Administrator setting mode

Engineer setting mode

Item

Description

Setting 

value

Setting range

Default

Unit

Lock

Lock setting

0

Unlock, engineer set up available

0

-

1

Lock, engineer set up unavailable

trSL

Decimal 

display setting

0

Decimal display(0.1 ℃) 

0

-

1

Non decimal display(1 ℃) 

Time

Time unit 

setting

0

Timer: second setting(0 ~ 3600 sec)

1

-

1

Timer: minute setting(0 ~ 3600 min)

PorF

Control setting

0

Proportional control (P.B / M.R value 
set up available)

1

-

1

ON/OFF control

G.COM Communication setting Click the Shift Key to enter the communication setting

Operator setting mode

Item

Description

Setting range

Default

Unit

SV

Setting value (SV)

TSL(min) ~ TSH(max)

25.0 

Pb

Proportional band setting (P.B)

1 ~ 100

20

Mr

Remove offset (M.R)

0 ~ 100

50

%

BIT Information 

ERR.STS

BIT

0x0008

0

-Over

1

Over

2
3
4
5
6
7
8
9

10

11

12
13
14
15

Item

Description

Setting range

Default

Unit

0.typ

Control method setting

Cool / Heat

Cool

-

1.dIF

Deviation setting

A : 1 ~ 50

1.0 

B : 0.2 ~ 50.0

2.dLy

Delay time setting

0 ~ 240

0

Sec

3.rSt

Input compensation

A : -30 ~ +30

0.0 

B : -30.0 ~ +30.0

4.tSH

Higher limit of setting range

A : TSL(min) ~ 150

150.0 

B : TSL(min) ~ 150.0

5.tSL

Lower limit of setting range 

A : -50 ~ TSH(max)

-50.0 

B : -50.0 ~ TSH(max)

6.SAo 

Selection of auxiliary output 

function

0: Alarm setting

0

-

1: Timer setting

Menu of setting alarm

7.AtS

Setting alarm temperature

A : -50 ~ 150

-40.0 

B : -50.0 ~ 150.0

8.AdF

Deviation settings for the 

alarm

A : 1 ~ 50

1.0 

B : 0.2 ~ 50.0

9.AdL  Delay time setting for alarm 0 ~ 240

0

Sec

Menu for timer setting

7.ton

On time setting

0 ~ 3600

3

*1

8.toF

Off time setting

0 ~ 3600

3

9.Moc

Main output control

0: Releasing output control

0

-

0: Releasing output

G.COM

Submanu

Description

Setting range

Default

Unit

PrS

Protocol

ASCII / RTU

RTU

-

bPS

Baud Rate

4800 / 9600 / 19200

9600

bps

PrI

Parity

None / EVEN / ODD

None

bit

StP

Stop Bit

1 or 2

1

bit

dLn

Data Length

7 or 8

8

bit

Adr

Address

1 ~ 31

1

-

rP.t

Response Time

0 ~ 10

0

-

█ Communication setting

A : 1 ℃ display mode (trSL = 1)
B : 0.1 ℃ display mode (trSL = 0)

*1 : when time=0 in administrator setting mode, it is Sec. when time=1 in administrator setting 
    mode, it is Min. 

Description per address

Process (0x0000 ~ )

Addr

Parameter

Description

Setting range

Remark

R/W

0x0001

PV

Current value

-60.0 ~ 160.0

x10 (℃)*2

R

0x0002

SV

Current value

-50.0 ~ 150.0

x10 (℃)*2

R

0x0003

MV OUT

Output quantity

0 ~ 100

(%)

R

0x0004

OUT

OUTPUT1

0 or 1

0: Releasing output

R

1 : Output

0x0005

ALM

ALARM1

0 or 1

0: Releasing output

R

1 : Output

0x0006 ON TIME Remaining ON Time

0 ~ 3600

(Sec or Min)*1

R

0x0007 OFF TIME Remaining OFF Time

0 ~ 3600

(Sec or Min)*1

R

0x0008

ERR.STS

Error status

Error status information Refer to BIT INFORMAITION R

Information (0x0100 ~ )

Addr

Parameter

Description

Setting range

Remark

R/W

0x0100

SYSTEM

System information

0 x 0001

~

0 x FFFF

0x0001 : BR6A

R

0x0101

OPTION

Offset information

0x0000 : NM0P4
0x0001 : NM1P4

R

0x0102 SPECIAL_1 Additional information 1

0x0000 : N/A

R

0x0103 SPECIAL_2 Additional information 2

0x0000 : N/A

R

0x0104

H/W Ver

Hardware version

0x0001 : Ver 0.1

R

0x0105

F/W Ver

Firmware version

0x0001 : Ver 0.1

R

0x0106

F.INIT

Setting initialzation

0 or 1

1 : Flash init

R/W

Control (0x0200 ~ )

Addr

Parameter

Description

Setting range

Remark

R/W

0x0200

LOCK

Lock setting

0 or 1

0: Unlock

R/W

1 : Lock setting

0x0201

TRSL 

Decimal display 

setting

0 or 1

0: Decimal display

R/W

1: Non decimal display

0x0202

TIME

Time unit setting

0 or 1

0: Sec setting in timer

R/W

1: Min setting in timer

0x0203

PORF

Control setting

0 or 1

0: Proportional control

R/W

1: ON/OFF control

0x0204

TYP

Control method 

setting

0 or 1

0 : Cool

R/W

1 : Heat

0x0205

DIF

Deviation setting

0.2 ~ 50.0

x10 (℃)*2

R/W

0x0206

DLY

Delay time setting

0 ~ 240

(Sec)

R/W

0x0207

RST

Input compensation -30.0 ~ +30.0 x10 (℃)*2

R/W

0x0208

TSH

Higher limit of setting range TSL(min) ~ 150.0

x10 (℃)*2

R/W

0x0209

TSL

Lower limit of setting range  -50.0 ~ TSH(max) x10 (℃)*2

R/W

0x0210

SAO

Selection of auxiliary 

output function

0 or 1

0: Alarm setting

R/W

1: Timer setting

0x0211

ATS

Setting alarm temperature -50.0 ~ 150.0

x10 (℃)*2

R/W

0x0212

ADF

Deviation settings for the alarm

0.2 ~ 50.0

x10 (℃)*2

R/W

0x0213

ADL 

Delay time for alarm

0 ~ 240

(Sec)

R/W

0x0214

TON

On time setting

0 ~ 3600

(Sec or Min)*1

R/W

0x0215

TOF

Off time setting

0 ~ 3600

(Sec or Min)*1

R/W

0x0216

MOC

Main output control

0 or 1

0: Releasing output control R/W
1: Output control

SV (0x0300 ~ )

Addr

Parameter

Description

Setting range

Remark

R/W

0x0300

SV

Setting value

-50.0 ~ +150.0

x10 (℃)*2

R/W

0x0301

PB

Proportional band setting

1 ~ 100

x10 (℃)*2

R/W

0x0302

MR

Remove offset

0 ~ 100

(%)

R/W

Communcation (0x0500 ~ )

Addr

Parameter

Description

Setting range

Remark

R/W

0x0510

PRS

Protocol

2 ~ 3

2 : ModBus ASCII

R

3 : ModBus RTU

0x0511

BPS

Baud rate

3 ~ 6

3 : 4800 bps

R

4 : 9600 bps
5 : 19200 bps

0x0512

PRI

Parity

0 ~ 2

0 : None

R

1 : Even
2 : Odd

0x0513

STP

Stop bit

1 ~ 2

1 or 2

R

0x0514

DLN

Data Length

7 ~ 8

7 or 8

R

0x0515

ADR

Address

1 ~ 31

1 ~ 31

R

0x0516

RPT

Response Time

0 ~ 10

0 ~ 10

R

*1 : when time(0x0202) = 0, it is Sec. when time(0x0202) = 1, it is Min. 

 

 

*2 : Communicated data is displayed as actual value x 10. 
     (Ex, when 100.0 ℃ or 100 ℃, 100.0 x 10 = "1000" displays.)    