Hansen HLM2 Скачать руководство пользователя страница 8

8

A100b
JAN 2009

SETTING ADJUSTMENTS OF SENSORS

There are several selectable features included in the 
Hansen Gas Sensor.  Refer to pages 6 and 7 for the 
adjustable  features.    Note  the  adjustment  screws  on 
the circuit board for the electrochemical sensor have 
a different layout then the semiconductor sensor.  The 
jumpers may be moved without shutting off the power. 
With the use of a 12-24V AC/DC power source, these 
sensors can be set to the customers specifications 
prior to mounting the gas sensor in the engine room or 
refrigerated area.

Relay and Horn Set Point

The adjustment screw A sets the trip point for the relay 
and the alarm horn. A 0-5V scale measures the full sensing 
range of the Gas Sensor.  The trip point voltage can be 
measured at points ØV and REF1 located on the board.  
Refer to pages 6 and 7 for location of the reference pin 
REF1.  A 100 PPM range gas sensor reading 2.5 volts at 
the reference pin would be equivalent to half the range 
or 50 PPM.  

Default factor y setting is 50% of range.  

Note that the set point of the relay is independent 
of the set points to the Gas Detection Monitor. 

To 

assist in selecting the correct voltage for the desired 
PPM set point, refer to 

Table 1

 below.

VOLTAGE

PPM R ANGE

5

100

250

500

3000

10,000

4

80

200

400

2400

8000

3

60

150

300

1800

6000

2

40

100

200

1200

4000

1

20

50

100

600

2000

.5

10

25

50

300

1000

TABLE 1

Setting Minimum or Maximum Relay Set Point

There is a practical limit for setting the minimum or 
maximum relay set point. There is the tolerance of the 
electronic board and the test meter. It is recommended 
to keep the relay set point between 10% and 95% of 
the range.

Time Delay

A time delay for the operation of the relay and alarm horn 
can be selected using jumpers JP5 and JP6.  

Default 

factor y setting is zero.   

Alarm Horn

Alarm horn is 40dB at 2 feet for Basic Sensor; all other 
models not audible with cover closed.  The alarm horn 
can be disabled using jumper JP2.  

Default factor y 

setting is enabled. 

Adjustment of the Detection Range

Adjustment Screw Z sets the zero (0 PPM) and Adjustment 
Screw S sets the span. (full range = 1000PPM, for 
instance). The output of the sensor circuit can be 
monitored via test points ØV and VS. The full range 
equals 5 volts DC. See 

Calibration Procedures

 for 

fur ther details.

GAS SENSOR OPERATION

On power up the internal relay will energize switching 
from the normally closed position to the normally open 
position.  In addition, the sensor will go through an 

initial warm-up delay for five minutes.  At this time, the 
I and  V outputs are 0.  This is indicated by the green 
LED flashing approximately ever y second.  After five 
minutes, the green LED stays on continuously, indicating 
power to the gas sensor and ready for service.  The gas 
sensor also sends a milliamp output signal to the gas 
detection monitor, PLC, or computer.  This output signal 
is propor tional to the amount of the specific gas being 
monitored in the air around the gas sensor.  If signal 
reads 0.5mA, it is an indication the sensing element has 
failed or disconnected.  Verify proper installation and 
refer to testing and calibration procedures.

Fail Safe Operation

Hansen Gas Sensors feature a one amp SPDT alarm 
relay for fail safe operation.  In the event of a sensor 
element failure, power loss or gas leak detection, the 
internal relay will be de-energized.  This relay can be 
used to trigger an external alarm.

Start Up Test

Once the installation of the gas sensors and monitors 
is complete, the entire gas sensor system should be 
tested.  Normally, two people are required—one person 
using a small amount of the target gas to “bump” each 
sensor in turn, a second person at the monitor location 
to verify the sensor is connected to the correct input, 
responds to the target gas and causes the lights and 
alarms to respond.

Gas Sensor Testing

Field testing of the gas sensor is normally done for three 
reasons.  The first is to determine if the gas sensor is 
responding to the specific gas.  This test is sometimes 
called a “bump” test.  The frequency of the test is usually 
stated in the facilities Process Safety Management (PSM) 
document, but not less than ever y six months.

The second reason for gas sensor testing is to be sure 
the gas sensor is properly calibrated.  Depending on the 
sensing element type, the sensor sensitivity will change 
with time. In par ticular, electrochemical sensors use a 
material that is depleted with time.  The length of time 
varies depending on the amount of exposure to the target 
gas, the ambient temperature and humidity, and changes 
to temperature and humidity range.  Atmospheres that 
are ver y dr y or ver y humid will shor ten the life of a 
sensing element.

The third reason is to be sure the gas sensor output 
triggers the alarms on the monitor, PLC, Gas Alert System, 
horn  or  lights.  Gas  sensors  should  be  recalibrated  at 
least once a year or sooner where the gas sensor is 
frequently exposed to low concentrations of the target 
gas.  Semiconductor and infrared sensors should be 
checked annually.  All sensor types should be recalibrated 
immediately after exposure to a large concentration of 
the target gas.

Note: Insurance companies, local and state agencies 
may require more frequent testing and calibration; 
refer to insurance carrier mandates as well as local 
and state codes.

Calibration of Electrochemical Sensors

Read the calibration instructions completely before 
proceeding.  If in doubt about a procedure, please 
contact Hansen Technologies for fur ther assistance.

