HAMWORTHY HEATING LTD
16
Wessex ModuMax
mk3
Boilers
500001308/C
Prior to fitting the flue collector assembly, check all
water and gas connections for soundness.
Lubricate the seals on the boiler flue spigot to ena-
ble easy movement and adjustment.
Adjust and fit the assembled flue collector box to
the boiler flue spigots and fit the condense drain
discharge pipe to the base of the flue using the
fitting supplied.
Figure 5.2.2
-
Flue Header Connection
32mm condense
trap fitted for
connection to drain
5.3 Water Connections:
The following connections are provided on each boiler module;
Figure 5.3.1
-
Rear Water Connections
Flow G1½” Male thread (97 & 116)
Flow G2½” Male thread (147/196/254).
Indicated by a red dot on boiler.
Safety valve R¾ Male thread. Adjacent
to flow connection. Capped when
delivered.
Condense 32mm dia. Male plain. Offset
and below return connection.
Gas R1” Male (97 & 116)
Gas R1
1/4
” Male (147/196/254)
Return G1½” Male thread (97 & 116)
Return G2½” Male thread (147/196/254).
Indicated by a blue dot on boiler.