Installation

Installing 

Place the stove on a non-combustible floor protector that extends a minimum of 6 inches to the front (152mm), 6 inches 

to the sides (152mm) and 0"(152mm) to the rear, which is flush with the rear of the hopper. Front and side floor protection 

measurements are made from the firebox or window opening. Floor protection must also be positioned under horizontal flue 

pipe, extending 2" (51mm) beyond each side of the pipe. 

NOTE for Canadian installation only:

  Per  ULC-S627-00,  If  installed  on  a  combustible  floor,  the  need  to  provide  a 

noncombustible 

floor protector 

covering the area beneath the 

space heater 

and extending at least 17.72" (450mm) on the 

firing side and at least 7.87" (200mm) on the other sides.

In Canada, you may follow smaller U.S. floor protection requirements ONLY if the user agrees to completely shut-

down the appliance, and allow it to cool to where all fire is extinguished and the combustion blower and its indicator 

light shuts off, prior to opening the firebox door or ash door.

The minimum floor protector material is 20 gauge sheet metal. Other floor protector materials are ceramic tile, stone, brick, etc.
Place the stove away from combustible walls at least as far as shown in Figures 2 and 3.
Note that the clearances shown are minimum for safety but do not leave much room for access when cleaning or servicing. 

Please take this into account when placing the stove.

Floor Protection

L

J

Floor Protection 

Requirements

US

Canada

Sides

Rear

6" 

200mm

0" 

200mm

K

Front

6" 

450mm

Floor protector minimum: 40" X 40" 

(1016mm X 1016mm)

NOTE:

 Measurement 

"K" is measured from 

the glass in the US 

ONLY

K

J

Canada

L

J

USA

Floor Protection

6.25"

159mm

6.25"

159mm

Floor Protection

12"/ 305mm

3"/ 76mm

Fig. 3

Alternate floor protector dimension may be used as long as 

they satisfy the measurement requirements shown below.

Minumum size floor protection for a corner installation hearth 

pad is 36" x 36". Clearance shown as 9" with optional side 

shields installed.

Corner to edge dimension for corner installation floor protection.

Floor Protection

45-7/8”

Fig. 2

Содержание XXV Freestanding Pellet Stove

Страница 1: ...tallation MUST comply with local regional state and national codes and regulations Contact local building or fire officials about restrictions and installation inspection requirements in your area Tes...

Страница 2: ...hich does not flow properly through the feed system NOTICE Hearth Home Technologies is not responsible for stove performance or extra maintenance required as a result of using fuel with higher ash or...

Страница 3: ...nly with 5mm ceramic available from your dealer For further instruction refer to owner s manual Keep viewing and ash removal doors tightly closed during operation CLEARANCES TO COMBUSTIBLES Back Wall...

Страница 4: ...XV fusing the highest caliber pellet stove innovations with the allure of cast iron Assembly Installation 5 Installation 6 Venting 8 ESP Control 16 Low Draft Voltage Adjustment 17 Automatic Operation...

Страница 5: ...tion and repair of this Harman stove should be done by a qualified service person We recommend that the stove be inspected before use and at least annually by a qualified service person Periodic clean...

Страница 6: ...combustion blower and its indicator light shuts off prior to opening the firebox door or ash door The minimum floor protector material is 20 gauge sheet metal Other floor protector materials are cera...

Страница 7: ...ag screws 2 The unit must be connected to outside air See page 10 3 Floor protection and clearances must be followed as shown above 4 The appliance must be properly grounded to the frame of the mobile...

Страница 8: ...pipe G The clearance to an inside corner is 12 H A vent must not be installed within 3 feet 90cm above a gas meter regulator assembly when measured from the horizontal center line of the regulator I...

Страница 9: ...ions of pipe lock together to form an air tight seal in most cases However in some cases a perfect seal is not achieved For this reason and the fact that the XXV operates with a positive vent pressure...

Страница 10: ...est located on the same exterior wall as the exhaust vent outlet and located lower on the wall than the exhaust vent outlet When the appliance is roof vented The air intake is best located on the exte...

Страница 11: ...increase fire risk 2 Preferred method This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent sho...

Страница 12: ...de diameter of this liner should be 4 Either flexible or rigid liner may be used for this purpose Refer to Method 6 Be sure to design the venting so that it can be easily cleaned Venting 4 Installing...

