PP38+ Pellet Stove

3-90-08422R33_06/13

venting

venting

A  combustion  blower  is  used  to  extract  the  combustion 

gases from the firebox. This causes a negative pressure in 

the firebox and a positive pressure in the venting system as 

shown in Fig. 7. The longer the vent pipe and more elbows 

used in the system, the greater the flow resistance. Because 

of these facts we recommend using as few elbows as possible 

and 15 feet or less of vent pipe. The maximum horizontal 

run should not exceed 48". If more than 15 feet of pipe is 

needed, the interior diameter should be increased from 3" to 

4" because a larger pipe causes less flow resistance. 

be sure 

to use approved pellet vent pipe wall and ceiling pass-

through fittings to go through combustible walls and 

ceilings. all joints for connector pipe must be fastened 

with a minimum of three screws and a termination cap 

must be installed. Follow pellet vent manufacturer 

instructions for properly securing each pellet vent joint. 

the pellet starting collar must be secured to the unit's 

flue collar.

a chiMneY connector MaY not Pass through 

an attic or rooF sPace, closet or siMilar 

concealed sPace, Floor , or ceiling. reFerence 

local building codes For details.

iMPortant notice

Approved 3" or 4" Pellet Vent Pipe Such As, Type "PL", 

Must Be Used.

+

+

-

Fig. 7

vent Pipe

Pellet venting pipe (known as PL vent) is constructed of two 

layers with air space between the layers. This air space acts 

as an insulator and reduces the outside surface temperature 

to allow a clearance to combustibles of 1 to 3 inches. The 

sections  of  pipe  lock  together  to  form  an  air  tight  seal  in 

most cases. However, in some cases a perfect seal is not 

achieved. For this reason and the fact that the unit operates 

with  a  positive  vent  pressure 

we specify that the joints 

also be sealed with high temp (rtv) silicone. 

Aluminum 

tape can also be used for any joint that is 1ft. or more from 

the outlet of the stove.

note: simpson duravent Pelletvent Pro harman adapter 

Part #3PvP-adhb and Pelletvent Pro harman adapter 

increaser Part #3PvP-X4adhb are highly recommended 

to be installed on the starter collar to insure a proper 

pipe connection to the unit.

 

install vent at clearances sPeciFied bY the 

vent ManuFacturer
do not install a Flue daMPer in the eXhaust 

venting sYsteM oF this unit.
do not connect this unit to a chiMneY Flue 

serving another aPPliance

avoiding smoke and odors
negative Pressure, shut-down, and Power Failure:

T

o reduce the probability of back-drafting or burn-back in 

the pellet burning appliance during power failure or shut-

down conditions, the stove must be able to draft naturally

 

without exhaust blower operation. Negative pressure in the 

house will resist this natural draft if not accounted for in the 

pellet appliance installation.

Heat rises in the house and leaks out at upper levels. This air 

must be replaced with cold air from outdoors, which flows into 

lower levels of the house. Vents and chimneys into basements 

and lower levels of the house can become the conduit for air 

supply, and reverse under these conditions.

outside air:

hearth & home technologies strongly recommends 

attaching outside air in all installations, especially lower 

level and main floor locations.

caution

do not use MaKeshiFt coMProMises when 

installing this aPPliance.  daMage and/or 

injurY MaY result.

= Positive Static Pressure
= Negative Static Pressure

+

-

Содержание P38plus

Страница 1: ...ermine the need for a permit Cette guide d utilisation est disponible en francais Chez votre concessionnaire de Harman HOME HEATING Model s PP38 Freestanding Pellet Stove NOTICE SAVE THESE INSTRUCTION...

Страница 2: ...de pr voir une prise d alr ext rieur L int grit structurale du plancher du plafond et des murs doit tre strictement pr serv e Se reporter aux instructions du fabricant et aux r glementations sp ci que...

Страница 3: ...tre plac sous les parties horizontales du tuyau de raccord la chemin e et s tendre 51mm o 2 po au del de la mesure du tuyau Made in U S A of US and imported parts Fabriqu aux tats Unis d Am rique par...

Страница 4: ...lified service person Periodic cleaning is required throughout the heating season and at the end of each winter for the stove to work efficiently refer to the maintenance section of this manual WARNIN...

Страница 5: ...ions along with all local codes regarding installation of this appliance Do NOT use makeshift compromises when installing this appliance serious consequences may result With any hearth appliance insta...

Страница 6: ...he first reading check for possible restrictions or the need for outside air see page 10 For more information on the draft test procedure refer to Page 19 Mobile Home Installation When installing this...

Страница 7: ...mbly when measured from the horizontal center line of the regulator I The clearance to service regulator vent outlet must be a minimum of 6 feet J The clearance to a non mechanical air supply inlet to...

Страница 8: ...an air tight seal in most cases However in some cases a perfect seal is not achieved For this reason and the fact that the unit operates with a positive vent pressure we specify that the joints also...

Страница 9: ...s 15 feet If a longer run is needed the size must be increased to 3 Inlet cover part number 1 10 08542 should be used to keep birds rodents etc out of the pipe You may choose to use the optional Direc...

Страница 10: ...n wall pass throughs 1 Preferred method This method provides excellent venting for normal operation and allows the stove to be installed closest to the wall Two inches from the wall is safe however fo...

Страница 11: ...provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is questionable you may want to install a liner as in...

Страница 12: ...out rain Be sure to use approved pellet vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to...

Страница 13: ...er installation clearances Minimum flue vent configuration It is required that outside air be installed with this venting configuration to reduce smoke and creosote smell in the room in the event of p...