Содержание HLM2

Страница 1: ...of gas present in the surrounding environment The analog outputs 4 20mA or 0 10V DC can interface with nearly any existing monitor computer or PLC controller The sensing elements except Basic and Ext...

Страница 2: ...is NEMA4X IP65 conduit connection must be vaporproof Note Auxilliary power required when used with Hansen monitors HLM2 and HLM6 and Gas Alert System Vent Line Gas Sensor For operating temperatures do...

Страница 3: ...present power up the unit as soon as possible as long term exposure can shorten the life of the gas sensing element Select the unit for harsh environments where a condensing atmosphere may be present...

Страница 4: ...advantageous to have both local and remote displays and alarms A display alarm control inside or just outside of a room can be monitored and the same display alarm or a Hansen monitor in the control...

Страница 5: ...age signal wires be in a common conduit tray or wiring panel with power wiring over 48 volts Do not run wires near variable frequency drive VFD equipment When using the gas sensors connected directly...

Страница 6: ...NAL MULTI WIRE SHIELDED CABLE GROUND SHIELD AT OTHER END Voltage Selector D 24V DC A 24V AC D A Fail Safe Relay Relay engerized to normally open position when power applied POWER NO NC COM V V 0 V 0 V...

Страница 7: ...MULTI WIRE SHIELDED CABLE GROUND SHIELD AT OTHER END Voltage Selector D 24V DC A 24V AC D A Fail Safe Relay Relay engerized to normally open position when power applied NO NC COM V V 0 V 0 V I Relay...

Страница 8: ...s the green LED stays on continuously indicating power to the gas sensor and ready for service The gas sensor also sends a milliamp output signal to the gas detection monitor PLC or computer This outp...

Страница 9: ...on and observe the voltage The sensor voltage will slowly climb toward 5VDC When the voltage does not change by more than 0 010 volts per 15 seconds the sensor output voltage is considered to be stabl...

Страница 10: ...for 24 hours Recalibrate and install the cover Note Infrared sensing element CO2 is not replaceable Standard Harsh and Explosion Proof Sensors Standard Harsh and Explosion Proof Sensing Elements are e...

Страница 11: ...fault output 10 amp 230V AC HLM6 Model only Power Required 120V AC 230V AC available Power Consumption 300mA 120V AC 50 60 Hz HLM6 150mA 230V AC 50 60 Hz HLM6 100mA 120V AC 50 60 Hz HLM2 50 mA 230V A...

Страница 12: ...larm relay using the Low Level Alarm Pot which is located closest to the calibration pins This setting applies to the six channels For the high level alarm relay setting measure the voltage across Cal...

Страница 13: ...IN GREEN RED REM OTE SENSOR V V V I NO COM NC 0 0 HORN LINE GROUND NEUTRAL 12V BUZZ 0 V CN11 FAIL SAFE OFF ON FUSE CAL L N G Y R Y R Y R Y R Y R R Y CN1 1 2 3 4 CN2 1 2 3 4 CN3 1 2 3 4 CN4 1 2 3 4 CN...

Страница 14: ...used sensor channel 4 Install 3 3K ohm resistor across terminal 1 and 2 TROUBLESHOOTING GAS SENSORS Symptom Sensor green light is off Cause Possible wiring fault between controller and 1 sensor Check...

Страница 15: ...160 2 56 65 62 16 2 07 53 4 13 105 173 DIA 4 4 MOUNTING HOLE 3 PLACES 29 7 2 93 78 6 37 162 358 DIA 9 1 MOUNTING HOLE 3 10 79 7 58 191 49 DIA 5X 12 AUDIBLE ALARM KEY SWITCH HIGH LEVEL ALARM RESET 173...

Страница 16: ...be removed to access the two mounting holes for screw mounting Attach to the wall with the appropriate mounting screws Replace the cover when complete WIRING GAS ALERT SYSTEM The GAS Alert System can...

Страница 17: ...AL L N G Y R Y R Y R Y R Y R R Y CN1 1 2 3 4 CN2 1 2 3 4 CN3 1 2 3 4 CN4 1 2 3 4 CN5 1 2 3 4 CN6 1 2 3 4 FUSE FUSE FUSE FUSE FUSE FUSE N 0 N C N 0 N C COM N 0 N C COM COM CN10 CN9 CN12 POWER ON LIGHT...

Страница 18: ...L N G Y R Y R Y R Y R Y R R Y CN1 1 2 3 4 CN2 1 2 3 4 CN3 1 2 3 4 CN4 1 2 3 4 CN5 1 2 3 4 CN6 1 2 3 4 FUSE FUSE FUSE FUSE FUSE FUSE N 0 N C N 0 N C COM N 0 N C COM COM CN10 CN9 CN12 POWER ON LIGHT MO...

Страница 19: ...0 HSC4H F3K R410 HSC4E F3K R410 Semiconductor 0 3 000 Note Gas Sensors available for additional refrigerants consult factory CO2 Sensor Type Range PPM Basic to 32 F 0 C Harsh to 40 F 40 C Extreme to 6...

Страница 20: ...sen products except electronics are guaranteed against defective materials or workmanship for one year F O B factory Electronics are guaranteed against defective materials or workmanship for 90 days F...

Отзывы: