PARAMETER
DESCRIPTION
RANGE
DEFAULT
AL00
Subcooling Temperature out of Range
OFF ON
OFF
AL01
Subcooling Temperature Limit
-76°F – 250°F
-76°F
AL02
Superheat out of Range
OFF ON
OFF
AL03
Superheat Temperature Limit
-76°F – 250°F
125°F
AL04
Superheat /Subcooling Differential Alarm
0°F – 100°F
10°F
AL05
Input #1 out of range (low)
OFF ON
ON
AL06
Input #1 Lower Limit
0 PSIA
0 PSIA
AL07
Input #1 Out of Range (high)
OFF ON
OFF
AL08
Input #1 Upper Limit
0 PSIA
100 PSIA
AL09
Input #1 Differential Alarm
0 PSI – 100 PSI
10 PSI
AL10
Input #2 Out of Range (low)
OFF ON
OFF
AL11
Input #2 Lower Limit
-76°F – 250°F
-76°F
AL12
Input # 2 Out of range(high)
OFF ON
OFF
AL13
Input #2 Upper limit
-76°F – 250°F
250°F
AL14
Input #2 Differential Alarm
0°F – 100°F
10°F
PARAMETER
DESCRIPTION
VALUE
DEFAULT
FS00
R717
R22
R134a
R507
0
1
2
3
0
10
PXVC
AUGUST 2018
PXVC-PT
PARAMETER ACCESS CODE 0015
Refrigerant Selection
PARAMETER ACCESS CODE 0030
TABLE 2.
TABLE 3.
Parameters
Alarms
Alarms can be used for a variety of needs, default configurations allow operation of external equipment, send a signal
back to a programmable logic controller, or any combination thereof. By default alarms are configured to operate on
digital output 2 and have no effect on the control system. By Default the alarm will be enabled until the controller is
reset or the value rises to an increment of 10 (degrees F , PSI, %,etc) above its set-point. this can be modified, contact
Hansen for configuration instructions.