6
Administrator setting mode
Engineer setting mode
Item
Description
Setting
value
Setting range
Default
Unit
Lock
Lock setting
0
Unlock, engineer set up available
0
-
1
Lock, engineer set up unavailable
trSL
Decimal
display setting
0
Decimal display(0.1 ℃)
0
-
1
Non decimal display(1 ℃)
Time
Time unit
setting
0
Timer: second setting(0 ~ 3600 sec)
1
-
1
Timer: minute setting(0 ~ 3600 min)
PorF
Control setting
0
Proportional control (P.B / M.R value
set up available)
1
-
1
ON/OFF control
G.COM Communication setting Click the Shift Key to enter the communication setting
Operator setting mode
Item
Description
Setting range
Default
Unit
SV
Setting value (SV)
TSL(min) ~ TSH(max)
25.0
℃
Pb
Proportional band setting (P.B)
1 ~ 100
20
℃
Mr
Remove offset (M.R)
0 ~ 100
50
%
BIT Information
ERR.STS
BIT
0x0008
0
-Over
1
Over
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Item
Description
Setting range
Default
Unit
0.typ
Control method setting
Cool / Heat
Cool
-
1.dIF
Deviation setting
A : 1 ~ 50
1.0
℃
B : 0.2 ~ 50.0
2.dLy
Delay time setting
0 ~ 240
0
Sec
3.rSt
Input compensation
A : -30 ~ +30
0.0
℃
B : -30.0 ~ +30.0
4.tSH
Higher limit of setting range
A : TSL(min) ~ 150
150.0
℃
B : TSL(min) ~ 150.0
5.tSL
Lower limit of setting range
A : -50 ~ TSH(max)
-50.0
℃
B : -50.0 ~ TSH(max)
6.SAo
Selection of auxiliary output
function
0: Alarm setting
0
-
1: Timer setting
Menu of setting alarm
7.AtS
Setting alarm temperature
A : -50 ~ 150
-40.0
℃
B : -50.0 ~ 150.0
8.AdF
Deviation settings for the
alarm
A : 1 ~ 50
1.0
℃
B : 0.2 ~ 50.0
9.AdL Delay time setting for alarm 0 ~ 240
0
Sec
Menu for timer setting
7.ton
On time setting
0 ~ 3600
3
*1
8.toF
Off time setting
0 ~ 3600
3
9.Moc
Main output control
0: Releasing output control
0
-
0: Releasing output
G.COM
Submanu
Description
Setting range
Default
Unit
PrS
Protocol
ASCII / RTU
RTU
-
bPS
Baud Rate
4800 / 9600 / 19200
9600
bps
PrI
Parity
None / EVEN / ODD
None
bit
StP
Stop Bit
1 or 2
1
bit
dLn
Data Length
7 or 8
8
bit
Adr
Address
1 ~ 31
1
-
rP.t
Response Time
0 ~ 10
0
-
█ Communication setting
A : 1 ℃ display mode (trSL = 1)
B : 0.1 ℃ display mode (trSL = 0)
*1 : when time=0 in administrator setting mode, it is Sec. when time=1 in administrator setting
mode, it is Min.
