Holding Registers (4xxxx Addresses)
38
Address Register Function
Size
Min.
Value
Max.
Value
Default
Value Details
40121
CH1 Setpoint 2 deviation
float
Parameter
dependent
Parameter
dependent
Parameter
dependent
Low part of float
(bytes
1‑0
)
40122
High part of float
(bytes
3‑2
)
40123
CH1 Setpoint 2 hysteresis
float
Parameter
dependent
Parameter
dependent
Parameter
dependent
Low part of float
(bytes
1‑0
)
40124
High part of float
(bytes
3‑2
)
40125
CH1 Setpoint 2 reset time
uint16_t
60
60000
60000
[seconds]
40126
CH1 Setpoint 2 rate time
uint16_t
0
60000
0
[seconds]
40127
CH2 Setpoint 1 parameter No.
uint8_t
0
1
0
0
= main parameter
1
= temperature
40128
CH2 Setpoint 1 status
uint8_t
0
1
9
0
= disabled
1
= active
40129
CH2 Setpoint 1 control mode
uint8_t
0
2
0
0
= On/Off control
1
= Prop. control
2
= PID control
40130
CH2 Setpoint 1 over time
uint16_t
10
120
30
[minutes]
0
= overtime alarm
disabled
40131
CH2 Setpoint 1 minim OnTime
uint16_t
1
10
3
[seconds]
40132
CH2 Setpoint 1 Value
float
Low limit
parameter
High Limit
parameter
Param. default
control
Low part of float
(bytes
1‑0
)
40133
High part of float
(bytes
3‑2
)
40134
CH2 Setpoint 1 control action
uint8_t
0
1
0
0
= low direction
1
= high direction
40135
CH2 Setpoint 1 control period
uint16_t
10
1800
60
[seconds]
40136
CH2 Setpoint 1 deviation
float
Parameter
dependent
Parameter
dependent
Parameter
dependent
Low part of float
(bytes
1‑0
)
40137
High part of float
(bytes
3‑2
)
40138
CH2 Setpoint 1 hysteresis
float
Parameter
dependent
Parameter
dependent
Parameter
dependent
Low part of float
(bytes
1‑0
)
40139
High part of float
(bytes
3‑2
)
40140
CH2 Setpoint 1 reset time
uint16_t
60
60000
60000
[seconds]
40141
CH2 Setpoint 1 rate time
uint16_t
0
60000
0
[seconds]
40142
CH2 Setpoint 2 parameter number
uint8_t
0
1
0
0
= main parameter
1
= temperature
40143
CH2 Setpoint 2 status
uint8_t
0
1
9
0
= disabled
1
= active
40144
CH2 Setpoint 2 control mode
uint8_t
0
2
0
0
= On/Off control
1
= Prop. control
2
= PID control
40145
CH2 Setpoint 2 over time
uint16_t
10
120
30
[minutes]
0
= overtime alarm
disabled