Hansen HLM2 Скачать руководство пользователя страница 18

18

A100b
JAN 2009

PLC 4 PT. ANALOG IN MODULE (CURRENT)

FIG. J

TYPICAL WIRING DIAGRAM HLM6 TO EXTREME GAS SENSOR

FIG. K

GREEN

RED

V +V

V

I

NO COM NC

0

0

V

Power Supply

24V AC/DC

EARTH GRD

Multi-Wire

Cable Shield

*REMOTE SENSOR

+

-

INPUT #1

INPUT #2

INPUT #3

INPUT #4

ANALOG GND

REMOTE SENSOR

REMOTE SENSOR

REMOTE SENSOR

* Wiring is the same for AC or DC Power Supply.

Voltage selector must match external power supply.

A
D

POWER
IN

GREEN

RED

EXTREME GAS SENSOR

V +V

V

I

NO COM NC

0

0

HORN

- LINE
- GROUND

- NEUTRAL

+12V

BUZZ

0 V

CN11

FAIL

SAFE

OFF   ON

FUSE

CAL

L

N

G

Y

R

Y

R

Y

R

Y

R

Y

R

R

Y

CN1

1

2

3

4

CN2

1

2

3

4

CN3

1

2

3

4

CN4

1

2

3

4

CN5

1

2

3

4

CN6

1

2

3

4

FUSE

FUSE

FUSE

FUSE

FUSE

FUSE

N/0

N/C

N/0

N/C

COM

N/0

N/C

COM

COM

CN10

CN9

CN12

POWER ON LIGHT

MODEL HLM6

V

*

Remove Resistor when connecting a sensor

*

*

*

*

1 2 3 4

LOW  LEVEL ALARM POT

CALIBRATION PINS

HIGH LEVEL ALARM POT

LOW LEVEL
ALARM

HIGH LEVEL
ALARM 

FAULT OUT PUT

FUSE

GMC-200mA 250V

120V:  GMC-315mA 250V
230V:  GMC-160mA 250V

120V/230V:  GMC-315mA 250V

Valve:  3.3K ohm

1

Power Supply

24V AC/DC

EARTH GRD

Multi-Wire

Cable Shield

18 AWG.

GREEN

RED

V +V

V

I

NO COM NC

0

0

V

Multi-Wire

Cable Shield

* Wiring is the same for AC or DC power supply.

Voltage selector must match external power supply.

A
D

A
D

External Power Supply

Voltage Selector

Содержание HLM2

Страница 1: ...of gas present in the surrounding environment The analog outputs 4 20mA or 0 10V DC can interface with nearly any existing monitor computer or PLC controller The sensing elements except Basic and Ext...

Страница 2: ...is NEMA4X IP65 conduit connection must be vaporproof Note Auxilliary power required when used with Hansen monitors HLM2 and HLM6 and Gas Alert System Vent Line Gas Sensor For operating temperatures do...

Страница 3: ...present power up the unit as soon as possible as long term exposure can shorten the life of the gas sensing element Select the unit for harsh environments where a condensing atmosphere may be present...

Страница 4: ...advantageous to have both local and remote displays and alarms A display alarm control inside or just outside of a room can be monitored and the same display alarm or a Hansen monitor in the control...

Страница 5: ...age signal wires be in a common conduit tray or wiring panel with power wiring over 48 volts Do not run wires near variable frequency drive VFD equipment When using the gas sensors connected directly...

Страница 6: ...NAL MULTI WIRE SHIELDED CABLE GROUND SHIELD AT OTHER END Voltage Selector D 24V DC A 24V AC D A Fail Safe Relay Relay engerized to normally open position when power applied POWER NO NC COM V V 0 V 0 V...

Страница 7: ...MULTI WIRE SHIELDED CABLE GROUND SHIELD AT OTHER END Voltage Selector D 24V DC A 24V AC D A Fail Safe Relay Relay engerized to normally open position when power applied NO NC COM V V 0 V 0 V I Relay...

Страница 8: ...s the green LED stays on continuously indicating power to the gas sensor and ready for service The gas sensor also sends a milliamp output signal to the gas detection monitor PLC or computer This outp...

Страница 9: ...on and observe the voltage The sensor voltage will slowly climb toward 5VDC When the voltage does not change by more than 0 010 volts per 15 seconds the sensor output voltage is considered to be stabl...

Страница 10: ...for 24 hours Recalibrate and install the cover Note Infrared sensing element CO2 is not replaceable Standard Harsh and Explosion Proof Sensors Standard Harsh and Explosion Proof Sensing Elements are e...

Страница 11: ...fault output 10 amp 230V AC HLM6 Model only Power Required 120V AC 230V AC available Power Consumption 300mA 120V AC 50 60 Hz HLM6 150mA 230V AC 50 60 Hz HLM6 100mA 120V AC 50 60 Hz HLM2 50 mA 230V A...

Страница 12: ...larm relay using the Low Level Alarm Pot which is located closest to the calibration pins This setting applies to the six channels For the high level alarm relay setting measure the voltage across Cal...

Страница 13: ...IN GREEN RED REM OTE SENSOR V V V I NO COM NC 0 0 HORN LINE GROUND NEUTRAL 12V BUZZ 0 V CN11 FAIL SAFE OFF ON FUSE CAL L N G Y R Y R Y R Y R Y R R Y CN1 1 2 3 4 CN2 1 2 3 4 CN3 1 2 3 4 CN4 1 2 3 4 CN...

Страница 14: ...used sensor channel 4 Install 3 3K ohm resistor across terminal 1 and 2 TROUBLESHOOTING GAS SENSORS Symptom Sensor green light is off Cause Possible wiring fault between controller and 1 sensor Check...

Страница 15: ...160 2 56 65 62 16 2 07 53 4 13 105 173 DIA 4 4 MOUNTING HOLE 3 PLACES 29 7 2 93 78 6 37 162 358 DIA 9 1 MOUNTING HOLE 3 10 79 7 58 191 49 DIA 5X 12 AUDIBLE ALARM KEY SWITCH HIGH LEVEL ALARM RESET 173...

Страница 16: ...be removed to access the two mounting holes for screw mounting Attach to the wall with the appropriate mounting screws Replace the cover when complete WIRING GAS ALERT SYSTEM The GAS Alert System can...

Страница 17: ...AL L N G Y R Y R Y R Y R Y R R Y CN1 1 2 3 4 CN2 1 2 3 4 CN3 1 2 3 4 CN4 1 2 3 4 CN5 1 2 3 4 CN6 1 2 3 4 FUSE FUSE FUSE FUSE FUSE FUSE N 0 N C N 0 N C COM N 0 N C COM COM CN10 CN9 CN12 POWER ON LIGHT...

Страница 18: ...L N G Y R Y R Y R Y R Y R R Y CN1 1 2 3 4 CN2 1 2 3 4 CN3 1 2 3 4 CN4 1 2 3 4 CN5 1 2 3 4 CN6 1 2 3 4 FUSE FUSE FUSE FUSE FUSE FUSE N 0 N C N 0 N C COM N 0 N C COM COM CN10 CN9 CN12 POWER ON LIGHT MO...

Страница 19: ...0 HSC4H F3K R410 HSC4E F3K R410 Semiconductor 0 3 000 Note Gas Sensors available for additional refrigerants consult factory CO2 Sensor Type Range PPM Basic to 32 F 0 C Harsh to 40 F 40 C Extreme to 6...

Страница 20: ...sen products except electronics are guaranteed against defective materials or workmanship for one year F O B factory Electronics are guaranteed against defective materials or workmanship for 90 days F...

Отзывы: