 6

v

venting

requirements for Terminating the venting

wArNINg:

 Venting terminals must not be recessed 

into a wall or siding.

NOTE:

 Only pellet vent pipe wall pass-throughs 

and fire stops should be used when venting through 

combustible materials.

NOTE: 

Always take into consideration the effect  the 

prevailing wind direction or other wind currents will 

cause  with  flyash  and  /or  smoke  when  placing  the 

termination.

In addition, the following must be observed:

A. The clearance above grade  must be a minimum 

of 18".

1

B. The clearance to a window or door that may be 

opened must be a minimum of 48".

1

(

with outside air installed, 18”

)

C. A 12"  clearance to a permanently closed window  

is  recommended to prevent condensation on the 

window.

D. The vertical clearance to a ventilated soffit located 

above the terminal within a horizontal distance of 

2 feet (60 cm) from the center-line of the terminal  

must be a minimum of 18".

E. The clearance to an unventilated soffit  must be a 

minimum of 12".

F. The clearance to an outside corner is 11" from center 

of pipe.

G. The clearance to an inside corner is 12".

H.  A vent must not be installed within 3 feet (90 cm)  

above a meter/regulator assembly when measured 

from the horizontal center-line of the regulator.

1

I. The clearance to service regulator vent outlet must 

be a minimum of 6 feet.

1

J. The clearance to a non-mechanical air supply inlet to 

the building or the combustion air inlet to any other 

appliance must be a minimum of 48”.

1

K. The clearance to a mechanical air supply inlet must 

be a minimum of 10 feet.

1

(

with outside air installed, 6 feet 

)

L. The clearance above a paved sidewalk or a paved 

driveway located on public property must be a 

minimum of  7 feet.

1,2

M. The clearance under a veranda, porch, deck or 

balcony must be a minimum of 12 inches.

1,3 

(see b.)

NOTE:

  The clearance to vegetation and other exterior 

combustibles such as mulch is 36” as measured from 

the center of the outlet or cap. This 36” radius continues 

to grade or a minimum of 7 feet below the outlet.

1

Certain Canadian and or  Local codes or regulations 

may require different clearances.

2

A vent shall not terminate directly above a side-walk 

or paved driveway which is located between two 

single  family dwellings and serves both dwellings.

3

Only permitted if veranda, porch, deck, or balcony is 

fully open on a minimum of  2 sides beneath the floor.

NOTE: where passage through a wall, or partition of 

combustible construction is desired, the installation 

shall conform to CAN/CSA-b365. (if in  Canada)

Vent terminal

Содержание P61

Страница 1: ...MAY RESULT FOR YOUR SAFETY FOLLOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Contact your local authorit...

Страница 2: ...1 N O T I C E T h i s L a b e l C o p y I s F o r R e f e r e n c e O n l y C o n s u l t T h e A c t u a l U n i t L a b e l F o r C l e a r a n c e s A n d O t h e r S p e c i fi c I n f o r m a t i...

Страница 3: ...r even death SUITABLE FOR MOBILE HOME INSTALLATIONS SAVE THESE INSTRUCTIONS Harman Home Heating 352 Mountain House Road Halifax PA 17032 Testing Label 2 Assembly Installation 4 Venting 7 Operation 12...

Страница 4: ...rm a draft test for later comparison Remove the plug bolt on the underside of the firebox as shown Using the hole from the bolt attach a draft meter that is capable of reading at least 5 inches of wat...

Страница 5: ...lag screws through the 2 holes in the base plate 2 The unit must also be connected for the outside air See page 7 3 Floor protection and clearances must be followed as shown 4 Unit must be grounded to...

Страница 6: ...r assembly when measured from the horizontal center line of the regulator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 J The clearance to a non mechanical air suppl...

Страница 7: ...t achieved For this reason and the fact that the P61 operates with a positive vent pressure we specify that the joints also be sealed with high temp silicone Outside Air Outside air is optional except...

Страница 8: ...ide natural draft in the event of a power failure 1 Preferred method This method provides excellent venting for normal operation and allows the stove to be installed closest to the wall Two inches fro...

Страница 9: ...ot mandatory 5 Installing into an existing fireplace chimney This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure The dam...

Страница 10: ...vent pipe fittings Seal pipe joints with silicone in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 7 Installing into an existing chimney...

Страница 11: ...ith this venting configuration Min above ground level 18 Fig 15 Fig 16 Venting DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT DO NOT CONNECT THIS UNIT TOA CHIMNEY FLUE SERVING...

Страница 12: ...his resets the control for start up Turn Temp Dial to 7 This will allow the stove to burn at maximum for feed rate adjusting purposes Apply starting gel to pellets in burn pot and light the gel Close...

Страница 13: ...l consumption is sacrificed for exact room temperature Therefore as it gets colder more pellets will be burned automatically The distribution blower speed will vary according to the position of the mo...

Страница 14: ...e combustion occurring for more than 50 minutes See Troubleshooting section for more details Manual reset disconnect power cord for a few seconds and reconnect If error still occurs call your Dealer T...

Страница 15: ...5 feet from the unit or in another room are not recommended The room sensor is essential for the P61 s excellent efficiency NOTE It is recommended that the room sensor be installed even if only instal...

Страница 16: ...better performanc you ll have The stove will need to be cleaned for approximately every 2 to 5 tons of pellets burned The amount of pellets burned before cleaning will vary depending on the brand of p...

Страница 17: ...to determine if cleaning is necessary Maintenance Exposed blower wheel and flue opening NOTE ESP probe is visible ESP probe Fig 28 Blower cover removed ESP Probe Fig 29 Be careful not to damage ESP p...

Страница 18: ...rn Pot Whenever your stove is not burning take the opportunity to scrape the burn pot to remove carbon buildup A vacuum cleaner is handy to remove the residue Be sure the stove is cold if you use a va...

Страница 19: ...tions 12 375 34 5 9 32 375 23 5 29 5 Weight 249 lbs Blower 135 cfm Feed Rate 75 to 7 5 lbs per hr Hopper Capacity 72 lbs Fuel Wood Pellets Flue Size 3 inch Outside Air Size 2 3 8 in Inside diameter On...

Страница 20: ...20 Wiring Diagram...

Страница 21: ...without the optional decorative tile Slide the spring clip into the channel on one end of the frame Place the frame into the recessed area on the door inserting the clip end first The tension of the s...

Страница 22: ...ombustible materials Hopper Extension The hopper extension allows you to put more pellet fuel in the hopper and extends the burn time on one load of pellets The hopper extension adds 60 pounds to the...

Страница 23: ...are not covered Damage and or repairs including but not limited to remote controls filters fuses knobs glass ceramic brick panels ceramic fiber afterburners door packing tile ceramic log sets paint ba...

Страница 24: ......

Отзывы: