11
The heat pump will produce condensation (water) operating. The heat pump base is designed to allow the
condensation to exit through the bottom drain port. The condensation will increase as the outdoor air humidity
level increases. Check the following at regular intervals to ensure proper condensate drainage:
1.
Visually inspect and clear the bottom drain port of any debris that could clog the port.
2.
Keep the air intake area and discharge area clear of debris so the airflow through the heat pump is not
restricted. The cooler discharge air should not accumulate and be drawn into the side air intake coils.
During normal operation, the heat pump produces ten to twenty liters of condensation per hour. If
condensation drainage is above this range during operation or if water continues to drain from the base
when the heat pump is not in operation for more than an hour, a leak in the internal plumbing may have
occurred. Call a qualified heat pump technician to investigate the problem.
A quick way to verify that the water running through the drain is condensation water is to shut off the unit and
keep the pool pump running. If the water stops running out of the base pan, it is condensation water.
Display settings
1.Under running status, press
to adjust the temperature
2.
Press
"
M
"
to choose the mode
Press "M
“ again
for cooling
Press "M
“again
for heating
3.
Standby status:
Press "M" 5 seconds,
get a sound “B” ,LCD display will show “0" “27”
.
Press “SET” to enter cooling
temp. setting, press
to alter cooling temp.
Press “SET”
again to confirm.
Press "M again" "1
27" Press “SET” to enter heating temp.
setting, press
to alter heating temp.
Press “SET”
again to confirm.
Press "M again" " "2
40" Press “SET” to enter defrosting time
setting, press
to alter defrosting time.
Press “SET”
again to confirm.
Press "M" again "3" "-
7" Press “SET” to enter defrosting temp.
setting, press to alter defrosting temp.
Press “SET”
again to confirm.
Press "M"
again "4" "13 " Press “SET” to enter exit defrosting temp.
setting, press to alter exit
defrosting temp.
Press “SET”
again to confirm.
Press "M"
again "5" "8 " Press “SET” to enter exit defrosting time
setting, press to alter exit defrosting
time.
Press “SET”
again to confirm.
Press "M"
again "6" "1 " Press “SET” to enter
system quantity setting, press to alter system quantity.
Press “SET”
again to confirm.
Press "M"
again "7" "1 " Press “SET” to enter Automatic
setting, press to alter.
Press “SET”
again to
confirm.