10
Modbus Registers
Holding Register
Reference
Address
Name
Units
Description
40001 0x0000
DRYER_STATUS
Status ID
Status ID for the dryer
40002 0x0001
ALARM_STATUS
Flag Bits
Alarm flag bits
40003 0x0002
WARNING_STATUS
Flag Bits
Warning flag bits
40004 0x0003
RESERVED
N/A
Reserved
40005 0x0004
SERVICE_TIMER
Hours
Timer to service
40006 0x0005
TOTAL_TIMER
Hours
Total operating hours
40007 0x0006
EVAPORATOR_INLET_TEMP
1/10 Degree Celsius
Evaporator inlet temperature
40008 0x0007
DISCHARGE_TEMP
1/10 Degree Celsius
Discharge temperature
40009 0x0008
DRYER_LOAD
%
Dryer load
40010 0x0009
SAVINGS
Dollars / Euros
Energy savings
40011 0x000A
EVAPORATOR_OUTLET_TEMP
1/10 Degree Celsius
Evaporator outlet temperature
40012 0x000B
40013 0x000C
40014 0x000D
40015 0x000E
40016 0x000F
40017 0x0010
DRYER_MODEL
Model_ID
Dryer model
40018 0x0011
DRYER_MODE
Mode_ID
Dryer mode
40019 0x0012
SERVICE_INTERVAL
Hours
Service interval
40020 0x0013
AUTO_RESTART
Boolean
Auto-restart (0=Disabled, 1=Enabled)
40021 0x0014
UI_LANGUAGE
Language_ID
User interface language
40022 0x0015
RESERVED
N/A
Reserved
40023 0x0016
RESERVED
N/A
Reserved
40024 0x0017
ENERGY_COST
Integer
Energy cost (Cost / kWh)
40025 0x0018
AUDIBLE_ALARM
Boolean
Audible Alarm (0=Disabled, 1=Enabled)
40026 0x0019
MODBUS_ADDRESS
Integer
Modbus Address
40027 0x001A
FULL_POWER
Watts
Full load power
40028 0x001B
40029 0x001C
40030 0x001D
40031 0x001E
40032 0x001F
40033 0x0020
ALARM_MSG_1
Integer
Alarm message #1 phrase id
40034 0x0021
ALARM_MSG_2
Integer
Alarm message #2 phrase id
40035 0x0022
40036 0x0023
40037 0x0024
40038 0x0025
40039 0x0026
40040 0x0027
40041 0x0028
INPUT_STATUS
Flag Bits
Digital Input Status
40042 0x0029
OUTPUT_STATUS
Flag Bits
Digital Output Status
40043 0x002A
ANALOG[0]
1/10 Degree Celsius
Analog Input [0]
40044 0x002B
ANALOG[1]
1/10 Degree Celsius
Analog Input [1]
40045 0x002C
ANALOG[2]
1/10 Degree Celsius
Analog Input [2]
40046 0x002D
PV
1/10 Degree Celsius
Process value
40047 0x002E
P
Integer
P Term
40048 0x002F
I
Integer
I Term
40049 0x0030
D
Integer
D Term
40050 0x0031
FIXED_LOAD
Seconds
Fixed cycle load period
40051 0x0032
FIXED_UNLOAD
Seconds
Fixed cycle unload period
40052 0x0033
FIXED_TIME
Seconds
Fixed mode timeout period
40053 0x0034
DELTA_PID_CALC
1/10 Degree Celsius
PID calculation set point
40054 0x0035
DELTA_PID_CTRL
1/10 Degree Celsius
PID control set point