71
for more detail.
5.4 Selection of magnetic contactor
Please refer to AC3 specification, compressor selection program and design conditions of system to choose suitable
contactor.
5.5 Grounding
There
’s a grounding terminal inside cable box. Please accurately connect it to grounding of control panel for the
system.
2
8
(Option)
A:PTC
B:Pt100Ω / Pt1000Ω
PW2:7,8,9
PW1:1,2,3
3
9
Earth Bolt
1
7
B
A
Suggestion:
a. The regular setting of electric leak protection should be greater than 50mA; for a humid location, 25mA is
better.
b. Grounding voltage of casing should be no greater than 50V; for a humid location, the limit is 25V.
c. Grounding resistance should be no greater than 500 Ohm.
d. Air cut board (ACB) is regularly equipped with electric leak protection. Please refer to related settings for its
normal action.
e. If electric leak protection is active, please check if insulation of equipments is normal and if its wiring and
setting are correct. Please make sure nothing is wrong before turning on the power. If there are any questions,
please contact the supplier of equipments.
Grounding Terminal
Содержание RC2-100AF
Страница 6: ...5 2 2 Compressor outline ...
Страница 7: ...6 ...
Страница 8: ...7 ...
Страница 9: ...8 ...
Страница 10: ...9 ...
Страница 11: ...10 ...
Страница 12: ...11 ...
Страница 13: ...12 ...
Страница 14: ...13 ...
Страница 15: ...14 ...
Страница 16: ...15 ...
Страница 17: ...16 ...
Страница 18: ...17 ...
Страница 19: ...18 ...
Страница 20: ...19 ...
Страница 21: ...20 ...
Страница 22: ...21 ...
Страница 23: ...22 ...
Страница 24: ...23 ...
Страница 25: ...24 ...
Страница 26: ...25 ...
Страница 27: ...26 ...
Страница 85: ...84 Horizontal External Oil Separator OS80 Horizontal External Oil Separator OS100 OS125 OS150 ...