Changing the number of turns 

 
With the DIP switch settings, you can adjust anything between 1 and 31 turns to represent the full signal 
range of 4-20 

mA. Check in the table below. (1 = “On”, 0 = “Off”) 

 
 
 

Total Turns 

Dip4=0 

DIP 5 

DIP 6 

DIP 7 

DIP 8 

reserved 

10 

11 

12 

13 

14 

15 

 
 
 

 

WARNING

: Be sure that the number of turns the actuator is set for is 

LESS

 than the number of 

turns for the valve. The actuator should not stop itself on a fully opened valve. It can damage the 
valve, and the actuator will lose its position.  

 

 
 
 
 

 
 
 
 
 
 
 

 

For more turns, set DIP 4 to the ON position. 

This will add 16 turns to the number set by DIPs 5 
through 8, as shown in the table.

 

 
 

DIP 4=0 

+0 turns 

DIP 4=1 

+16 turns 

 

Содержание RC Series

Страница 1: ...Explosion Proof Actuators 2 Wiring for Non Explosion Proof actuators 4 Power Supply and Current Draw 4 Control Signal and Feedback 5 Operation 6 DIP switches 6 Controlling the Actuator 6 Changing the...

Страница 2: ...ocation should be installed by qualified personnel in accordance with site and local requirements The actuator comes standard with a FNPT thread cable entry See p 14 for location of FNPT housing acces...

Страница 3: ...d cable gland are installed connect the wires to the pins on the terminal block as indicated here Pin Function 6 Already Connected to battery board then transformer board serially Connect live wire to...

Страница 4: ...moving the actuator draws approx 5 mA AC power is connected to the RED BLACK wires with crimp connectors WM18225 DN WM18230 ND 18 22 AWG Ground is connected on the panhead ground screw circled in yell...

Страница 5: ...e actuator 4 20 mA output is internally supplying the signal current and can drive sufficient voltage for any sensing resistor of up to 250 ohms The potential of the external GND after the sensing res...

Страница 6: ...IP 6 and 8 are on then the total turns of the actuator would be five 9 Signal loss See p 10 10 11 Seating Torque Set how much torque the actuator exerts on the valve lever during the calibration findi...

Страница 7: ...0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 5 0 1 0 1 6 0 1 1 0 7 0 1 1 1 8 1 0 0 0 9 1 0 0 1 10 1 0 1 0 11 1 0 1 1 12 1 1 0 0 13 1 1 0 1 14 1 1 1 0 15 1 1 1 1 WARNING Be sure that the number of turns...

Страница 8: ...double the power set by DIP 10 and DIP 11 up to 100 power This pull out function is always enabled Speed and Torque Details The maximum speed of the actuator can be set by using the first two positio...

Страница 9: ...de torque values by 3 To convert in lbs to Nm divide by 9 RCH AC B xxxAx Actuators Speed Torque DIP 1 DIP 2 Time for 1 turn sec DIP 10 DIP 11 Seating Torque in lbs Operating torque is 100 OFF OFF 90 O...

Страница 10: ...ition The default signal position is an absolute actuator position i e not a signal value 3 Re zeroing the actuator and initiating calibration routine The actuator will re zero when the input signal i...

Страница 11: ...anually If the valve is moved with the manual override when its power is turned off it will lose its position and it will need to be re zeroed as described in the Signal Loss and Calibration section T...

Страница 12: ...onths without power being applied The fail safe actuation can be performed for 30 cycles on the charge available in the battery During normal operation from totally discharged the batteries will take...

Страница 13: ...x AC B BxxAx IECEX Standards Editions IEC 60079 0 2017 7th Edition IEC 60079 1 2014 7th Edition Serial number will be engraved on the lid CSA Standards Class I Div 1 Groups B C D T6 Class II Groups E...

Страница 14: ...User Manual RCx B xxxAx 8 09 Page 14 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com ACTUATOR DIMENSIONS RCJ RCL RCM AC B xxxAx models...

Страница 15: ...User Manual RCx B xxxAx 8 09 Page 15 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com RCH AC B xxxAx models...

Страница 16: ...User Manual RCx B xxxAx 8 09 Page 16 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com RCF AC B xxxAx models...

Страница 17: ...User Manual RCx B xxxAx 8 09 Page 17 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com PART NUMBER BREAKDOWN Full Hanbay Part Number...

Страница 18: ...Part Number Refer to part number breakdown for available options Ex proof Certification Info on ex proof ratings and installation instructions Actuator Serial Number This serial number is unique for...

Отзывы: