HI 1769-WS/HI 1769-2WS WEIGH SCALE MODULE
4-18
WRITEMETRIC
3
Writes the Metric
Parameter. Does NOT save
the value of the metric
parameter to non-volatile
memory.
O:0 = 3
O:1 - unused
O:2 - unused
O:3 - New METRIC value
I:0 = 3
I:1 = COMMAND STATUS
I:2-I:15 See NOCMD,
continuously updating
WRITENONVOLATILE
4
This command is normally
not needed, since the
commands that write
parameters automatically
save values to non-volatile
memory. Exceptions are the
ZEROCMD, TARECMD,
and WRITEMETRIC,
which do not automatically
save.
O:0 = 4
O:1-O:15 (unused)
I:0 = 4
I:1 = 0
I:2-I:15 See NOCMD,
continuously updating
RELOADNONVOLATILE
0X10
Reread the non-volatile
memory
O:0 = 0x10
O:1-O:15 (unused)
I:0 = 0x10
I:1 = 0
I:2-I:15 See NOCMD
continuously updating
CALLOWCMD
0x64
Do the low step of a Hard
Calibration.
Results saved to non-
volatile memory.
O:0 = 0x64
O:1-O:15 (unused)
I:0 = 0x64
I:1 = COMMAND STATUS
I:2-I:15 See NOCMD,
continuously updating
CALHIGHCMD
0x65
Do the high setpoint of a
Hard Calibration.
Results saved to non-
volatile memory.
O:0 = 0x65
O:1-O:15 (unused)
I:0 = 0x65
I:1 = COMMAND STATUS
I:2-I:15 See NOCMD,
continuously updating
C2CALCMD
0x66
Do a C2 Calibration.
Results saved to non-
volatile memory
O:0 = 0x66
O:1-O:15 (unused)
I:0 = 0x66
I:1 = COMMAND STATUS
I:2-I:15 See NOCMD,
continuously updating
Command
Required Output Table Values
Written by User (PLC)
Input Table Response
From Weigh Scale
Содержание HI 1769-WS
Страница 14: ...HI 1769 WS HI 1769 2WS WEIGH SCALE MODULE 1 6...
Страница 27: ...Chapter 3 Installation 3 9 FIG 3 7 RAIL FASTENERS IN THE CLOSED POSITION...
Страница 60: ...HI 1769 WS HI 1769 2WS WEIGH SCALE MODULE 4 26...
Страница 74: ...HI 1769 WS HI 1769 2WS MANUAL 6 8...
Страница 82: ...HI 1769 WS HI 1769 2WS MANUAL Weighing System Tests 1 4 wrist strap grounding device 3 2...