0 V Clear counters on screen 19 Port 3 Shows the current status ID frame count and baud rate for the central station communications link A question mark will appear in front of the baud rate when th...

Страница 58: ...5 seconds The remote panel stops sending data after 15 minutes Commands id N Display the service terminal for Panel id Esc Disconnect remote connection 69 Network Verify Displays the current status of...

Страница 59: ...um Maximum Values 0 P Energize both sets of terminals 1 P Energize only B terminals 2 P Energize only A terminals 85 Alarms For a single circuit shows a grid displaying the current Alarm Early Warning...

Страница 60: ...erminals 90 Analog Displays the analog values of 10 consecutive addresses for a single circuit Commands A Display next device address A Display selected device at address 0 M Reset Minimum Maximum Val...

Страница 61: ...th date year D Enter the date and year The year may be entered as 00 to 99 in a two digit format or as 1991 to 2090 in a four digit format hours minutes T Set the time hours minutes seconds T Set the...

Страница 62: ...hen Dialer Direction Contact ID Auto Rep Codes SIA Auto Rep Codes Zone Supv Rest zone goes into supervisory restore 2 S R AA See Table 4 Zone Alarms Rest zone goes into alarm alarm condition has been...

Страница 63: ...r Alarm 24 Hour Non Fire 1 A1 Emergency Panic Alarms 1 51 Gas Detected 1 A2 Fail to Report In 1 2A Panic 1 52 Refrigeration Fire Alarms 1 21 Duress 1 53 Loss of Heat 1 1A Fire Alarm 1 22 Silent 1 54 W...

Страница 64: ...Harrington Signal Inc 2519 4th Avenue Moline IL 61265 HARRINGTON FIRE ALARM SIGNAL INC...

Отзывы: