XXV Pellet Stove

3-90-00885R17_02/15

Minimum flue vent configuration

It is recommended that outside air be 

installed with this venting configuration 

to reduce smoke and creosote smell in 

the room in the event of power failure.

12"

venting

Fig. 18

Min. above ground level

Vent Configurations:

To reduce probability of reverse drafting during shut-down conditions, Hearth & Home Technologies strongly recommends:
•  Installing the pellet vent with a minimum vertical run of five feet, preferably terminating above the roof line.
•  Installing the outside air intake at least four feet below the vent termination.

To prevent soot damage to exterior walls of the house and to prevent re-entry of soot or ash into the house:
•  Maintain specified clearances to windows, doors, and air inlets, including air conditioners.
•  Vents should not be placed below ventilated soffits. Run the vent above the roof.
•  Avoid venting into alcove locations.
•  Vents should not terminate under overhangs, decks or onto covered porches.
•  Maintain minimum clearance of 12 inches from the vent termination to the exterior wall. If you see deposits developing 

on the wall, you may need to extend this distance to accommodate your installation conditions.

Hearth & Home Technologies assumes no responsibility for, nor does the warranty extend to, smoke damage caused 

by reverse drafting of pellet appliances under shut-down or power failure conditions.

12"

min. wall to outlet

36"             

min. clear

anc

e to an

combustable ma

terial

Fig. 19

Содержание XXV Freestanding Pellet Stove

Страница 1: ...tallation MUST comply with local regional state and national codes and regulations Contact local building or fire officials about restrictions and installation inspection requirements in your area Tes...

Страница 2: ...hich does not flow properly through the feed system NOTICE Hearth Home Technologies is not responsible for stove performance or extra maintenance required as a result of using fuel with higher ash or...

Страница 3: ...nly with 5mm ceramic available from your dealer For further instruction refer to owner s manual Keep viewing and ash removal doors tightly closed during operation CLEARANCES TO COMBUSTIBLES Back Wall...

Страница 4: ...XV fusing the highest caliber pellet stove innovations with the allure of cast iron Assembly Installation 5 Installation 6 Venting 8 ESP Control 16 Low Draft Voltage Adjustment 17 Automatic Operation...

Страница 5: ...tion and repair of this Harman stove should be done by a qualified service person We recommend that the stove be inspected before use and at least annually by a qualified service person Periodic clean...

Страница 6: ...combustion blower and its indicator light shuts off prior to opening the firebox door or ash door The minimum floor protector material is 20 gauge sheet metal Other floor protector materials are cera...

Страница 7: ...ag screws 2 The unit must be connected to outside air See page 10 3 Floor protection and clearances must be followed as shown above 4 The appliance must be properly grounded to the frame of the mobile...

Страница 8: ...pipe G The clearance to an inside corner is 12 H A vent must not be installed within 3 feet 90cm above a gas meter regulator assembly when measured from the horizontal center line of the regulator I...

Страница 9: ...ions of pipe lock together to form an air tight seal in most cases However in some cases a perfect seal is not achieved For this reason and the fact that the XXV operates with a positive vent pressure...

Страница 10: ...est located on the same exterior wall as the exhaust vent outlet and located lower on the wall than the exhaust vent outlet When the appliance is roof vented The air intake is best located on the exte...

Страница 11: ...increase fire risk 2 Preferred method This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent sho...

Страница 12: ...de diameter of this liner should be 4 Either flexible or rigid liner may be used for this purpose Refer to Method 6 Be sure to design the venting so that it can be easily cleaned Venting 4 Installing...

Страница 13: ...et vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Installing into...

Страница 14: ...nnector manufacturers recommendations Due to combustible fuel vent pipe to hopper clearances must meet guidelines stated by NFPA or local codes 8 Installing through the ceiling Through the ceiling ven...

Страница 15: ...walls of the house and to prevent re entry of soot or ash into the house Maintain specified clearances to windows doors and air inlets including air conditioners Vents should not be placed below venti...

