background image

6

ChImNEY & vENTINg

Types Of Chimneys

The chimney is one of the most important, yet most 

neglected and misunderstood portions of any solid 

fuel burning stove installation. Do not connect this 

stove to a chimney flue serving another heating de

-

vice.

THE STOVE MUST BE CONNECTED TO ITS OWN 

TILE-LINED FLUE. A MINIMUM FLUE SIZE OF 8” X 

8” IS NECESSARY FOR PROPER OPERATION.

UNDER NO CIRCUMSTANCES SHOULD A MANUAL 

FLUE DAMPER BE INSTALLED IN THE SMOKE 

PIPE BETWEEN THE STOVE AND THE CHIMNEY.

NO DAMPER, HEAT SAVER OR AUTOMATIC VENT 

DAMPER DEVICE SHOULD BE INSTALLED IN OR 

ON THE SMOKE PIPE.

CAUTION: THE CHIMNEY MUST BE A CLASS “A” 

CHIMNEY, IN GOOD OPERATING AND CLEAN 

CONDITION. 

NOTE: THE USE OF ALUMINUM TYPE “B” GAS 

VENT FOR SOLID FUELS IS UNSAFE AND PRO-

HIBITED BY THE NATIONAL FIRE PROTECTION 

AGENCY CODE.

There are three types of class “A” chimneys:

1. Masonry with tile liner, to include brick or stone. It 

must be supported on grade level foundation.

2. Insulated, manufactured chimney, listed or certified 

by a national test agency.

3. Triple-wall metal class “A” chimney, listed or certi

-

fied by a national test agency.

If your masonry chimney has not been used for some 

time, have it inspected by a qualified person. If a listed 

or certified manufactured chimney is to be used, make 

certain it is installed in accordance with the manufac

-

turer’s instructions and all local and state codes. 

The minimum recommended height for solid fuel 

chimneys is 6 feet from the stove collar. The chimney 

must be two feet higher than anything within ten feet. 

It also must extend three feet above the point where it 

intersects or exits the roof line. 

In order to have a properly operating solid fuel heat-

ing system, the chimney must be capable of provid

-

ing the necessary draft. The minimum required draft 

is .06 inches of water column (W.C.). This must be 

measured using a draft gauge. If the chimney cannot 

supply this constant draft, the stove will not operate 

properly. A barometric damper may be used and prop-

erly adjusted to compensate for excessive draft only.

 

IMPORTANT: When you measure the the draft, the 

stove must be operating with sufficient time given for 

the stove and chimney to warm. Burn for at least thirty 

minutes. The draft reading is best taken 18” up from 

the center of the flue outlet, in the connector pipe. Drill 

a hole in the pipe for the meter tube, and fill it with a 

screw or silicone when done with the test.

IMPORTANT: The connector pipe must be 4 gauge 

or thicker. 

When connecting the flue pipe to the stove, the first 

section should be installed inside the stove collar. It 

should be secured to the collar with, at least, three 

screws or rivets. 

Do not pass the connector pipe through a wall or 

ceiling without first checking with your local codes. If 

allowed, use only approved pass-thru methods.

NOTE: All horizontal runs of venting should have a /4 

inch of rise per foot of length.

Use no more than two 90° elbows in the connector. 

If a barometric damper is needed, to compensate for 

excessive draft, install it only in a vertical section of 

vent pipe.

The three foot, two foot, ten foot rule

Содержание SF 250

Страница 1: ...MAY RESULT FOR YOUR SAFETY FOL LOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Contact your local authorit...

Страница 2: ...Table of Contents Safety Considerations 3 Assembly 4 Installation 5 Chimney Venting 6 Operating Instructions 8 Preventive Maintenance 9 Optional Hot Water Coil 10 Testing Label 12 Warranty 13...

Страница 3: ...rate It has been verified that creosote will ignite at 650 degrees fahrenheit It is the owner s responsibility to follow these recommenda tions This stove consumes air when it is burning if your house...

Страница 4: ...The shaker handle installs onto the shaker handle mount using the two hex bolts and washers provided Firebricks The SF250 uses 14 standard firebricks as shown below These standard firebricks measure 9...

Страница 5: ...hould con sist of 3 8 millboard or a stove board providing equal protection k 84 R 45 The floor protection should extend 8 to the rear and either side and 16 in front of the stove The floor protection...

Страница 6: ...from the stove collar The chimney must be two feet higher than anything within ten feet It also must extend three feet above the point where it intersects or exits the roof line In order to have a pro...

Страница 7: ...uld be no more than two 90 elbows or the equivalent used in connecting the stove to the chimney flue H Shared Flue No more than one appliance shall vent into a single flue The most common cause of poo...

Страница 8: ...in between Loading Coal should only be added when there is a reasonably hot fire The coal bed should be bright and vigorous If the fire is burning hot and there is a deep bed of coals full loads can...

Страница 9: ...After cleaning the chimney any debris will be at the bottom by the clean out door Open the clean out and vacuum the loose debris Clean the smoke pipe from the chimney to the stove using a metal brush...

Страница 10: ...supplied nuts on each leg of the coil Place the coil through the holes in the stove and adjust the nuts so that the pipes stick out about 1 to 1 from the sidewall of the stove Put flat wash ers and nu...

Страница 11: ...2 Circulating pump method Used when the distance is more than ten feet or when the stove is on a higher level than the existing water heater In addition to a circulator you may want to add a aquastat...

Страница 12: ...testing label 12 This appliance is also approved for installation into a shop...

Страница 13: ...13...

Страница 14: ...14...

Страница 15: ...15 Notes...

Страница 16: ......

Отзывы: