background image

 

 

INTERNAL THREAD BURNER 

INSTALLATION INSTRUCTIONS 

Thermopile and Pilot Burner Assembly 

 

1.  Attach the pilot generator (thermopile and pilot burner assembly) to the back side of the burner pan using the  
(2) #8 X ½ screws.  
2.  Connect the opposite end of the pilot tubing to the pilot port on the gas valve. 
3.  Attach the leads from the thermopile (pilot generator) to the terminals labeled “TP” on the valve. 

Make sure the pilot tubing and thermopile leads do not contact any parts that get hot or run through any 
areas that may have flames.

 

 

 

 

 

TOP VIEW OF INTERNAL 

THREAD BURNER 

INSTALLATION

 

H-BURNER 

49-6-8 

RSMVNG-C 

69-6-8 

49-6-6Z2 (INCLUDED IN H-BURNER 
ACCESSORY KIT) 

(2) #8x1/2” Screws 

RSTPG-48 

WIRING SCHEMATIC 

SWITCHING DEVICES 

WALL SWITCH, REMOTE 

CONTROL, BARK CHIP SWITCH, 

AND PINECONE SWITCH 

PILOT  

GENERATOR 

RSMVNG-C 

VALVE 

GAS 
CONTROL 
KNOB 

WALL SWITCH – (use installation instructions accompanying any other switching device) 

 

1.  To install a wall switch, mount a standard 3” X 2” electrical box in the wall near the fireplace.  Run thermostat 
wire (18 gauge wire) from the electrical box to the millivolt valve.  At the valve, connect the lead wires to the two 
outside terminals labeled “TH”.   
2.  Mount the wall switch to the electrical box and install the cover plate. 

If using a remote control attach the leads from the receiver to the same terminals as the Wall Switch on 
the RSMVNG-C valve. 

 

RECOMMENDED GAUGE 

OF WIRE 

WALL SWITCH & REMOTE 

CONTROL

 

 

WIRE 

SIZE 

14 Gauge 
16 Gauge 
18 Gauge 
20 Gauge 
22 Gauge

 

MAXIMUM 

LENGTH 

100 ft. 

64 ft. 
40 ft. 
25 ft. 
16 ft.

 

Содержание RME-PO

Страница 1: ...by an experienced service technician trained in gas safety equipment 2 Turn off gas supply before installing valve 3 All piping must meet applicable local codes and ordinances and the national fuel gas code ANSI Z223 1 NFPA NO 54 4 All wiring must meet applicable electrical codes and ordinances 5 Check out the complete system after installing the valve 6 Prior to installation verify conformance wi...

Страница 2: ...rom gas supply to valve and from valve to burner must be supplied by installer when installed outside the firebox Remote Control optional ordered separately A RC A12V J 12 Volt battery operated remote and receiver B RC 110 V requires 110 Volt electricity for the receiver Note Piping from gas supply to valve and from valve to burner must be supplied by installer when installed outside the firebox P...

Страница 3: ...rmostat wire 18 gauge wire from the electrical box to the millivolt valve At the valve connect the lead wires to the two outside terminals labeled TH On the switch connect a lead wire to each terminal Fig 4 2 Mount the wall switch to the electrical box and install cover plate If installing a remote control attach the leads from the receiver to the same terminals as the wall switch on the MV C 69 6...

Страница 4: ...2 Screws RSTPG 48 WIRING SCHEMATIC SWITCHING DEVICES WALL SWITCH REMOTE CONTROL BARK CHIP SWITCH AND PINECONE SWITCH PILOT GENERATOR RSMVNG C VALVE GAS CONTROL KNOB WALL SWITCH use installation instructions accompanying any other switching device 1 To install a wall switch mount a standard 3 X 2 electrical box in the wall near the fireplace Run thermostat wire 18 gauge wire from the electrical box...

Страница 5: ...CEDURE CAUTION Make sure the wall switch and remote are in the off position before lighting the pilot 1 Turn the gas control knob to the off position it will be necessary to depress the knob slightly at the pilot position Allow five minutes for any gas in the combustion chamber to escape LP gas which is heavier than air may require forced ventilation 2 Turn the gas control knob to the pilot positi...

Отзывы: