Eco Gateway for CANopen
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
28
IOs
Red
Module bus not ready-to oper
-
ate
Check the correct mounting of the single
BL20-modules
Red
flashing, 1 Hz
Non adaptable changes in the
configuration of the module
bus nodes
Compare the configured list of modules in
your BL20-station to the current configura
-
tion.
Check the physical station for defective or
incorrectly plugged electronic modules.
Red flashing,
4 Hz
No module bus communication Check the station configuration and the
voltage supply at the gateway and at the
supply modules.
Red/green flash
-
ing, 1 Hz
Adaptable changes in the con
-
figuration of the module bus
nodes
Check the physical station for pulled or new
but not planned modules.
ERR
Off
No errors in communication
between the BL20-CANopen
gateway and other CANopen
nodes
–
Red
Faulty or interrupted communi
-
cation between BL20-CANopen
gateway and other CANopen
nodes.
–
CAN BusOff
–
Heartbeat error
–
Guarding error
–
Transmit timeout
–
Check that the fieldbus ends with a termi
-
nation resistor, if the BL20-CANopen gate
-
way is the last node in the bus topology.
–
Check the CANopen cable for possible
damage, and for correct connections
–
Check that the correct bit rate has been
set.
–
Check that the NMT-master is still func
-
tioning properly.
BUS
Green
The modules configured corre
-
spond to the modules in the sta
-
tion, communication running.
-
Red
NMT-slave state of the BL20-
CANopen gateway is "Stopped”
–
„Reset-Node“-command from NMTmaster
for the respective node necessary.
–
If this command is not successful, execute
a voltage reset.
Orange
NMT-slave state of the BL20-
CANopen gateway is "Preopera
-
tional”
„Start-Node“-command from NMT-master
necessary.
ERR + BUS
Red flashing,
alternately, 4 Hz
Invalid Node-ID set
Set the correct Node-ID with the DIP
switches
(1 to 63)
Red flickering,
alternately,
10 Hz
Autobaud function active
LED
Status
Meaning
Remedy
Содержание BL20-E-GW-CO
Страница 1: ...Your Global Automation Partner BL20 E GW CO ECO Gateway for CANopen Instructions for Use ...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com ...
Страница 6: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 4 ...
Страница 10: ...Notes on the Product Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 8 ...
Страница 12: ...For Your Safety Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 10 ...
Страница 53: ...Over 30 subsidiaries and over 60 representations worldwide www turck com D301108 2020 09 D301108 ...