HAMWORTHY HEATING LTD
36
Wessex ModuMax
mk3
Boilers
500001308/C
APPENDIX A
-
GAS DATA
GAS DATA
97
116
147
196
254
Gas Inlet Connection Pipe Thread Size
R1”
R1
1/4”
Nominal Inlet Pressure Nat Gas (LPG)
-
mbar
20 (37)
Maximum Inlet Pressure Nat Gas (LPG)
-
mbar
25 (45)
Gas Pressure Switch Setting Nat Gas
-
mbar
7
7
7
5
5
Gas Flow Rate (max. per module) Nat Gas
-
m
3
/h
10.4
12.7
15.5
20.9
26.2
Gas Flow Rate (max. per module) LPG
-
m
3
/h
4.0
4.9
6.0
8.1
10.1
Target CO
2
% at High / Low fire Nat Gas ±0.25%
9.0
Target CO
2
% at High / Low fire LPG ±0.25%
10.6
NO
x
emission at 0% O
2
(dry) Nat Gas mg/kWh
39.8
34.3
37.7
39.9
38.8
NO
x
emission at 0% O
2
(dry) LPG mg/kWh
42.0
58.1
69.3
68.6
39.9
GENERAL DATA
BOILER MODEL
Model
-
Condensing
97/194
97/291
97/97
Nat Gas
LPG
Nat Gas
LPG
Nat Gas
LPG
Boiler Input (maximum)
-
kW (Gross)
109.0
106.7
218.0
213.4
327.0
320.1
Boiler Input (maximum)
-
kW (Nett)
98.2
98.2
196.4
196.4
294.6
294.6
Boiler Output kW (maximum) condensing 50/30°C
-
kW
97.2
97.2
194.4
194.4
291.6
291.6
Boiler Output kW (maximum) non condensing
80/60°C
-
kW
95.7
95.7
191.4
191.4
287.1
287.1
Boiler Module Output (minimum) 80/60°C
kW
19.1
Model
-
Condensing
116/116
116/232
116/348
Nat Gas
LPG
Nat Gas
LPG
Nat Gas
LPG
Boiler Input (maximum)
-
kW (Gross)
133.0
130.2
266
260.4
399
390.5
Boiler Input (maximum)
-
kW (Nett)
119.8
119.8
239.6
239.6
359.4
359.4
Boiler Output kW (maximum) condensing 50/30°C
-
kW
116.2
116.2
232.5
232.5
348.7
348.7
Boiler Output kW (maximum) non condensing
80/60°C
-
kW
115.2
115.2
230.4
230.4
345.6
345.6
Boiler Module Output (minimum) 80/60°C
-
kW
23.5
Model
-
Condensing
147/147
147/294
147/441
Nat Gas
LPG
Nat Gas
LPG
Nat Gas
LPG
Boiler Input (maximum)
-
kW (Gross)
163.0
159.5
326
319.1
489
478.6
Boiler Input (maximum)
-
kW (Nett)
146.8
146.8
293.6
293.6
440.3
440.3
Boiler Output kW (maximum) condensing 50/30°C
-
kW
147.4
147.4
294.8
294.8
442.2
442.2
Boiler Output kW (maximum) non condensing
80/60°C
-
kW
142.8
142.8
285.6
285.6
428.4
428.4
Boiler Module Output (minimum) 80/60°C
-
kW
28.7
Model
-
Condensing
196/196
196/392
196/588
Nat Gas
LPG
Nat Gas
LPG
Nat Gas
LPG
Boiler Input (maximum)
-
kW (Gross)
219.0
214.4
428.7
394.4
657
643.1
Boiler Input (maximum)
-
kW (Nett)
197.2
197.2
394.4
394.4
591.6
591.6
Boiler Output kW (maximum) condensing 50/30°C
-
kW
196.3
196.3
392.6
392.6
588.9
588.9
Boiler Output kW (maximum) non condensing
80/60°C
-
kW
191.6
191.6
383.2
383.2
574.8
574.8
Boiler Module Output (minimum) 80/60°C
-
kW
38.6
Model
-
Condensing
254/254
254/508
254/762
Nat Gas
LPG
Nat Gas
LPG
Nat Gas
LPG
Boiler Input (maximum)
-
kW (Gross)
275.0
269.2
550
538.3
825
807.5
Boiler Input (maximum)
-
kW (Nett)
247.6
247.6
495.3
495.3
742.9
742.9
Boiler Output kW (maximum) condensing 50/30°C
-
kW
254.4
254.4
508.7
508.7
763.1
763.1
Boiler Output kW (maximum) non condensing
80/60°C
-
kW
239.8
239.8
479.6
479.6
719.4
719.4
Boiler Module Output (minimum) 80/60°C
-
kW
48.4