Страница 16: ...lector Allows you to choose between Room Temp Mode Stove Temp Mode or OFF Also allows you to vary the distribution blower speed by turning the knob to the high or low side of each mode Feed adjuster S...

Страница 17: ...tor or the igniter to operate Combustion Motor Speed Control Low draft only set point The small straight screwdriver slot is plastic therefore the unit can be adjusted while in operation Fig 29 Low Dr...

Страница 18: ...ature to your desired setting In the Room Temperature Mode you can select either Auto or Manual modes for the igniter using the igniter toggle switch When the toggle switch is in the Auto position the...

Страница 19: ...amount of time per cycle that the feed motor is allowed to run Based on the control settings and temperature demand the control will make it s own determination of how long to run the feed motor UP T...

Страница 20: ...llets set the feed adjuster to 4 Fig 22 This is a conservative number and will probably need to be increased After you know a feed rate setting that works well use that setting Remember if your feed r...

Страница 21: ...e as AUTO settings The blower will shut off completely if the temperature on the ESP is too low Igniter Switch to MANUAL Stove Temperature Mode The advantage of this mode is to allow the operator to h...

Страница 22: ...ash bed is not obtainable it is not a problem The 1 ash bed is only a maximum burn rate and at most normal settings the ash bed will be larger Manual Cold Start Igniter Switch to MANUAL up position Ma...

Страница 23: ...to the desired location 50 maximum The room sensor should be installed in the location where you want to control the temperature In most installations locating the room sensor behind the stove near t...

Страница 24: ...gloves if the stove is not cooled down See Fig 33 2 Slide the ash pan back into the stove seating it against the rear of the firebox Lift the ash lip to close the ash door and then close the front do...

Страница 25: ...o lock into place and tightening the 3 wing nuts Be sure the fan plate is flush with the exhaust housing on the stove body and the motor armature points up toward the hopper 11 Slide ash pan into the...

Страница 26: ...off of the igniter element Figure 41 The igniter is made to be removable for service by insulated male female wire connectors These connections between the hot leads the wires inside the burn pot and...

Страница 27: ...n each screw evenly to avoid making any stress points Maintenance Pellet fines will accumulate in the feeder body over a period of time therefore a yearly inspection and cleaning of this must be perfo...

Страница 28: ...ust on the rear of the stove and extends it to the top with a six inch stub This gives the appearance of a wood stove and also allows venting with existing single wall connector A 12 inch piece of 4 p...

Страница 29: ...hopper 2 Draft is too low blocked flue 3 Something is restricting fuel flow 4 Hopper lid not closed properly 5 Feed motor or combustion blower has failed Trouble Shooting Cleaning Burn Pot Whenever y...

Страница 30: ...P MAX WATTS 625 240 VAC 50 HZ 2 6 AMP DISTRIBUTION BLOWER COMBUSTION MOTOR 2 OUTBOARD FEEDER MOTOR ACC XXV 1 LT BLUE LOW PRESSURE SWITCH N O CONTACTS 6 WHITE 11 PIN PLUG BLUE PART NO 3 90 00777E 10 IN...

Страница 31: ...ration Your appliance will recognize when power is restored What happens depends on ESP temperature and whether it is equipped with automatic ignition In Automatic setting units equipped with automati...

Страница 32: ...e construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs...

Страница 33: ...is warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is...

Страница 34: ...o 2 or 3 Set temperature knob to desired amount Turn mode selector knob onto Room Temp mode After the fire has lit watch that the fuel does not feed too fast that it pushes the red glowing fuel bed of...

Страница 35: ...35 XXV Pellet Stove 3 90 00885R17_02 15 Service Maintenance Log Date Of Service Performed By Description Of Service...

Страница 36: ...ting appliance boasts uncompromising attention to detail and helps preserve our planet by using environmentally responsible fuels Signature of Boxer Your premium quality hearth product designed and as...

Отзывы: