HS-3100/3200 Programming Manual
7
2.3 System Window
Description
The System Window (see
Figure 2
) allows editing of all system level options, as well as detailing
other system wide information.
The Title Bar of the window shows whether editing or viewing of the database is being preformed
and the name of the current database.
Figure 2: Network Plus System Window
The text in the top left corner provides information about the database. The top line gives the date
and time the database was last edited. The next line states whether the current contents have
been verified or not; and whether the database has been compressed or not.
The options
Bell System, Subsequent Alarm, Resound, Evac
and
Waterflow
all affect how the
notification appliance circuits (NAC), hereafter referred to as bells, react to alarm conditions.
Bell System
Bell System is a drop down list for selecting how the bells and strobes will operate. This sets the
base operation for the entire network. If coded bells are required, the bell codes are defined for
each input individually. The following options are available:
•
Alert:
A First Stage alarm activates the selected bells in Alert mode. If the
Signal Silence
or
Second Stage Inhibit
Hot Key is not pressed before the
[No Acknowledge] Second
Stage Inhibit
timeout, the panel will progress to Second Stage. Second stage will activate
all bells in Evacuation mode.
•
Evac:
A First Stage alarm will activate selected bells in Evacuation mode. Second Stage
will activate all bells in Evacuation mode. There is no timeout from First to Second Stage.
•
Alert/Evac:
A First Stage alarm activates the selected bells in Evacuation mode and all
other bells on the panel in Alert mode. If the
Signal Silence
or
Second Stage Inhibit
Hot
Key is not pressed before the
[No Acknowledge] Second Stage Inhibit
timeout, the system
will progress to Second Stage. Second Stage will activate all bells in Evacuation mode.
•
Staged:
The 1st alarm will activate selected bells in Alert mode. If the
Signal Silence
or
Second Stage Inhibit
Hot Key is not pressed before the
[No Acknowledge] Second Stage