Hansen FM-71 Скачать руководство пользователя страница 3

3

F100d 

JAN 2011

EQUALIZE:    0  to  5  minutes.

  The EQUALIZE step 

permits gradual reduction of the pressure inside the 
evaporator after defrosting to near suction pressure.  

This is accomplished by either a bleed-down solenoid 

valve  by-passing  the  suction  shut-off  valve  or  by 
merely allowing the surrounding ambient temperature 
to cool the evaporator.  This step lowers the internal 
pressure  and  the  likelihood  of  evaporator,  piping 
and  component  shock  when  the  suction  stop  valve 
is  opened.    Equalization  also  reduces  the  impact 
of  pressure  changes  upon  the  suction  accumulator.  
Radical pressure changes cause unnecessary loading 
and  unloading  of  compressors  and  also  encourage 
pumps to cavitate.  Observing the evaporator pressure 
gauge during this step may help determine the most 
appropriate time setting.

FAN  DELAY:    0  to  5  minutes. 

 This step resumes 

normal  refrigeration  but  delays  the  evaporator  fan 
operation  for  the  set  time.    This  delay  enables  the 
remaining  water  droplets  from  the  melted  frost  to 
freeze to the surface of the evaporator, thus preventing 
them from blowing into the refrigerated space when 
air flow resumes.

PUMPOUT:  0 to 15 minutes.

  The PUMPOUT step 

helps  in  the  removal  of  liquid  refrigerant  from  the 

evaporator  before  defrosting  begins.    Less  liquid 
means more internal evaporator surface is exposed to 
entering hot gas.  It also reduces the amount of liquid 
accommodated by the system during defrost.

HOT  GAS:    0  to  45  minutes.

    The  HOT  GAS  step 

begins the actual melting of the frost accumulation.  

The  amount  of  time  required  to  remove  the  frost  is 

dependent on many factors including the following:  
design of evaporator, quantity of frost accumulation, 
quality and quantity of hot gas supply, size of valves, 
etc.    A  fairly  accurate  way  of  setting  this  time  is 

by  observing  several  defrosts  of  the  evaporator 
to  estimate  the  amount  of  time  required,  possibly 
by  using  the  Manual  Stepping  feature  of  the  Frost 
Master®.    Be  sure  that  the  HOT  GAS  step  is  long 

enough to entirely remove every portion of the frost.  
Partial  removal  of  frost  is  not  acceptable  because 

it  will  tend  to  increase  in  mass  after  each  defrost, 

eventually causing a large frost/ice problem.  To help 
assure complete defrosting where the HOT GAS step 
duration  is  desired  to  be  kept  to  a  minimum,  a  coil 
clean temperature terminate device is an option.  (See 

TERMINATE, page 4 and 6).

FROST MASTER

®

 DEFROST CONTROLLER

NEMA 4 ENCLOSURE

LIGHTS FOR DEFROST 
STEPS

DEFROST STEPS TIME 

ADJUSTMENTS

CLAMP TYPE TERMINALS

GROUNDING SCREW

TIME-OF-DAY AT ARROWHEAD

QUARTZ TIME CLOCK
(24 HOUR OR 7-DAY)

TIME CLOCK TABS

“OPTIONAL INITIATE” 

SPADE TERMINALS

“OPTIONAL TERMINATE” 

SPADE TERMINALS

DEFROST MODE LIGHT

MANUAL INITIATE & 
STEPPING BUTTON

Содержание FM-71

Страница 1: ... specifically for defrosting industrial and large commercial refrigeration systems the Frost Master sequences solenoid valves and relays to provide quick and efficient defrosting of evaporator coils Because of its SPDT relays and time adjustable defrost steps this controller is suitable for almost every defrost application including top and bottom feed unit coolers blast freezer evaporators and ic...

Страница 2: ...of defrosts per day or week by not defrosting unless necessary the time clock can be used to prevent defrost from happening when it would not be advantageous Temperature terminate contacts are provided to optionally connect a thermostat or other device for minimized defrost time The Remote Initiate models clockless require only an external momentary dry contact closure of the initiate terminals fr...

Страница 3: ... begins Less liquid means more internal evaporator surface is exposed to entering hot gas It also reduces the amount of liquid accommodated by the system during defrost HOT GAS 0 to 45 minutes The HOT GAS step begins the actual melting of the frost accumulation The amount of time required to remove the frost is dependent on many factors including the following design of evaporator quantity of fros...

Страница 4: ...and a time clock tab must trip before a defrost will begin In other words initiate for a clock equipped defrost controller will only occur if called for by an initiation device during a clock scheduled defrost period On the other hand a clockless Remote Initiate Model FM 01 FM 02 FMP 01 could initiate defrost any time the initiate device closed the terminals The Frost Master is supplied with a fac...

Страница 5: ...vaporator shown on page 9 Other wiring schemes are possible to meet system requirements This wiring diagram is for illustration purposes only and does not show all controls and safety devices Final control wiring is the responsibility of the system designer See above table for relay operation Relays shown with no power to Frost Master See above for relay operation relay energized POWER INPUT RELAY...

Страница 6: ...sture Field sensor wire size should be at least 20 AWG 0 5 mm2 and limited to a distance of 500 ft 152 m Avoid running wires through evaporator air stream or with high voltage wiring Connect field sensor wires to terminate temperature sensor quick disconnect plug inside defrost controller enclosure terminate temperature sensor INTRODUCTION This deluxe model Frost Master Plus includes an additional...

Страница 7: ...ator shown on page 9 Other wiring schemes are possible to meet system requirements This wiring diagram is for illustration purposes only and does not show all controls and safety devices Final control wiring is the responsibility of the system designer See above table for relay operation Relays shown with no power to Frost Master Plus See above for relay operation relay energized POWER INPUT RELAY...

Страница 8: ...al Typically the defrost relief regulator is set at about 70 psig 5 bar for ammonia When a defrost condensate liquid drainer is used an outlet pressure regulator in the hot gas supply line should be used to limit the internal evaporator pressure Check valves are installed after the liquid solenoid valve to prevent higher pressure gas from entering the liquid supply line during defrost Also check v...

Страница 9: ...NOID VALVE WITH ELECTRIC SHUT OFF STOP VALVE OR REGULATOR OR GAS POWERED SUCTION SUCTION SOLENOID VALVE FOR EQUALIZING WITH WIDE OPENING FEATURE DEFROST RELIEF REGULATOR OVERFEED LIQUID LINE SUCTION LINE OVERFEED BOTTOM FEED EVAPORATOR TOP FEED EVAPORATOR EVAPORATOR WITH GAS POWERED SUCTION STOP VALVE EVAPORATOR WITH DEFROST CONDENSATE LIQUID DRAINER DEFROST RELIEF HOT GAS SOLENOID VALVE SOFT GAS ...

Страница 10: ...frost melting can begin Typical rating at 86ºF to 10ºF is 7 5 lbs min 0 063 kg sec for ammonia and 24 5 lbs min 0 117 kg sec for R22 For greater capacities contact factory Inlet outlet connections combination FPT 1 Weld HD101 dEFROST CONDENSATE LIQUID DRAINER Mechanical non electrical float regulator drains liquid condensate from evaporator during defrost It has built in gas vent plus expansion va...

Страница 11: ...se requires no pressure drop to operate Requires a single pilot solenoid valve to control Typically used to close off evaporators from system suction especially below 20F 30C HS9B GAS POWERED SOLENOID VALVE This valve uses a remote gas or liquid pressure source to close requires no pressure drop to operate Dual pilot solenoid valve assembly controls opening and closing of valve without internal bl...

Страница 12: ...me of day and defrost start times WARRANTY Hansen defrost controllers are guaranteed against defective materials or workmanship for 90 days F O B our plant No consequential damages or field labor is included REMOTE INITIATE MODELS Remote Initiate Models FM 01 FM 02 and FMP 01 are supplied less any time clock and horizontal jumper wire The defrost begins when the initiate spade terminals are moment...

Отзывы: