RC2-D Technical Manual
b.
The grounding voltage of terminal box shall not be greater than 50V; in humid area, it should be 25V.
c.
The grounding resistance shall not be greater than 50
Ω
.
d.
Air cut board (ACB) is usually connected with leakage protector. Please refer to relevant operation
settings.
e.
Once the leakage protection is started, please check if the insulation is normal and if the circuit and
setting are correct. Please turn on the power after confirmation. If you have any questions, please
contact the equipment supplier.
Specification for terminal plate nut
Model
Specification
Torque(N.m)
RC2 -100~180D-S(P)
M8
20
RC2 -200~930D-S(P)
M12
35
Note:
when the surface temperature of compressor is lower than the air dew point
temperature, it is recommended to wrap the exposed part of the wiring with electrical
insulation tape to improve reliability
Содержание RC2-D
Страница 27: ...RC2 D Technical Manual 2 RC2 200 470 D S P terminal box 3 RC2 510 930 D S P terminal box ...
Страница 44: ...RC2 D Technical Manual 46 10 Appearance Drawing 10 1 RC2 100 930D S Drawing RC2 100 140D S Drawing ...
Страница 45: ...RC2 D Technical Manual 47 RC2 180D S Drawing ...
Страница 46: ...RC2 D Technical Manual 48 RC2 200 620D S Horizontal suction port Drawing ...
Страница 48: ...RC2 D Technical Manual 50 RC2 620 930D S Vertical suction port Drawing ...
Страница 49: ...RC2 D Technical Manual 51 10 2 RC2 100 930D P Drawing RC2 100 140D P Drawing ...
Страница 50: ...RC2 D Technical Manual 52 RC2 180D P Drawing ...
Страница 51: ...RC2 D Technical Manual 53 RC2 200 620D P Drawing ...
Страница 53: ...RC2 D Technical Manual 55 RC2 620 930D P Drawing ...