Description per address
Process (0x0000 ~ )
Addr
Parameter
Description
Setting range
Remark
R/W
0x0001
PV
Current value
-60.0 ~ 160.0
x10 (℃)*2
R
0x0002
SV
Current value
-50.0 ~ 150.0
x10 (℃)*2
R
0x0003
MV OUT
Output quantity
0 ~ 100
(%)
R
0x0004
OUT
OUTPUT1
0 or 1
0: Releasing output
R
1 : Output
0x0005
ALM
ALARM1
0 or 1
0: Releasing output
R
1 : Output
0x0006 ON TIME Remaining ON Time
0 ~ 3600
(Sec or Min)*1
R
0x0007 OFF TIME Remaining OFF Time
0 ~ 3600
(Sec or Min)*1
R
0x0008
ERR.STS
Error status
Error status information Refer to BIT INFORMAITION R
Information (0x0100 ~ )
Addr
Parameter
Description
Setting range
Remark
R/W
0x0100
SYSTEM
System information
0 x 0001
~
0 x FFFF
0x0001 : BR6A
R
0x0101
OPTION
Offset information
0x0000 : NM0P4
0x0001 : NM1P4
R
0x0102 SPECIAL_1 Additional information 1
0x0000 : N/A
R
0x0103 SPECIAL_2 Additional information 2
0x0000 : N/A
R
0x0104
H/W Ver
Hardware version
0x0001 : Ver 0.1
R
0x0105
F/W Ver
Firmware version
0x0001 : Ver 0.1
R
0x0106
F.INIT
Setting initialzation
0 or 1
1 : Flash init
R/W
Control (0x0200 ~ )
Addr
Parameter
Description
Setting range
Remark
R/W
0x0200
LOCK
Lock setting
0 or 1
0: Unlock
R/W
1 : Lock setting
0x0201
TRSL
Decimal display
setting
0 or 1
0: Decimal display
R/W
1: Non decimal display
0x0202
TIME
Time unit setting
0 or 1
0: Sec setting in timer
R/W
1: Min setting in timer
0x0203
PORF
Control setting
0 or 1
0: Proportional control
R/W
1: ON/OFF control
0x0204
TYP
Control method
setting
0 or 1
0 : Cool
R/W
1 : Heat
0x0205
DIF
Deviation setting
0.2 ~ 50.0
x10 (℃)*2
R/W
0x0206
DLY
Delay time setting
0 ~ 240
(Sec)
R/W
0x0207
RST
Input compensation -30.0 ~ +30.0 x10 (℃)*2
R/W
0x0208
TSH
Higher limit of setting range TSL(min) ~ 150.0
x10 (℃)*2
R/W
0x0209
TSL
Lower limit of setting range -50.0 ~ TSH(max) x10 (℃)*2
R/W
0x0210
SAO
Selection of auxiliary
output function
0 or 1
0: Alarm setting
R/W
1: Timer setting
0x0211
ATS
Setting alarm temperature -50.0 ~ 150.0
x10 (℃)*2
R/W
0x0212
ADF
Deviation settings for the alarm
0.2 ~ 50.0
x10 (℃)*2
R/W
0x0213
ADL
Delay time for alarm
0 ~ 240
(Sec)
R/W
0x0214
TON
On time setting
0 ~ 3600
(Sec or Min)*1
R/W
0x0215
TOF
Off time setting
0 ~ 3600
(Sec or Min)*1
R/W
0x0216
MOC
Main output control
0 or 1
0: Releasing output control R/W
1: Output control
SV (0x0300 ~ )
Addr
Parameter
Description
Setting range
Remark
R/W
0x0300
SV
Setting value
-50.0 ~ +150.0
x10 (℃)*2
R/W
0x0301
PB
Proportional band setting
1 ~ 100
x10 (℃)*2
R/W
0x0302
MR
Remove offset
0 ~ 100
(%)
R/W
Communcation (0x0500 ~ )
Addr
Parameter
Description
Setting range
Remark
R/W
0x0510
PRS
Protocol
2 ~ 3
2 : ModBus ASCII
R
3 : ModBus RTU
0x0511
BPS
Baud rate
3 ~ 6
3 : 4800 bps
R
4 : 9600 bps
5 : 19200 bps
0x0512
PRI
Parity
0 ~ 2
0 : None
R
1 : Even
2 : Odd
0x0513
STP
Stop bit
1 ~ 2
1 or 2
R
0x0514
DLN
Data Length
7 ~ 8
7 or 8
R
0x0515
ADR
Address
1 ~ 31
1 ~ 31
R
0x0516
RPT
Response Time
0 ~ 10
0 ~ 10
R
*1 : when time(0x0202) = 0, it is Sec. when time(0x0202) = 1, it is Min.
*2 : Communicated data is displayed as actual value x 10.
(Ex, when 100.0 ℃ or 100 ℃, 100.0 x 10 = "1000" displays.)