Страница 14: ...the stove temperature while in Stove Temp Mode using the inner scale marked from 1 to 7 Mode Selector Allows you to choose between Room Temp Mode Stove Temp Mode or OFF Also allows you to vary the dis...

Страница 15: ...he stove will gradually slow down and hold at the minimum burn rate When the house cools down the stove will automatically bring the room temperature to the precise temperature you desire In the Room...

Страница 16: ...er and smoke will escape through window and door gaskets Feed Adjuster Knob For most premium grade pellet fuels the Feed Adjuster Knob should be set at 4 If higher ash fuels are used the setting shoul...

Страница 17: ...e burn pot When the stove is ignited these scrapings will be pushed out by the feeder and burned 6 The ash pan can hold the ashes from approximately 1 ton of premium fuel This means the ashes will onl...

Страница 18: ...onds to pass for the combustion motor to slow before checking the low draft 6 If the low draft is between 25 and 35 record the reading _____ in W C If the reading is lower check for resistance in the...

Страница 19: ...leaned Clean the glass with a soft cloth and mild glass cleaner Do not clean the glass when hot and avoid the use of abrasive cleaners Glass replacement Carefully remove all remaining glass and gasket...

Страница 20: ...sed they should be retained in the closed container until all cinders have been thoroughly cooled Other waste shall not be placed in this container Cleaning It is recommended that the stove is cold an...

Страница 21: ...THE STOVE LIVE PELLETS IF SUCKED INTO THE VACUUM WILL LIGHT THE VACUUM ON FIRE AND MAY ULTIMATELY CAUSE A HOUSE FIRE 9 Use a brush to clean the flue being careful not to damage the ESP probe see Fig 3...

Страница 22: ...e of the burn pot Fig 34 3 Lift off the clean out cover Fig 35 to open the bottom clean out chamber Fig 36 4 Clean ash buildup from inside the chamber while cover is off Use the scraper to tap on the...

Страница 23: ...in the firebox through a port on the rear of the feeder Poor draft will result in an interruption of power to the feeder motor Poor draft can be caused by blockage in the exhaust excessive build up o...

Страница 24: ...tatus blink A 6 blink control board status indication is caused by poor or incomplete combustion The circuit board has the ability to track the combustion through feed settings and ESP temperatures Wh...

Страница 25: ...6 13 Specifications 33 1 8 10 28 5 8 Weight 212 lbs Blower 135 cfm Feed Rate approximate 75lb to 5 5 lbs per hr Hopper Capacity 50 lbs Fuel Wood Pellets Flue Size 3 inch Outside Air Size 2 3 8 I D inc...

Страница 26: ...ary to hold the slate in place on the stove There are 4 decorative slate choices See dealer for samples The Brushed Stainless deer cutout pictured below is another option available This cutout reveals...

Страница 27: ...t temperature knob to desired amount Turn mode selector knob onto Room Temp mode After the fire has lit watch that the fuel does not feed too fast that it pushes the red glowing fuel bed off of the bu...

Страница 28: ...content takes energy to dry and tends to cool the appliance thus robbing heat from your home Damp pellet fuel could turn back into sawdust which does not flow properly through the feed system Size Pel...

Страница 29: ...1 4 2 3 6 5 9 8 7 WHITE WHITE WHITE WHITE BLUE EMPTY EMPTY PLUGGED BROWN 11 BLACK PART NO 3 90 773869 WHITE 11 PIN PLUG 10 RED GREEN BONDED TO STOVE BODY GREEN WIRE IS GROUND 1 8 3 R U B B E R C O R D...

Страница 30: ...of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whiche...

Страница 31: ...y does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw...

Страница 32: ...826 Y 2 Feeder Assembly Pre SN 008080066 Refer to following page 3 Feeder Assembly Post SN 008080066 Refer to following page 4 Flue Tail Pipe 3 00 247237 Y 5 Auger Motor Cover 2 00 773852P Y 6 Auger M...

Страница 33: ...08080066 1 10 7738106A 16 Bolt on Hinge Weldment 2 00 06952B 17 Cast Door Frame 4 00 06800P Cast Door w Glass 1 10 06800A 18 Glass Panel 3 40 950133125 Y Glass Clip w hardware Pkg of 4 Pre 00880001 1...

Страница 34: ...amper Assembly 1 10 06466W 2 2 Air Intake Weldment 1 10 773843 2 3 Feeder Weldment 1 10 677150 Y 2 4 Slide Plate Assembly 1 10 08037 Y 2 5 Pusher Arm Assembly 1 10 773890 Y 2 6 Feed Cover and Gasket 2...

Страница 35: ...6 Y 3 6 UL Feeder Air Intake 1 10 72222 3 7 Gasket Ultra Air Intake Pkg of 10 3 44 677160 10 Y 3 8 Ultra Feeder Weldment 1 10 724132 Y 3 9 UL Feeder Pusher Arm 1 10 677187W Y 3 10 Fines Deflector No...

Страница 36: ...Y Gasket 3 8 Rope White LD Ash Door or Load Door 30 Ft 1 00 00888 Y Gasket Burn Pot Tailpipe Pkg of 5 1 00 07381 Y Gasket Hopper Lid 1 00 00248 Y Hopper Lid W HInge 1 10 08518 Y Labels Caution Danger...

Страница 37: ...37 PP38 Pellet Stove 3 90 08422R33_06 13 Service Maintenance Log Date Of Service Performed By Description Of Service...

Страница 38: ...ts uncompromising attention to detail and helps preserve our planet by using environmentally responsible fuels Signature of Boxer Your premium quality hearth product designed and assembled by the expe...

Отзывы: