Exception F200 Wood Insert

11

Floor Protector

W

a

ll

Floor Protection

In all installations, the area under and around the

insert must be protected from falling ash and live coals.
This protector must be of noncombustible material, and
positioned as shown in the accompanying illustration.

The guidelines for the floor protection are in both

USA and CANADA: 8"(200mm) to each side of the door
opening, and:

In USA:

16" of non-combustible material in front
of the door opening.

In CANADA: 

(1)

 If the floor surface is 0" - 4 1/2"(114

mm) below the insert base, 18"(450mm)
of 1/2"(12.7mm) thick, k=.84 thermal
protection is required in front of the door
opening.

(2)

 If the floor surface is greater than 4

1/2"(114mm) below the base of the
insert, 18"(450mm) of non-combustible
material in front of the door is required.
See appendix A.

Clearances

Clearance is the empty space required between the

insert and the nearest combustible surface or object, such
as walls, ceilings, floors, or furniture.  Clearance distances
may only be reduced by using methods approved by ei-
ther  the  CAN/CSA  B365  standard  (Canada)  or  NFPA
211 (U.S.)  Contact your building authority for informa-
tion if you are interested in reducing clearance distances
other than those presented here.

From the front of the insert, clearance to combus-

tible  materials  such  as  furniture,  curtains,  fuel,  etc.,  is:
48 "( 12 15  

m m)  

in 

th e 

U. S.  

and  

60 "

(1525 mm) in Canada.

The clearance to combustibles from the top of the

unit to the mantel must be 24" (610 mm), if using the op-
tional hood, and at least 36" (900 mm) if the hood is not
used.

Do  Not  Connect  This  Unit  To  A  Chimney  Serving
Another  Appliance

Masonry  Fireplace  Requirements
1. The chimney must be at least 15 feet high but not more

than 33 feet high.

2. This room heater must be connected to a code approved

masonry chimney with a clay tile or stainless steel flue
liner.

3. The entire fireplace and chimney must be clean and in

good condition. Any damage must be repaired before
installing the insert. A stainless steel liner may be in-
stalled if the tile liner of the masonry chimney is dam-
aged.

4. The fireplace  and chimney must meet  local building

codes.

8"

16"USA

18"Canada

22"

559mm

The blower cord can be routed to either side after

removing the ash lip and base cover. Route the cord to
right or left by placing the cord in the proper notch shown
above.

Notch

Warning:  Do not install in sleeping room.

Mantel

2 4" ( 61 0 mm )
with  hood
36" (900  mm)
without  hood

Evaluation notes were added to the output document. To get rid of these notes, please order your copy of ePrint IV now.

Содержание R7R1 Exception Wood Fireplace

Страница 1: ...TY FOLLOW INSTALLATIONDIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATION INSPECTION REQUIREMENTS INYOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL BUILDING...

Страница 2: ...od burning insert Failure to follow instructions may result in property damage bodily injury or even death SAVE THESE INSTRUCTIONS Harman Stove Company 352 MountainHouse Road Halifax PA 17032 INDEX Sp...

Страница 3: ...DINSERT ISNOTPROPERLY INSTALLED AHOUSEFIREMAYRESULT FORYOURSAFETY FOLLOWTHEINSTALLATIONDIRECTIONS CONTACTLOCAL BUILDINGORFIREOFFICIALS ABOUTRESTRICTIONS ANDINSTALLATION INSPECTIONREQUIREMENTSINYOURARE...

Страница 4: ...hearth The Insert Doors Your insert has a large glass paneled door for loading and fireviewing To open the glassdoor turn the handles clockwise and pull out to closethe door return the handles to an...

Страница 5: ...itialevaporation stage where mois ture is released from the wood a stage where volatile gases containing much of the wood s heating capacity are released and burned and a charcoal stage where the rema...

Страница 6: ...se Build a bed of paper and kindling place several 1 2 25 mm 50 mm split pieces of dry wood on top followed by a few 2 3 50 mm 80 mm split pieces Ignite the paper Allow the fire to burn until a good c...

Страница 7: ...Wood ash can be added to your garden or compost When the air setting is low the blower should always be at the minimum setting corresponding to a blower speed of 750 RPM At higher settings above firs...

Страница 8: ...pieces carefully Replace glass only with Harman Insert Com pany replacement glass panels do not use substitutes To replace the glass panel s you will need to remove thedoor To do this open the door l...

Страница 9: ...once every two months during the heating season to seeif any creosote buildup has occurred Checking your chimney and chimney connector more frequently especially while you are getting used to your in...

Страница 10: ...eft and right side wings with 1 4 20 button head bolts Nextinstall top wing use the same size bolts Install andirons with 5 16 bolts and washers Install the corner panels using an 5 32 allen wrench an...

Страница 11: ...authority for informa tion if you are interested in reducing clearance distances other than those presented here From the front of the insert clearance to combus tible materials such as furniture cur...

Страница 12: ...method used a chimney cap is recommended to prevent the fiberglass from being exposed to the rain If the masonry chimney flue cross sectional area is greater than 3 times that of the insert which is 2...

Страница 13: ...eway tothe top 6 The smokeshelf internalbaffles damperand glass ormetaldoors may be removedas necessary 7 Internalparts suchasrefractorylinings firebricks insulation fireboxwalls ordoorframesmaynotbe...

Страница 14: ...LBOW 3 40 00121 21 SSS 5 16 18 X 1 4 3 30 2931180252 22 WOODEN HANDLE 3 40 00122 23 RPH MS 1 4 20 X 2 1 2 3 30 625202501 24 GOLD DOOR W ROPE 1 10 05165 CAST DOOR W ROPE 1 10 08159A 25 GLASS WITH GASKE...

Страница 15: ...cifieda certainmaterialaminimum ofoneinchthickthatis appropriate foruse as a hearth extension with theirfireplace system The k valuefor that materialis 84 You decide to use commonbrick forhearth exten...

Страница 16: ...not limited to fire lightning acts of God power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to remote controls filters fu...

Отзывы: