7
INSTALLATION
MOUNTING REQUIREMENTS
The inverter should be mounted in a that fits the following criteria:
• STABLE
- The inverter must be mounted on a surface capable of holding its weight, using all four
mounting points with the appropriate fasteners.
• ORIENTATION
- The inverter should ideally be mounted horizontally either on a wall or flat surface with
the base facing downward. You can mount the inverter vertically on a wall, however this orientation is
less ideal due to the possibility of stress on the circuit board.
Do not mount the inverter base up on
any surface, as this puts higher stress on the circuit board and risks damaging components.
• DRY
- The inverter must be mounted in an area free from water ingress of any kind.
• COOL
- For optimal operating conditions, choose a location that stays within the temperature range of
between
0°C
and
40°C
.
• SAFE
- The inverter must be mounted in an area free from fumes and other hazardous substances.
• VENTILATED
- Ensure a margin of at least
100mm
around the inverter to reduce heat build-up.
• LIMITED DUST
- The inverter must be mounted in an area with little to no dust ingress to reduce the
likelihood of dust being drawn in by the fans when in operation.
• ELECTRICALLY SAFE
- Ensure the inverter is mounted close to the battery to reduce any significant drop
in voltage. With this in mind, the inverter must not be mounted within 300mm of the battery. A fuse must
be fitted between the inverter and battery on the positive cable, with the fuse fitted close to the battery
end to protect the cable.