INSTALLATION SPECIFICATIONS
BTU Ratings and Pressure Requirements
Fireplace Dimensions and Clearances
Refer to the following charts to determine the proper size set for your fireplace.
LOG SET SIZE
GAS TYPE
MAX. HEAT INPUT (BTU/Hr.)
MIN. HEAT INPUT (BTU/Hr.)
GAS INLET PRESSURE
MAX.
MIN.
REGULATOR PRESSURE
18
” SETS
Natural
Propane
32,000
32,000
24,000
23,500
10.5
” WC
13
” WC
5
” WC
11
” WC
4
” WC
10
” WC
24
” SETS
Natural
Propane
40,000
33,000
29,000
23,500
10.5
”WC
13
” WC
5
” WC
11
” WC
4
” WC
10
” WC
When operating the main burner, use the control knob to raise and lower the min. and max. heat output. Turn
the control knob counterclockwise for max. heat and clockwise for min heat.
Input ratings are shown in BTU per hour and are
for elevations up to 2,000 feet. For elevations
above 2,000 feet, input ratings should be reduced
4% for each 1,000 feet above sea level. Refer to
the National Fuel Gas Code.
WARNING:
OPERATION OF THIS
APPLIANCE ON GASES FOR WHICH IT IS
NOT EQUIPPED MAY LEAD TO CARBON
MONOXIDE POISONING.
Depth
Front Width
Log Set
Size
18
”
24”
30
”
Depth
12”
12”
12”
Height
16”
16”
16”
Front
Width
28”
32
”
36
”
Fireplace Dimensions
The chart above indicates the minimum
fireplace dimensions for each log set.
3