Страница 13: ...et vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Installing into...

Страница 14: ...nnector manufacturers recommendations Due to combustible fuel vent pipe to hopper clearances must meet guidelines stated by NFPA or local codes 8 Installing through the ceiling Through the ceiling ven...

Страница 15: ...walls of the house and to prevent re entry of soot or ash into the house Maintain specified clearances to windows doors and air inlets including air conditioners Vents should not be placed below venti...

Страница 16: ...lector Allows you to choose between Room Temp Mode Stove Temp Mode or OFF Also allows you to vary the distribution blower speed by turning the knob to the high or low side of each mode Feed adjuster S...

Страница 17: ...tor or the igniter to operate Combustion Motor Speed Control Low draft only set point The small straight screwdriver slot is plastic therefore the unit can be adjusted while in operation Fig 29 Low Dr...

Страница 18: ...ature to your desired setting In the Room Temperature Mode you can select either Auto or Manual modes for the igniter using the igniter toggle switch When the toggle switch is in the Auto position the...

Страница 19: ...amount of time per cycle that the feed motor is allowed to run Based on the control settings and temperature demand the control will make it s own determination of how long to run the feed motor UP T...

Страница 20: ...llets set the feed adjuster to 4 Fig 22 This is a conservative number and will probably need to be increased After you know a feed rate setting that works well use that setting Remember if your feed r...

Страница 21: ...e as AUTO settings The blower will shut off completely if the temperature on the ESP is too low Igniter Switch to MANUAL Stove Temperature Mode The advantage of this mode is to allow the operator to h...

Страница 22: ...ash bed is not obtainable it is not a problem The 1 ash bed is only a maximum burn rate and at most normal settings the ash bed will be larger Manual Cold Start Igniter Switch to MANUAL up position Ma...

Страница 23: ...to the desired location 50 maximum The room sensor should be installed in the location where you want to control the temperature In most installations locating the room sensor behind the stove near t...

Страница 24: ...gloves if the stove is not cooled down See Fig 33 2 Slide the ash pan back into the stove seating it against the rear of the firebox Lift the ash lip to close the ash door and then close the front do...

Страница 25: ...o lock into place and tightening the 3 wing nuts Be sure the fan plate is flush with the exhaust housing on the stove body and the motor armature points up toward the hopper 11 Slide ash pan into the...

Страница 26: ...off of the igniter element Figure 41 The igniter is made to be removable for service by insulated male female wire connectors These connections between the hot leads the wires inside the burn pot and...

Страница 27: ...n each screw evenly to avoid making any stress points Maintenance Pellet fines will accumulate in the feeder body over a period of time therefore a yearly inspection and cleaning of this must be perfo...

Страница 28: ...ust on the rear of the stove and extends it to the top with a six inch stub This gives the appearance of a wood stove and also allows venting with existing single wall connector A 12 inch piece of 4 p...

Страница 29: ...hopper 2 Draft is too low blocked flue 3 Something is restricting fuel flow 4 Hopper lid not closed properly 5 Feed motor or combustion blower has failed Trouble Shooting Cleaning Burn Pot Whenever y...

Страница 30: ...P MAX WATTS 625 240 VAC 50 HZ 2 6 AMP DISTRIBUTION BLOWER COMBUSTION MOTOR 2 OUTBOARD FEEDER MOTOR ACC XXV 1 LT BLUE LOW PRESSURE SWITCH N O CONTACTS 6 WHITE 11 PIN PLUG BLUE PART NO 3 90 00777E 10 IN...

Страница 31: ...ration Your appliance will recognize when power is restored What happens depends on ESP temperature and whether it is equipped with automatic ignition In Automatic setting units equipped with automati...

Страница 32: ...e construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs...

Страница 33: ...is warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is...

Страница 34: ...o 2 or 3 Set temperature knob to desired amount Turn mode selector knob onto Room Temp mode After the fire has lit watch that the fuel does not feed too fast that it pushes the red glowing fuel bed of...

Страница 35: ...35 XXV Pellet Stove 3 90 00885R17_02 15 Service Maintenance Log Date Of Service Performed By Description Of Service...

Страница 36: ...ting appliance boasts uncompromising attention to detail and helps preserve our planet by using environmentally responsible fuels Signature of Boxer Your premium quality hearth product designed and as...

Отзывы: